Belimo ZK2-GEN : Cable for use with ZTH-GEN, ZTH US, or ZIP-USB-MP US to connect to actuators not equipped with diagnotic programming socket
To connect to a spring return actuator you will use the ZK2-GEN cable since these actuators do not have service ports. The cable has a phone jack on one end and three wires on the other. Connect the phone jack to the MP port of the ZTH US and then match the wire colors to the labels on the cable. The white wire from the cable connects to the black wire on the actuator, the blue wire connects to the red wire on the actuator, and the turquoise wire connects to the orange or feedback wire on the actuator. For the LF Spring Return MFT actuators, they do not have an orange feedback wire, but there will be a wire that is labeled number five, so you're going to use the number five feedback wire.