null Skip to main content

Belimo 01CT-5QPF1-4 : Cable Temperature Sensor, NTC 20K thermistor, 8" Probe, 9.8 ft Bare Copper Shielded Plenum Cable, Mounting Flange Included, 5-Year Warranty

Belimo

MSRP: $49.00
$22.05
(You save $26.95 )
(No reviews yet) Write a Review
SKU:
01CT-5QPF1-4
Condition:
New
Availability:
Ships Today
Adding to cart… The item has been added
TypeCable Temp Sensor
ElementNTC 20K
Probe Length8"
Range-13 to 167°F
Cable9.8 ft bare copper plenum
EnclosureNEMA 4X / IP67
PowerPassive (no 24V)

The 01CT-5QPF1-4 is a Belimo passive cable temperature sensor with a NTC 20K thermistor sensing element on a 8" stainless steel probe, supplied with 9.8 ft of bare copper shielded plenum cable, black jacket and a plastic mounting flange. It ships with the A-22D-A03 plastic mounting flange installed for single-hole duct mount. The cable jacket is rated to -13 to 167°F; the stainless steel probe handles the same range. The signal returns directly to the controller as a resistance — no 24V supply or signal conditioning required.

Best For

Supply, return, mixed-air, and outdoor-air duct temperature in air handlers and rooftop units when a single-hole duct probe with built-in mounting flange is the fastest install. Pre-integrated flange eliminates a parts pull at the jobsite.

5-YEAR WARRANTY
Backed by Belimo's industry-leading 5-year factory warranty. All units are factory-tested and ship from our West Palm Beach, FL warehouse.

Key Features

NEMA 4X / IP67 Stainless Probe

Stainless steel sensing probe rated NEMA 4X / IP67. Suitable for duct air, mechanical-room environments, and — with a thermowell — direct fluid immersion.

Drift-Resistant Element

Factory-trimmed NTC 20K element delivers stable long-term accuracy with no field calibration required.

Mounting Flange Included

Ships with the A-22D-A03 plastic mounting flange pre-installed for fast single-hole duct mount. No separate parts pull required.

Direct Resistance Output

Passive resistance returns directly to the controller — no 24V supply, no signal conditioning, no scaling required.

9.8 ft Plenum-Rated Cable

9.8 ft of bare copper shielded plenum cable, black jacket runs from the probe directly to the controller terminations — no exterior junction box on the duct.

5-Year Belimo Warranty

Industry-leading factory warranty backed by Belimo's worldwide service network.

Technical Specifications

SpecificationDetail
Sensor StyleCable temperature sensor with stainless steel probe and pre-installed mounting flange
Measured ValueTemperature
Sensing ElementNTC 20K thermistor
Measuring Range-13...167°F [-25...75°C]
Probe Length8" [200 mm]
Probe Diameter0.24" [6 mm]
Probe MaterialStainless steel
Cable9.8 ft [3 m] bare copper shielded plenum cable, black jacket, 22AWG, 2-wire, 300 V
Applicationair (duct mount)
MountingPre-installed mounting flange (single-hole duct mount)
Process ConnectionPlastic flange (included)
Enclosure RatingNEMA 4X / IP67
Protection ClassIEC/EN III, Protective Extra-Low Voltage (PELV)
UL ApprovalcULus per UL60730-1A/-2-9, CAN/CSA E60730-1/-2-9
Power RequiredNone — passive resistance element
Weight0.18 lb
ManufacturerBelimo
Manufacturer Part Number01CT-5QPF1-4
Warranty5-year factory warranty

Compatible Accessories

Mounting flange A-22D-A03 is included with this SKU. For most duct-mount applications, no additional accessories are required. For higher-temperature ducts (above 248°F), consider upgrading to the brass mounting flange.

Higher-Temperature Flange Upgrade

Documentation

Frequently Asked Questions

Does this need 24V power?

No. The 01CT-5QPF1-4 is a passive resistance temperature sensor — the controller reads its element directly through the analog input. No 24V supply or signal conditioner needed.

What sensing element is in the 01CT-5QPF1-4?

The 01CT-5QPF1-4 uses a NTC 20K thermistor. The first letter after '01CT-5' identifies the element: A=Pt 100, B=Pt 1000, E=Ni 1000 (JCI), L=NTC 10K Type II, M=NTC 10K Type III (Precon), Q=NTC 20K. Match this to your controller's input curve.

What does the probe length code mean?

The letter after the element code encodes probe length: H=2", L=4", P=8". This SKU has a 8" probe.

What's included with the F1-4 variant?

The F1-4 ships with the A-22D-A03 plastic mounting flange pre-installed for single-hole duct mount. The cable is 9.8 ft (vs 6.5 ft on the standard variant). The application is air-duct only — for fluid immersion, use the standard 01CT-5.. variant with a thermowell.

Can I use this on a water or chilled-water line?

No — the F1-4 variant is rated for air duct only. For liquid immersion in chilled water, hot water, or condenser water, use the standard 01CT-5.. variant with a matching length thermowell from the A-22P-A.. series.

Does it work with my BAS?

Any BAS controller with a temperature input configured for the NTC 20K curve will read this sensor directly. See the linked Resistance Characteristics PDF for the full curve table at standard temperature points.

How is this different from the 01DT duct sensor?

The 01DT mounts in a NEMA 4X polymer enclosure on the duct exterior with terminals inside the box. The 01CT terminates directly via the cable — no exterior junction box, cleaner installs into a controller panel. Both use the same passive elements and the same family of thermowells when used for liquid immersion.

Sensor Type:
Probe with Mounting Flange
Probe Length:
8 Inch
Temperature Element:
20K Thermistor
Lead Length:
10 Foot Plenum Rated Cable
Enclosure:
No Box
Supported Protocols:
None
Humidity Element:
None
CO2 Element:
None
Setpoint:
No Setpoint
Override:
No Override
Display: