Senva CM02SV-480 : Enhanced Core Module, 160-480 VAC L-L / 0.1A, 50 Hz (Combined Sensing And Power Supply Input); Used For 3W Applications Where Neutral Is Not Available
The Core Module Multi-Circuit Monitoring System is designed to measure the current, voltage, and energy consumption and other critical power parameters on up to 96 circuits. Current transformers are connected via a variety of Interface Boards optimized for different applications that connect to the Core Module via network cables. Each Interface Card monitors up to 24 circuits and the Core Module hosts up to four interface cards. The Core Module can communicate via Modbus TCP/IP, Modbus RTU as well as provides access to real time and logged data via an on board web server. Data is also transmitied wirelessly via an option cellular modem. Logged data can reside directly on the Core Module or on SD storage card with up to 32 GB capacity. The Core Module also monitors two digital inputs and provides two digital outputs.
Specifications
Inputs | |
Input power (standard) | 90-277 VAC (480 VAC 4W+G) 50/ 60 Hz |
Input power (enhanced) | 480-600 VAC (3W or 4W+G) 50/ 60 Hz |
Voltage connection Terminals | 22-14 AWG |
Overload protection | Internally fused |
Power Consumption | <5W / 0.1 A @ 240 VAC |
Channels / circuit capacity | 24 x 4 channels (96 circuits total) |
Performace | |
Accuracy | 0.50% |
Sampling Rate | > 3 kHz |
Communications | |
Data protocols | Modbus TCP/IP (Ethernet), Modbus RTU (RS-485 2 wire), HTML (web server) |
Modbus serial specifications | 9600, 19200, 38400 Baud (selectable) |
Ethernet Ports | 2 z RJ-45 10/100 Mbit |
USB port | USB 2.0 Type A |
Web Server | HTML via Standard Browser |
WiFi option | 802.11 g/n ; requires WiFi option |
Cellular option | CAT 1 / CAT M1; requires subscription |
Datasheets
Senva Multi-Circuit & Branch Circuit Monitoring System | |
Senva Core Module Installation Guide |
- Meter Type:
- Multi-Circuit
- Mounting:
- Din Mount
- Supported Protocols:
- Modbus TCP/RTU