null Skip to main content

BAPI BA/ZPMB-LR-AT-ND-BB : Zone Pressure Multi-Sensor (ZPM), ±1% FS Accuracy, 10 Field-Selectable Ranges up to ±1 in WC Bi/Uni-Directional, Field-Selectable Outputs 4-20 mA / 0-5 V / 0-10 V, Attached Static Probe, No Display, IP66/NEMA 4 Enclosure

BAPI

MSRP: $245.00
$96.75
(You save $148.25 )
(No reviews yet) Write a Review
SKU:
BA/ZPMB-LR-AT-ND-BB
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
Range ClassLow Range (±1.00” WC)
Accuracy±1% FS • ±0.02” WC (±4.98 Pa)
Outputs4-20 mA / 0-5 V / 0-10 V
ProbeAttached Static Probe
DisplayNo Display
EnclosureIP66 / NEMA 4 BAPI-Box

The BAPI BA/ZPMB-LR-AT-ND-BB is a field-configurable Zone Pressure Multi-Sensor (ZPM) in BAPI’s IP66-rated BAPI-Box enclosure. This is the Low Range model with ten field-selectable pressure ranges up to ±1.00” WC (five unidirectional and five bidirectional, switchable via DIP switch SW8) and three field-selectable outputs (4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC). Output, range, units (inches WC or Pascals), response time, and direction are all set via DIP switches without powering the unit. This configuration ships complete with the attached 6” aluminum static pressure probe in a cost-optimized configuration without the optional LCD display.

Best for: building pressurization, isolation and cleanroom differential pressure, room-to-room pressure monitoring, fume hood face velocity, and other low-pressure zone applications below 1” WC — where a single SKU needs to cover multiple ranges, units, and output types across a project rather than stocking multiple fixed-range transmitters.

Five Switch-Selectable Ranges

DIP switches SW3–SW5 select between five low range pressure ranges up to 0 to 1.00” WC. Switch SW6 toggles inches WC or Pascals, and SW8 switches between unidirectional and bidirectional operation. No re-ordering, no re-stocking, no re-calibration for range changes.

Three Output Types, One SKU

Switches SW1 & SW2 select 4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC output. Powered from 13–40 VDC (4-20 mA) or 7–40 VDC / 18–28 VAC (VDC outputs). Load resistance 850Ω max at 24 VDC for current output, 6 kΩ min for voltage output.

Attached Probe + Line-of-Sight LEDs

Ships with BAPI’s 6” aluminum static pressure probe pre-attached via tubing with surge damper — a complete duct assembly in one SKU. Three face-mounted status LEDs indicate Out-of-Range Low / In-Range / Out-of-Range High for the configured range.

Specifications

BA/ZPMB-LR-AT-ND-BB Zone Pressure Multi-Sensor
ModelBA/ZPMB-LR-AT-ND-BB
Range ClassLow Range (Bi-Directional, switchable to Unidirectional via SW8)
Selectable Outputs4 to 20 mA / 0 to 5 VDC / 0 to 10 VDC (DIP-switch selectable)
DisplayNo display (status LEDs only)
Static ProbeAttached 6” aluminum static pressure probe (included)
Accuracy±1.0% FS, 32 to 104°F (0 to 40°C), or ±0.02” WC (±4.98 Pa)
Total Error Band±1.25% FS or ±0.025” WC (±6.22 Pa)
Temp Hysteresis & Stability±1% FS per year
OverpressureProof 300” WC (74 kPa)
Power (4-20 mA)13 to 40 VDC
Power (0-5 VDC)7 to 40 VDC or 18 to 28 VAC
Power (0-10 VDC)13 to 40 VDC or 18 to 28 VAC
Power Consumption20 mA max DC (4-20 mA); 7 mA max DC or 0.58 VA max AC (VDC outputs)
Load Resistance4-20 mA: 850Ω max @ 24 VDC  |  Voltage: 6 kΩ min
Wiring3 wires (2 wires for 4-20 mA output)
Port Size1/4” barb (6.3 mm)
MediaClean, dry, non-corrosive gases
Operating Temp-4 to 140°F (-20 to 60°C)
Storage Temp-40 to 185°F (-40 to 85°C)
Humidity0 to 95% RH, non-condensing
Dimensions4.11” W × 5.49” H × 2.50” D (104.4 × 139.4 × 63.5 mm)
Conduit Entry1/2” NPSM threaded port with 1/2” drillable knockout
Enclosure MaterialUV-resistant polycarbonate, UL94 V-0
Enclosure RatingIP66, NEMA 4 (cover latch screws required)
AgencyCE EN 61326-1:2013 EMC (Industrial Electromagnetic Environment), RoHS
Warranty5-year BAPI manufacturer warranty

Field-Selectable Low Range Pressure Ranges

Inches WCPascals
0 to 0.100 to 30
0 to 0.250 to 50
0 to 0.500 to 100
0 to 0.750 to 175
0 to 1.000 to 250
-0.10 to 0.10-30 to 30
-0.25 to 0.25-50 to 50
-0.50 to 0.50-100 to 100
-0.75 to 0.75-175 to 175
-1.00 to 1.00-250 to 250

Frequently Asked Questions

How do I select bidirectional vs. unidirectional mode on the BA/ZPMB-LR-AT-ND-BB?

DIP switch SW8 selects direction. In bidirectional mode a nominal 1” range becomes −1” to +1”; in unidirectional mode the same setting becomes 0” to +1”. Always perform the auto-zero procedure after changing SW8 or any other configuration switch.

What is included with this attached-probe (-AT) variant?

The BA/ZPMB-LR-AT-ND-BB ships with the BAPI-Box pressure sensor, a 6” aluminum static pressure probe connected via tubing and a bulkhead fitting, a surge damper on the probe tube, four self-tapping mounting screws, cover latch screws, and deadhead tubing for the auto-zero procedure.

Can an LCD display be added to the BA/ZPMB-LR-AT-ND-BB later?

No, the display is factory-fitted. If on-board pressure readout is required, order the corresponding –D model: BA/ZPMB-LR-NT-D-BB (no probe, with display) or BA/ZPMB-LR-AT-D-BB (attached probe, with display). Three face-mounted status LEDs are still included on the no-display unit for basic in-range indication.

WARRANTYBAPI backs every ZPMB Zone Pressure Multi-Sensor with a 5-year manufacturer warranty against defects in materials and workmanship. ZOT Supply is an authorized BAPI distributor — contact us for complete warranty terms and technical support.

Output Signal:
4-20 mA, 0-5 VDC, or 0-10 VDC
Pressure Type:
Differential
Pressure Ranges:
0 to 1 Inch
Media:
Dry
Accuracy:
1.00%
LCD Display:
LCD Display
Zero Function:
Yes
Range Setting:
Adjustable
Communication:
None
Series:
ZPM Series