Functional Devices RIBMNA1D0 : Manual Analog Override Switch + Monitor, 24 Vac/dc Power Input, 2.75" Track Mount
SPECIFICATIONS
Operating Temperature: -30 to 140° F
Humidity Range: 5 to 95% (noncondensing)
Dimensions: 2.450" x 2.750" x 1.270"
Track Mount: 2.750";,MT212 Mounting Track Sold Separately
Input Voltage: 24 Vac/dc
Input Current: 90mA Max.
Range/Impedance Override:
- 0-5 Vdc, 200 Ω Min.
- 0-10 Vdc, 400 Ω Min.
- 0-15 Vdc, 1 kΩ Min.
- 0-20mA dc, 500 Ω Max.
Feedback Contact: 2A Max. @ 24 Vac/dc
Notes:
-
Set the jumpers according to your input signal (Analog signal from the controller.) Example: When controlling a damper with 0-10 Vdc, the jumpers need to be in position for the 0-10 Vdc override range. If the LED range does not match your analog scale, ensure the jumpers are set for the proper range.
-
Feedback contact closed when switch is in Manual position, open when switch is in Auto position.