ACI PXP2.3GFS : Analog Input (0-5VDC), Pressure Output (0-15PSI), Dual Valve, Exhausts on Power Failure, Gauge, (0-10V, 0-15V, 0-20mA Selectable)
The PXP*.3 is an electric-to-pneumatic transducer that converts an analog electrical input signal into a proportional pneumatic output. It automatically adjusts its control valve(s) to maintain the branch line pressure at a selected set point determined by the input signal. The PXP*.3 offers four selectable input ranges, resulting in a 0 to 15 psig modulating output (note that the EPC product provides 0 to 20 psig outputs). It also provides a 0-5 VDC feedback signal that corresponds linearly to the branch pressure (0 volts = 0 psig, 5 volts = 15 psig).
PXP2.3 incorporates two valves and doesn't use air at the set point. Its branch exhaust flow and response time are similar to the load rate. If power fails to the PXP2.3 and there's no air leakage in the branch line, the branch line pressure remains constant. PXP2.3FS is equipped with a normally open branch exhaust valve to release branch air on power failure. It also has a manual override (jumper selectable) for adjusting the output pressure, and custom calibration is available upon request for an additional charge, which can expedite installation.
These devices are suitable for various applications, including Three-Way Mixing Valve Control, Pilot Positioner Control, Pneumatic Valve & Damper Actuator Control, Fan Vane Control, DDC Control, and Above Ceiling Applications involving mixing and VAV boxes.
Specifications
Supply Voltage: | 24 VAC (+/-10%), 50 or 60Hz, 24 VDC (+10%/- 5%) |
Supply Current: | 160 mA maximum, 200 mA on fail safe models |
Input Signal Source (@ Impedance): | 0-5 VDC @ 10,000 Ω | 0-10 VDC @ 10,000Ω | 0-15 VDC @ 10,000Ω | 0-20 mA @ 250Ω |
Feedback Signal Output Range: | 0-5 VDC = Output Span |
Output Pressure Range: | Field Calibration Possible: 0 to 15 psig (0-103.421 kPa) maximum |
Air Supply Pressure: | Maximum: 25 psig (172.369 kPa) | Minimum: 18 psig (124.106 kPa) |
Air Consumption: | See Ordering Grid |
Output Pressure Accuracy: | 1% full scale @ room temperature | 2% full scale across operating temperature range |
Manual / Auto Override: | MAN function = output can be varied | AUTO function = output is controlled from input signal |
Air Flow: | Supply valves @ 20 psig (138 kPa) main/15 psig (103 kPa) out, 750 scim (1400 on LG model) Branch Line requires 2 in3 or 33.78 cm3 (min.). Branch line min. of 25 feet of 1/4” O.D. poly tubing |
Filtering: | Furnished with integral-in-barb 80-100 micron filter (Part # PN004) except for PXP2LG which is furnished with external 5 micron in-line filter (PN021) |
Connections: | 90° Pluggable Screw Terminal Blocks |
Wire Size: | 16 (1.31 mm2) to 26 AWG (0.129 mm2) |
Terminal Block Torque Rating: | 0.5 Nm (Minimum); 0.6 Nm (Maximum) |
Connections | Pneumatic Tubing Size-Type: | 1/4" O.D. nominal (1/8” I.D.) polyethylene |
Pneumatic Fitting: | Removeable brass barbed fittings for Main and Branch in machined aluminum manifold Plugged 1/8-27-FNPT gauge port | Gauge installed at additional cost |
Gauge Pressure Range (Gauge Models): | 0-30 psig (0-200 kPa) |
Gauge Pressure Accuracy (Gauge Models): | ± 2.5% Midscale (± 3.5% Full Scale) |
Operating Temperature Range: | 35 to 120°F (1.7 to 48.9°C) |
Operating Humidity Rage: | 10 to 95% non-condensing |
Storage Temperature: | -20 to 150°F (-28.9 to 65.5°C) |
Snaptrack Material: | Polyvinyl Chloride (PVC) |
Snaptrack Flammability Rating: | UL94 V-0 |
Product Dimensions: | No Gauge: (L) 3.25” (W) 2.18” (H) 1.87” (82.55 x 55.37 x 47.49 mm) With Gauge: (L) 3.25” (W) 2.18” (H) 2.95” (82.55 x 55.37 x 74.9 mm) |
Product Weight: | PXP1.3: 0.40 lbs. (0.1814 Kg) | PXP2.3: 0.47 lbs. (0.2126 Kg) | PXP1.3G: 0.49 lbs. (0.2211 Kg) PXP2.3G & PXP2.3GFS: 0.59 lbs. (0.2693 Kg) |
Agency Approvals: | RoHS2, WEEE |
Data Sheets
- Input Signal:
- Analog
- Output Signal:
- Pressure
- Guage:
- With Gauge
- Failsafe:
- With Failsafe
- Valves:
- 2 Valves