null Skip to main content

BAPI BA/ZPMB-LR-NT-ND-BB : Zone Pressure Multi-Sensor (ZPM), ±1% FS Accuracy, 10 Field-Selectable Ranges up to ±1 in WC Bi/Uni-Directional, Field-Selectable Outputs 4-20 mA / 0-5 V / 0-10 V, No Probe Included, No Display, IP66/NEMA 4 Enclosure

BAPI

MSRP: $227.00
$90.00
(You save $137.00 )
(No reviews yet) Write a Review
SKU:
BA/ZPMB-LR-NT-ND-BB
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
Range ClassLow Range (±1.00” WC)
Accuracy±1% FS • ±0.02” WC (±4.98 Pa)
Outputs4-20 mA / 0-5 V / 0-10 V
ProbeNo Probe (Bulkhead Fitting)
DisplayNo Display
EnclosureIP66 / NEMA 4 BAPI-Box

The BAPI BA/ZPMB-LR-NT-ND-BB is a field-configurable Zone Pressure Multi-Sensor (ZPM) in BAPI’s IP66-rated BAPI-Box enclosure. This is the Low Range model with ten field-selectable pressure ranges up to ±1.00” WC (five unidirectional and five bidirectional, switchable via DIP switch SW8) and three field-selectable outputs (4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC). Output, range, units (inches WC or Pascals), response time, and direction are all set via DIP switches without powering the unit. This configuration includes the bulkhead fitting for a separately ordered static probe in a cost-optimized configuration without the optional LCD display.

Best for: building pressurization, isolation and cleanroom differential pressure, room-to-room pressure monitoring, fume hood face velocity, and other low-pressure zone applications below 1” WC — where a single SKU needs to cover multiple ranges, units, and output types across a project rather than stocking multiple fixed-range transmitters.

Five Switch-Selectable Ranges

DIP switches SW3–SW5 select between five low range pressure ranges up to 0 to 1.00” WC. Switch SW6 toggles inches WC or Pascals, and SW8 switches between unidirectional and bidirectional operation. No re-ordering, no re-stocking, no re-calibration for range changes.

Three Output Types, One SKU

Switches SW1 & SW2 select 4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC output. Powered from 13–40 VDC (4-20 mA) or 7–40 VDC / 18–28 VAC (VDC outputs). Load resistance 850Ω max at 24 VDC for current output, 6 kΩ min for voltage output.

Cost-Optimized with Status LEDs

No-display, no-probe configuration keeps the BAPI-Box form factor, IP66 rating, and field configurability while trimming cost for installations where the controller already shows live pressure. Bulkhead fitting is included for a separately ordered ZPS-ACC07 static probe or custom tubing runs.

Specifications

BA/ZPMB-LR-NT-ND-BB Zone Pressure Multi-Sensor
ModelBA/ZPMB-LR-NT-ND-BB
Range ClassLow Range (Bi-Directional, switchable to Unidirectional via SW8)
Selectable Outputs4 to 20 mA / 0 to 5 VDC / 0 to 10 VDC (DIP-switch selectable)
DisplayNo display (status LEDs only)
Static ProbeNot included (bulkhead fitting provided; order ZPS-ACC07 separately if needed)
Accuracy±1.0% FS, 32 to 104°F (0 to 40°C), or ±0.02” WC (±4.98 Pa)
Total Error Band±1.25% FS or ±0.025” WC (±6.22 Pa)
Temp Hysteresis & Stability±1% FS per year
OverpressureProof 300” WC (74 kPa)
Power (4-20 mA)13 to 40 VDC
Power (0-5 VDC)7 to 40 VDC or 18 to 28 VAC
Power (0-10 VDC)13 to 40 VDC or 18 to 28 VAC
Power Consumption20 mA max DC (4-20 mA); 7 mA max DC or 0.58 VA max AC (VDC outputs)
Load Resistance4-20 mA: 850Ω max @ 24 VDC  |  Voltage: 6 kΩ min
Wiring3 wires (2 wires for 4-20 mA output)
Port Size1/4” barb (6.3 mm)
MediaClean, dry, non-corrosive gases
Operating Temp-4 to 140°F (-20 to 60°C)
Storage Temp-40 to 185°F (-40 to 85°C)
Humidity0 to 95% RH, non-condensing
Dimensions4.11” W × 5.49” H × 2.50” D (104.4 × 139.4 × 63.5 mm)
Conduit Entry1/2” NPSM threaded port with 1/2” drillable knockout
Enclosure MaterialUV-resistant polycarbonate, UL94 V-0
Enclosure RatingIP66, NEMA 4 (cover latch screws required)
AgencyCE EN 61326-1:2013 EMC (Industrial Electromagnetic Environment), RoHS
Warranty5-year BAPI manufacturer warranty

Field-Selectable Low Range Pressure Ranges

Inches WCPascals
0 to 0.100 to 30
0 to 0.250 to 50
0 to 0.500 to 100
0 to 0.750 to 175
0 to 1.000 to 250
-0.10 to 0.10-30 to 30
-0.25 to 0.25-50 to 50
-0.50 to 0.50-100 to 100
-0.75 to 0.75-175 to 175
-1.00 to 1.00-250 to 250

Frequently Asked Questions

How do I select bidirectional vs. unidirectional mode on the BA/ZPMB-LR-NT-ND-BB?

DIP switch SW8 selects direction. In bidirectional mode a nominal 1” range becomes −1” to +1”; in unidirectional mode the same setting becomes 0” to +1”. Always perform the auto-zero procedure after changing SW8 or any other configuration switch.

Does this no-probe (-NT) variant include any probe hardware?

The BA/ZPMB-LR-NT-ND-BB includes the BAPI-Box pressure sensor with bulkhead fitting installed in the enclosure, four self-tapping mounting screws, cover latch screws, and deadhead tubing for auto-zero. A static pressure probe is not included — order the BA/ZPS-ACC07 (6” aluminum static probe) separately if required for the application.

Can an LCD display be added to the BA/ZPMB-LR-NT-ND-BB later?

No, the display is factory-fitted. If on-board pressure readout is required, order the corresponding –D model: BA/ZPMB-LR-NT-D-BB (no probe, with display) or BA/ZPMB-LR-AT-D-BB (attached probe, with display). Three face-mounted status LEDs are still included on the no-display unit for basic in-range indication.

WARRANTYBAPI backs every ZPMB Zone Pressure Multi-Sensor with a 5-year manufacturer warranty against defects in materials and workmanship. ZOT Supply is an authorized BAPI distributor — contact us for complete warranty terms and technical support.

Output Signal:
4-20 mA, 0-5 VDC, or 0-10 VDC
Pressure Type:
Differential
Pressure Ranges:
0 to 1 Inch
Media:
Dry
Accuracy:
1.00%
LCD Display:
LCD Display
Zero Function:
Yes
Range Setting:
Adjustable
Communication:
None
Series:
ZPM Series