null Skip to main content

Belimo 22DTH-56M : Active Duct Humidity + Temperature Sensor, BACnet MS/TP RH, Active Temp Output, NFC Config, BACnet MS/TP, 24 VAC/VDC, 5-Yr Warranty

Belimo

MSRP: $619.00
$278.55
(You save $340.45 )
(No reviews yet) Write a Review
SKU:
22DTH-56M
Condition:
New
Availability:
Ships Today
Adding to cart… The item has been added
TypeDuct Humidity + Temp
RH OutputBACnet MS/TP
Temp OutputActive V/mA temp
Range0-100% RH / -30 to 160°F
Power24 VAC/VDC
CommsBACnet MS/TP

The 22DTH-56M is a Belimo active 24V duct humidity and temperature sensor for measuring relative humidity (or absolute humidity / dewpoint / enthalpy — selectable) and temperature in air ducts. The active humidity output is BACnet MS/TP (RS-485) with 0–10V analog backup outputs. The temperature output is active and matches the humidity output type (V or mA). Communicates with the BAS via BACnet MS/TP on RS-485, with 0-10V analog backup outputs preserved for redundancy or for controllers that prefer to read both protocols. The orange UV-resistant polycarbonate housing mounts to the duct exterior; the probe penetrates through a single mounting hole.

Best For

Supply, return, and mixed-air duct humidity and temperature monitoring for demand-controlled ventilation, dehumidification staging, dewpoint-based freeze protection, and economizer changeover. Single sensor consolidates two BAS inputs at one duct location.

BACnet MS/TP Communication

This SKU communicates with the BAS via BACnet MS/TP over RS-485 as a native BACnet device — all sensor values exposed as BACnet objects, fully discoverable through standard BACnet device discovery. The 0-10V analog backup outputs remain available. BACnet device instance, MS/TP MAC address, and baud rate are configurable via the Belimo Duct Sensor Assistant App.

5-YEAR WARRANTY
Backed by Belimo's industry-leading 5-year factory warranty. ZOT Supply is an authorized Belimo distributor with fast nationwide and international shipping — every unit ships factory-tested with full warranty support.

Key Features

BACnet MS/TP Native Communication

All sensor values and configuration parameters are exposed via BACnet MS/TP over RS-485. Discoverable as a native bus device — no analog scaling, no standalone wiring per signal. Analog 0-10V backup outputs remain available for redundancy or for non-bus consumers.

4 Selectable Humidity Output Modes

Configure the humidity output channel to deliver relative humidity, absolute humidity, dew point, or enthalpy via NFC. Default is %RH; change in the field via the Belimo Duct Sensor Assistant App without re-wiring or removing the sensor.

Polymer Capacitive Humidity Sensor

±2% RH accuracy across 0-80% RH at 77°F. Long-term stability ±0.3% RH per year. Stainless steel wire mesh filter protects the polymer element from particulate contamination. 10-second time constant in moving air.

NFC Configuration via Mobile App

Tap a phone with NFC to the housing to read live values, change output mode, adjust CO2/dewpoint range mappings, set Modbus/BACnet addresses (where applicable), and view diagnostics. The Belimo Duct Sensor Assistant App is free for iOS and Android.

NEMA 4X / IP65 Outdoor-Rated Housing

UV-resistant polycarbonate enclosure with NBR70 seal. UL94 5VA flame class and UL 2043 plenum compliant for return-air ducts.

5-Year Belimo Warranty

Industry-leading factory warranty backed by Belimo's worldwide service network.

Selectable Humidity Output Modes

The active humidity output channel can be configured to deliver any of four values via NFC and the Belimo Duct Sensor Assistant App. The default is relative humidity (%RH) — change the mode in the field to match your control logic.

Output ModeRangeTypical Use
Relative Humidity (%RH)0–100% RH non-condensingDefault — most common BAS humidity input
Absolute Humidity0–50 g/m³ (default) or 0–80 g/m³For dehumidification control, dewpoint-based loads
Dew Point40–140°F (default) or 0–200°FFor condensation prevention on chilled surfaces
Enthalpy0–85 kJ/kgFor economizer changeover (energy-based instead of dry-bulb)

