Schneider Electric SE7652W5045 : Water Source Heat Pump Room Controller, Local Scheduling/Programmable, 2H/2C, PIR ready but PIR cover not included, Stand Alone Network Ready
Product Highlights
- 2 digital inputs
- Smart fan operation
- Unique configuration key with password
- Lockable keypad
- 6 hour reservable time for clock
- Remote room and outdoor temperature sensor
- Auxiliary output
- Discharge air sensor
- Intuitive menu-driven programming Options and accessories
- Intuitive menu-driven programming
- Economizer output 0-10 Vdc
- 3Heat/2Cool for heat pump models
Specifications
Power Requirements | 19-30Vac, 50/60 Hz; 2 VA (RC & C) Class 2 RC to RH jumper 2.0 Amps 48 VA maximum |
Temperature Sensor | Local 10 K NTC thermistor |
Digital Inputs | Relay dry contact only across C terminal to DI1 or DI2 |
Contact Output Rating | Each relay output: ( Y1, Y2, G, W1, W2 & AU ) 30 Vac, 1 Amp. maximum 30 Vac, 3 Amp. in-rush |
Economizer Analog Output Rating | 0 to 10 Vdc into 2KΩ resistance min. |
Wire Gauge | 18 gauge maximum, 22 gauge recommended |
Datasheets
Schneider Electric SE7652W5045 Data Sheet | |
Schneider Electric SE7000 Series Application Guide |
- Application:
- Water Source Heat Pump
- Sub-Category:
- SE7600 Series
- Occupancy:
- None
- Communication:
- Standalone