Schneider Electric SE7656E5045B : Indoor Air Quality Room Controller, Local Scheduling/Programmable, Economizer, 2H/2C, PIR ready but PIR cover not included, BACnet MS/TP Communication
The Schneider ElectricTM SE7600E IAQ controller, along with a CO2 sensor, is a cost-effective solution capable of controlling economiser-free cooling and IAQ demand-based ventilation strategy while providing a fresh air measurement input right outof the box. The Schneider Electric IAQ controller replaces the need for custom programmed DDC controllers and sensors to achieve the same results as in the past. When connected to a building automation system, the Schneider Electric IAQ controller can monitor and verify CO2 and fresh air levels, ensuring air quality and energy efficiency is optimised.
Product Highlights
- 2 digital inputs
- Smart fan operation
- Unique configuration key with password
- Lockable keypad
- 6 hour reservable time for clock
- Remote room and outdoor temperature sensor
- Auxiliary output
- Discharge air sensor
- Intuitive menu-driven programming Options and accessories
- Intuitive menu-driven programming
- Economizer output 0-10 Vdc
- 3Heat/2Cool for heat pump models
Specifications
Power Requirements | 19-30Vac, 50/60 Hz; 2 VA (RC & C) Class 2 RC to RH jumper 2.0 Amps 48 VA maximum |
Temperature Sensor | Local 10 K NTC thermistor |
Digital Inputs | Relay dry contact only across C terminal to DI1 or DI2 |
Contact Output Rating | Each relay output: ( Y1, Y2, G, W1, W2 & AU ) 30 Vac, 1 Amp. maximum 30 Vac, 3 Amp. in-rush |
Economizer Analog Output Rating | 0 to 10 Vdc into 2KΩ resistance min. |
Wire Gauge | 18 gauge maximum, 22 gauge recommended |
Datasheets
Schneider Electric SE7656E5045B Datasheet | |
Schneider Electric SE7000 Series Application Guide |
- Application:
- Indoor Air Quality
- Sub-Category:
- SE7600 Series
- Occupancy:
- None
- Communication:
- BACnet