Technical Specifications

SpecificationDetail
Sensor StyleDuct Humidity / Temperature Sensor
Measured ValuesRelative humidity, absolute humidity, dew point, enthalpy, temperature
Humidity Sensing ElementPolymer-based capacitive sensor with stainless steel wire mesh filter
Humidity Measuring Range0–100% RH non-condensing
Humidity Accuracy±2% RH between 0–80% RH at 77°F (25°C)
Humidity Long-Term Stability±0.3% RH per year at 70°F (21°C), 50% RH
Humidity Time Constant τ (63%)Typical 10 s @ 3 m/s air velocity
Humidity OutputBACnet MS/TP (RS-485) with 0–10V analog backup outputs — min. 10 kΩ load on backup outputs
Temperature Sensing ElementActive Pt 1000 (1/3 DIN)
Temperature OutputActive BACnet MS/TP (RS-485) with 0–10V analog backup outputs
Temperature Measuring Range-30 to 160°F (-35 to 70°C)
Temperature Accuracy±0.5°F (±0.3°C) — varies by element, see datasheet for full detail
Communication ProtocolBACnet MS/TP
Communication InterfaceRS-485, half-duplex
Bus ConfigurationConfigurable via NFC / Belimo Duct Sensor Assistant App
Analog Backup Outputs2× 0-10V (humidity + temperature) — preserved alongside bus communication
Default Output Mode (Humidity)Relative humidity (%RH); change via NFC to absolute / dewpoint / enthalpy
NFC ConfigurationYes — Belimo Duct Sensor Assistant App (iOS / Android)
ApplicationAir duct
MountingSingle-hole duct penetration; A-22D-A34 mounting flange and 1/2" NPT conduit adapter included
Power Supply24 VAC/VDC (19–29 VAC, 15–35 VDC)
Power Consumption4.3 VA AC / 2.3 W DC
Electrical ConnectionPluggable spring-loaded terminal block, max 2.5 mm²
Cable Entry1/2" NPT conduit adapter included; cable gland with strain relief, ø6...8 mm
HousingUV-resistant polycarbonate, orange — UL94 5VA
Enclosure RatingNEMA 4X / IP65 (UL Enclosure Type 4X), UL 2043 plenum compliant
Protection ClassIEC/EN III, SELV; UL Class 2 supply
UL ApprovalcULus per UL60730-1A/-2-9, CAN/CSA E60730-1/-2-9
ManufacturerBelimo
Manufacturer Part Number22DTH-56M
Warranty5-year factory warranty

What's In the Box

Complete Install Kit
  • 22DTH-56M active humidity + temperature transmitter in orange UV-resistant housing
  • A-22D-A34 mounting flange (plastic, up to 248°F / 120°C)
  • 1/2" NPT conduit adapter
  • Mounting screws and dowels

Documentation

Frequently Asked Questions

What does the 22DTH-56M measure and output?

It measures duct air humidity and temperature and outputs both as analog signals. The humidity output is BACnet MS/TP (RS-485) with 0–10V analog backup outputs; the temperature output is an active analog signal matching the humidity output type. The humidity channel is also configurable via NFC to output absolute humidity, dew point, or enthalpy instead of %RH.

How do I configure the humidity output mode?

Tap an NFC-equipped phone with the Belimo Duct Sensor Assistant App against the housing. The app reads the current configuration, lets you switch the humidity output between %RH, absolute humidity, dew point, or enthalpy, and writes the new configuration back to the sensor — all without removing the sensor or disconnecting wires. Default is %RH. The app is free for iOS and Android.

Why does this SKU have an active temperature output instead of a passive RTD?

This variant ships with both outputs as ACTIVE analog signals — the temperature output matches the humidity output type (BACnet MS/TP). For a PASSIVE RTD temperature output (Pt 1000, Ni 1000 JCI, NTC 10K Type II, NTC 10K Type III, or NTC 20K) instead, choose the appropriate suffix variant — e.g. 22DTH-51MB (Pt 1000), 22DTH-51ML (NTC 10K II). Active outputs are simpler to wire (two signal pairs); passive RTDs are necessary when your controller's temperature input is wired for a specific resistance curve.

Does the BACnet MS/TP version still expose analog outputs?

Yes. The BACnet MS/TP version exposes all sensor values as bus objects AND maintains 2× 0-10V analog backup outputs (humidity + temperature). You can wire the analog outputs as a redundant feed, leave them unconnected, or use them to drive non-bus equipment (e.g. an analog damper actuator) while the BAS reads the bus values. This is useful for migration scenarios where the BAS is bus-native but field equipment is still analog.

How do I configure the BACnet MS/TP address and baud rate?

Use the Belimo Duct Sensor Assistant App via NFC. The app exposes all communication parameters — address, baud rate, parity (Modbus), MAC address (BACnet), device instance (BACnet) — and writes them to the sensor without taking it offline.

What is the difference between humidity, dewpoint, and enthalpy as control inputs?

Relative humidity (%RH) tells you how saturated the air is at its current temperature — the most common input for indoor humidity control and dehumidification. Absolute humidity (g/m³) gives the total moisture content regardless of temperature — useful for mass-balance ventilation calculations. Dewpoint tells you the temperature at which moisture will start condensing — ideal for chilled-surface condensation prevention. Enthalpy (kJ/kg) is the total energy content of the air (sensible + latent) — the preferred input for ASHRAE-compliant economizer changeover, where the comparison should be energy-based rather than dry-bulb-temperature-based. Configure the output to match your control sequence.

Does it need 24V power?

Yes. Power is 24 VAC or 24 VDC. Power consumption is 4.3 VA AC / 2.3 W DC (higher than analog-only variants due to the active bus interface).

Sensor Type:
Duct
Output Signal:
Humidity + Temperature
Humidity Output:
BACnet MS/TP (RS-485) with 0–10V analog backup outputs
Temperature Output:
Active analog temperature output (matches humidity output type)
Power:
24 VAC/VDC
Humidity Element:
Polymer Capacitive
Temperature Element:
Active Transmitter (matches output)
Selectable Humidity Modes:
RH / Absolute / Dew Point / Enthalpy
Default Humidity Mode:
Relative Humidity (%RH)
NFC Configuration:
Yes (Belimo Duct Sensor Assistant App)
CO2 Element:
None
VOC Element:
None
Display:
No Display
Setpoint:
No Setpoint
Override:
No Override
Supported Protocols:
BACnet MS/TP
Enclosure:
NEMA 4X Enclosure