null Skip to main content

BAPI BA/ZPM-HR-ST-ND : Zone Pressure Multi-Sensor (ZPM), ±0.25% FS Accuracy, 5 Field-Selectable Ranges up to 30 in WC Unidirectional, 5 Selectable Outputs 4-20mA to 1-5V, Static Probe Included, No Display, IP44/NEMA 2 Enclosure

BAPI

MSRP: $409.00
$162.00
(You save $247.00 )
(No reviews yet) Write a Review
SKU:
BA/ZPM-HR-ST-ND
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
Range ClassHigh Range (0 to 30” WC)
Accuracy±0.25% FS
Outputs4-20 mA / 0-5 V / 0-10 V / 2-10 V / 1-5 V
ProbeStatic Probe Included
Display3-Color LED Status
EnclosureIP44 / NEMA 2

The BAPI BA/ZPM-HR-ST-ND is a field-configurable Zone Pressure Multi-Sensor (ZPM) in BAPI’s standard IP44/NEMA 2 enclosure. This is the High Range model with five field-selectable unidirectional pressure ranges up to 0 to 30” WC (DIRECTION switch disabled on HR boards — unidirectional only) and five field-selectable output signals (4 to 20 mA, 0 to 5 VDC, 0 to 10 VDC, 2 to 10 VDC, or 1 to 5 VDC). Output, range, units (inches WC or Pascals), directionality, and response time are all set via DIP switches without powering the unit. A NIST-traceable calibration certificate is included at no extra charge. This configuration ships with a static pressure probe included in the package — ready to install without a separate probe order and features a 3-color LED status indicator (Out of Range Low / In Range / Out of Range High) for at-a-glance line-of-sight pressure status.

Best for: High-velocity duct static pressure, AHU discharge, filter bank pressure drop monitoring, and other applications in the 5–30” WC range. Unidirectional only — the DIRECTION switch is disabled on HR boards.

5 Field-Selectable Ranges

DIP switches select between five high range pressure ranges up to 0 to 30” WC. No re-ordering or re-stocking when the application changes.

Five Output Signals — One SKU

DIP-switch selectable: 4 to 20 mA, 0 to 5 VDC, 0 to 10 VDC, 2 to 10 VDC, or 1 to 5 VDC. All five outputs are native — no multiplexing. Power 7–40 VDC for 4-20 mA; 7–40 VDC or 18–32 VAC for VDC outputs.

Static Probe Included + LED Status

Ships with a static pressure probe in the package for immediate installation. Three face-mounted LEDs provide at-a-glance pressure status without BAS access. NIST-traceable calibration certificate included at no extra charge.

Full Specifications

BA/ZPM-HR-ST-ND Zone Pressure Multi-Sensor
ManufacturerBuilding Automation Products, Inc. (BAPI)
SeriesZPM – Zone Pressure Multi-Sensor
Part NumberBA/ZPM-HR-ST-ND
Sensor TypePiezoresistive differential, dry media only
Pressure Range0 to 30” WC max (unidirectional only)
Field-Selectable Ranges5
Accuracy±0.25% FS at 77°F (25°C) • ±0.075” WC (±18.66 Pa)
Total Error Band±0.5% FS or ±0.15” WC (±37.33 Pa)
Output Signals4-20 mA / 0-5 VDC / 0-10 VDC / 2-10 VDC / 1-5 VDC (DIP-switch selectable)
Power Supply7 to 40 VDC (4-20 mA); 7 to 40 VDC or 18 to 32 VAC (0-5 / 1-5 VDC); 13 to 40 VDC or 18 to 32 VAC (0-10 / 2-10 VDC)
Power Consumption20 mA max DC (4-20 mA) • 5.2 mA max DC (VDC outputs) • 0.12 VA max AC (VDC outputs)
Load Resistance4-20 mA: 850Ω max @ 24 VDC • VDC: 6 kΩ min
Display / Indication3-color LED: Out of Range Low / In Range / Out of Range High
Zero AdjustPush-button auto-zero on front panel
Range SettingDIP-switch selectable without power
Probe OptionStatic pressure probe included in package (not pre-attached)
Enclosure MaterialUV-resistant Polycarbonate, UL94 V-0
Enclosure RatingIP44, NEMA 2
Enclosure Dimensions4.51 x 3.63 x 2.22” (115 x 92 x 57 mm) L x W x H
Pressure Port1/4” barb (6.3 mm)
Wiring2-wire (4-20 mA loop) or 3-wire (VDC outputs)
Operating Temperature−4 to 140°F (−20 to 60°C)
Storage Temperature−40 to 185°F (−40 to 85°C)
Humidity0 to 95% RH, non-condensing
OverpressureProof 350” WC (87 kPa)
AgencyCE EN 61326-1:2013 EMC (Industrial), UL, RoHS
NIST CertificateIncluded at no extra charge
Warranty5 Years

Field-Selectable Ranges

Note: High Range boards are unidirectional only. The DIRECTION switch is disabled on HR units; all five ranges read positive pressure only.

#Unidirectional RangePascals
10 – 5.0” WC0 – 0 to 1,250 Pa
20 – 10.0” WC0 – 0 to 2,500 Pa
30 – 15.0” WC0 – 0 to 4,000 Pa
40 – 25.0” WC0 – 0 to 6,000 Pa
50 – 30.0” WC0 – 0 to 7,400 Pa

Frequently Asked Questions

What is the accuracy of the BAPI ZPM High Range?

±0.25% of full scale at 77°F (25°C), equivalent to ±0.075” WC (±18.66 Pa) for the High Range. Total Error Band (covering non-linearity, hysteresis, and thermal effect across the compensated range of 32 to 122°F) is ±0.5% FS or ±0.15” WC (±37.33 Pa). Long-term stability is ±0.25% FS per year. A NIST-traceable calibration certificate is included at no extra charge.

What output signals does the BA/ZPM-HR-ST-ND support?

Five outputs are DIP-switch selectable: 4 to 20 mA (2-wire loop), 0 to 5 VDC, 0 to 10 VDC, 2 to 10 VDC, and 1 to 5 VDC. All five are native outputs — not multiplexed. Power requirements differ by output: 7–40 VDC for 4-20 mA; 7–40 VDC or 18–32 VAC for 0-5 / 1-5 VDC; 13–40 VDC or 18–32 VAC for 0-10 / 2-10 VDC.

Can the High Range ZPM read negative pressure?

No. High Range boards are unidirectional only — the DIRECTION switch present on SR and LR boards is disabled on HR. All five high ranges read positive pressure only (0 to +range). For bidirectional high-range sensing, use two HR units plumbed in opposite directions or step down to an SR unit.

WARRANTYBAPI backs every ZPM Zone Pressure Multi-Sensor with a 5-year manufacturer warranty against defects in materials and workmanship. ZOT Supply is an authorized BAPI distributor — contact us for complete warranty terms and technical support.

0 to 5 VDC
Output Signal:
4-20 mA, 0-5 VDC, or 0-10 VDC
Pressure Type:
Differential
Pressure Ranges:
0 to 30 Inch
Media:
Dry
Accuracy:
0.25%
LCD Display:
3-Color LED
Zero Function:
Yes
Range Setting:
Adjustable
Communication:
None
Series:
ZPM Series