Functional Devices RIBMN24Q4C-PX : 4 Output Field Adjustable Staging Threshold Relay Module, 24 Vac/dc Power Input, 0-10 Vdc Control Input, 2.75" Track Mount
SPECIFICATIONS
# Relays & Contact Type: Four (4) SPDT Continuous Duty Coil
Expected Relay Life: 10 million cycles minimum mechanical
Operating Temperature: -30 to 140° F
Humidity Range: -30 to 140° F
Power Status: Green LED On = Power On
Relay Status: Red LED On = Relay Activated
Heartbeat Status: Right-most decimal point
Dimensions: 4.950" x 2.750" x 1.750"
Track Mount: MT212-4 Mounting Track Provided
Approvals: UL Listed, UL916, C-UL, CE, RoHS
Gold Flash: No
Override Switch: No
Contact Ratings:
15 Amp General Use @ 125 Vac
10 Amp General Use @ 277 Vac
10 Amp Resistive @ 30 Vdc (N/O)
7 Amp Resistive @ 30 Vdc (N/C)
1/2 HP @ 125 Vac
1 HP @ 250 Vac
1/4 HP @ 277 Vac
470 VA Pilot Duty @ 125 Vac
770 VA Pilot Duty @ 250 Vac
Power Input:
24 Vac/dc ; 50-60 Hz
200mA max.
Notes:
- For AC applications, an isolation transformer, to be used solely for the power input, is recommended.
- Relay will activate when control signal voltage reaches or exceeds individual relay ON point. Relay will deactivate when control voltage reaches or drops below individual OFF point.
- Factory relay ON / OFF voltages:
- Relay 1: 3V / 2.8V
- Relay 2: 5V / 4.8V
- Relay 3: 7V / 6.8V
- Relay 4: 9V / 8.8 V
- Minimum ON point: 0.5V
- Maximum ON point: 9.9V
- Minimum OFF point: 0.3V
- Relay number will flash 3 times when voltage exceeds setpoint.
- Pressing UP or DN button in normal run mode will display the voltage present on Analog Input.
- ON/OFF points can be changed at any time, by the user, by entering “Program Mode";
- User defined ON/OFF points will be maintained upon power loss.
- Number of Relays:
- 4