The BAPI BA/ZPMB-HR-AT-D-BB is a field-configurable Zone Pressure Multi-Sensor (ZPM) in BAPI’s IP66-rated BAPI-Box enclosure. This is the High Range model with five selectable unidirectional pressure ranges up to 0 to 30.0” WC and three field-selectable outputs (4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC). Output, range, units (inches WC or Pascals), response time, and direction are all set via DIP switches without powering the unit. This configuration ships complete with the attached 6” aluminum static pressure probe and an LCD display that shows live pressure for quick commissioning and troubleshooting.
Five Switch-Selectable Ranges
DIP switches SW3–SW5 select between five high range pressure ranges up to 0 to 30.0” WC. Switch SW6 toggles inches WC or Pascals. No re-ordering, no re-stocking, no re-calibration for range changes.
Three Output Types, One SKU
Switches SW1 & SW2 select 4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC output. Powered from 13–40 VDC (4-20 mA) or 7–40 VDC / 18–28 VAC (VDC outputs). Load resistance 850Ω max at 24 VDC for current output, 6 kΩ min for voltage output.
Display + Probe Ready to Install
Ships with the 6” aluminum static pressure probe pre-attached via tubing with surge damper, plus an LCD display that reads live pressure regardless of the selected range. Three face-mounted LEDs provide Out-of-Range Low / In-Range / Out-of-Range High status from across a mechanical room.
Specifications
| BA/ZPMB-HR-AT-D-BB Zone Pressure Multi-Sensor | |
|---|---|
| Model | BA/ZPMB-HR-AT-D-BB |
| Range Class | High Range (Unidirectional only – SW8 disabled on HR units) |
| Selectable Outputs | 4 to 20 mA / 0 to 5 VDC / 0 to 10 VDC (DIP-switch selectable) |
| Display | LCD display shows live pressure regardless of selected range |
| Static Probe | Attached 6” aluminum static pressure probe (included) |
| Accuracy | ±1.0% FS, 32 to 104°F (0 to 40°C), or ±0.3” WC (±74.65 Pa) |
| Total Error Band | ±0.5% FS or ±0.15” WC (±37.33 Pa) |
| Temp Hysteresis & Stability | ±1% FS per year |
| Overpressure | Proof 500” WC (124 kPa) |
| Power (4-20 mA) | 13 to 40 VDC |
| Power (0-5 VDC) | 7 to 40 VDC or 18 to 28 VAC |
| Power (0-10 VDC) | 13 to 40 VDC or 18 to 28 VAC |
| Power Consumption | 20 mA max DC (4-20 mA); 7 mA max DC or 0.58 VA max AC (VDC outputs) |
| Load Resistance | 4-20 mA: 850Ω max @ 24 VDC | Voltage: 6 kΩ min |
| Wiring | 3 wires (2 wires for 4-20 mA output) |
| Port Size | 1/4” barb (6.3 mm) |
| Media | Clean, dry, non-corrosive gases |
| Operating Temp | -4 to 140°F (-20 to 60°C) |
| Storage Temp | -40 to 185°F (-40 to 85°C) |
| Humidity | 0 to 95% RH, non-condensing |
| Dimensions | 4.11” W × 5.49” H × 2.50” D (104.4 × 139.4 × 63.5 mm) |
| Conduit Entry | 1/2” NPSM threaded port with 1/2” drillable knockout |
| Enclosure Material | UV-resistant polycarbonate, UL94 V-0 |
| Enclosure Rating | IP66, NEMA 4 (cover latch screws required) |
| Agency | CE EN 61326-1:2013 EMC (Industrial Electromagnetic Environment), RoHS |
| Warranty | 5-year BAPI manufacturer warranty |
Field-Selectable High Range Pressure Ranges
| Inches WC | Pascals |
|---|---|
| 0 to 5.0 | 0 to 1,250 |
| 0 to 10.0 | 0 to 2,500 |
| 0 to 15.0 | 0 to 4,000 |
| 0 to 25.0 | 0 to 6,000 |
| 0 to 30.0 | 0 to 7,400 |
Frequently Asked Questions
Can this BA/ZPMB-HR-AT-D-BB be configured for bidirectional operation?
No. On High Range ZPMB units the SW8 direction switch is disabled and operation is permanently unidirectional. For bidirectional operation up to ±5” WC, use the Standard Range ZPMB model; for bidirectional operation up to ±1” WC, use the Low Range ZPMB model.
What is included with this attached-probe (-AT) variant?
The BA/ZPMB-HR-AT-D-BB ships with the BAPI-Box pressure sensor, a 6” aluminum static pressure probe connected via tubing and a bulkhead fitting, a surge damper on the probe tube, four self-tapping mounting screws, cover latch screws, and deadhead tubing for the auto-zero procedure.
What does the LCD display show, and does it depend on the selected range?
The LCD displays actual measured pressure continuously, in the selected units (inches WC or Pascals), regardless of which of the five pressure ranges is currently selected. This is independent of the output scaling and is specifically useful for troubleshooting controller scaling and verifying auto-zero.
- Output Signal:
- 4-20 mA, 0-5 VDC, or 0-10 VDC
- Pressure Type:
- Differential
- Pressure Ranges:
- 0 to 30 Inch
- Media:
- Dry
- Accuracy:
- 1.00%
- LCD Display:
- LCD Display
- Zero Function:
- Yes
- Range Setting:
- Adjustable
- Communication:
- None
- Series:
- ZPM Series