The Senva P6-4000-1LP is part of the Senva P6 Pro Series - the premium NEMA 4 universal dry pressure transmitter in Senva's lineup. Built for harsh and washdown environments, this unit's 0-40 in WC / 0-10000 Pa base scales to 10 field-selectable sub-ranges (via internal rotary dial) with field-selectable output signal (4-20 mA 2-wire loop, 4-20 mA 3-wire, 0-5 VDC, or 0-10 VDC), field-selectable direction (uni or bi), field-selectable display units (inches WC or pascals), and field-selectable response rate (2-second fast or 8-second slow). LCD display is standard. The watertight gasketed cover and integrated cable gland maintain NEMA 4 rating in wet, dusty, or washdown-clean environments where NEMA 1 transmitters can't be deployed. This is the Duct Probe variant - NEW for the P6: the duct probe variant now ships with both the threaded duct probe AND the dual brass barbs on the same unit. The probe screws into the back of the enclosure for direct in-duct mounting, with the unused barb capped (to maintain NEMA 4 rating). Alternatively, plumb tubing to the barbs and use the unit panel-mounted - one SKU covers both installation methods.
WARRANTY
Key Features
NEMA 4 Washdown Enclosure
Watertight, dust-tight, hose-down rated housing with gasketed cover and integrated watertight cable gland. UL94-5VB ABS construction. The right pick for kitchen exhaust, food/pharma plants, parking garages, indoor pools, and other wet or contaminated environments where NEMA 1 transmitters fail.
10 Selectable Sub-Ranges
Internal 10-position rotary dial selects from 1.0 in WC to 40 in WC (or equivalent Pa values), with 10 finely-spaced steps in between. Twice the granularity of the P5's 4-position selector - the right pick when range tuning matters or when you don't know the exact pressure profile yet at spec time.
Selectable Fast / Slow Response
DIP-switch selectable response: Fast = 2 seconds for dynamic applications (VAV, fast-acting filter monitoring, transient duct events) or Slow = 8 seconds for stable averaging in turbulent ducts. Match the response to the application without ordering a different SKU.
Universal Output Signal
Slide-switch selectable: 4-20 mA 2-wire loop powered, 4-20 mA 3-wire VAC/VDC powered, 0-5 VDC, or 0-10 VDC. One SKU covers all four output types - field-set to match the controller input at install time.
LCD Standard + inWC/Pa Selectable
Built-in LCD display is standard on all P6 SKUs (not optional). DIP-switch selects between inches WC and pascals on the display - same SKU works for imperial-spec North American projects and metric-spec international projects. LED status indicator: power heartbeat, auto-zero complete, 110% over-pressure.
Universal Duct Probe (NEW)
NEW for the P6 Pro Series: the duct probe variant ships with BOTH the threaded duct probe AND the dual brass barbs on the same unit. Mount the unit on a wall and plumb tubing to the barbs, OR thread the probe into the back of the enclosure for direct in-duct mounting (cap the unused barb to maintain NEMA 4 rating). One SKU covers both methods.
10 Selectable Sub-Ranges & Outputs
This SKU is the 0-40 in WC / 0-10000 Pa base unit. Set the internal 10-position rotary dial to the desired sub-range, then use the slide switches to select Uni/Bi direction, inWC/Pa display units, Fast/Slow response, and the output signal type. Power the unit off before making any changes and form a drip-loop in the tubing to protect against condensation.
| Dial Position | Inches WC Sub-Range | Pa Sub-Range |
|---|---|---|
| 0 | 1.0 in WC | 250 Pa |
| 1 | 2.5 in WC | 625 Pa |
| 2 | 5.0 in WC | 1250 Pa |
| 3 | 8.0 in WC | 2000 Pa |
| 4 | 10 in WC | 2500 Pa |
| 5 | 15 in WC | 3750 Pa |
| 6 | 20 in WC | 5000 Pa |
| 7 | 25 in WC | 6250 Pa |
| 8 | 30 in WC | 7500 Pa |
| 9 | 40 in WC | 10000 Pa |
Technical Specifications
| Specification | Value |
|---|---|
| Model | P6-4000-1LP |
| Series | P6 Pro Series (NEMA 4 Universal) |
| Base Pressure Range (Inches WC) | 0-40 in WC |
| Base Pressure Range (Pa) | 0-10000 Pa |
| Selectable Sub-Ranges (Inches WC) | 1.0 in WC, 2.5 in WC, 5.0 in WC, 8.0 in WC, 10 in WC, 15 in WC, 20 in WC, 25 in WC, 30 in WC, 40 in WC |
| Selectable Sub-Ranges (Pa) | 250 Pa, 625 Pa, 1250 Pa, 2000 Pa, 2500 Pa, 3750 Pa, 5000 Pa, 6250 Pa, 7500 Pa, 10000 Pa |
| Sub-Range Selection | 10-position internal rotary dial |
| Direction | Field-selectable (Uni or Bi) via slide switch |
| Display Units | Field-selectable (Inches WC or Pa) via slide switch |
| Output Signals | Field-selectable: 4-20 mA 2-wire loop / 4-20 mA 3-wire / 0-5 VDC / 0-10 VDC |
| Supply Voltage | 12-30 VDC or 24 VAC (+/-10%), 30 mA max |
| Accuracy | +/-1.00% of selected range (combined non-linearity, hysteresis, and repeatability at 70 F) |
| Sensor Type | MEMS silicon piezoresistive, precision calibrated |
| Zero Function | Pushbutton + N.O. contact-closure auto-zero |
| Zero Tolerance | Included in accuracy specification |
| Span Tolerance | +/-1.00% (+/-1% +/-0.005 in WC for ranges under 0.10 in WC) |
| Zero Drift (1 year) | 0.004 in WC/year max (0.4% for units over 0.5 in WC) |
| Thermal Shift | 0.02% FSO per deg C (0.01% FSO per deg F), referenced to 72 F |
| Response Rate | Field-selectable: 2 seconds (fast) or 8 seconds (slow) |
| Overpressure | 332 in WC |
| Max Static Line Pressure | 332 in WC |
| Burst Pressure | 415 in WC |
| Position Sensitivity | Non-position sensitive |
| Operating Temperature | -4 to 140 F (-20 to 60 C) |
| Compensated Temperature | -4 to 140 F (-20 to 60 C) |
| Operating Humidity | 0 to 95% RH, non-condensing |
| Media Compatibility | Dry, oil-free air or nitrogen (N2) |
| Display | 5-digit LCD (standard, not optional) |
| Pressure Port | Duct Probe + Barbs (Universal) |
| Tubing Connection | Brass hose barbs, accepts 1/8 in and 1/4 in ID poly tubing |
| Enclosure Material | UL94-5VB rated, ABS |
| Enclosure Rating | NEMA 4 (cap unused barb when using duct probe to maintain rating) |
| Cable Entry | Watertight cable gland (included); accepts 3/8 in conduit fitting if removed |
| Dimensions | 4.0 in H x 3.7 in W x 2.1 in D (101.6 x 94.0 x 53.3 mm) |
| Weight | 0.20 lb |
| Compliance | CE, RoHS |
| Procurement Compliance | Buy American Act (BAA), BABAA, TAA, ARRA Section 1605 |
| Country of Origin | Made in USA - Beaverton, Oregon (over 65% domestic component cost) |
| Warranty | 7-year limited (electronics) |
| Manufacturer Part Number | P6-4000-1LP |
Documentation
Frequently Asked Questions
What sub-ranges and output options does the P6-4000-1LP support?
How is the P6 Pro Series different from the P5 Universal?
What does NEMA 4 mean for installation?
When should I use fast vs slow response rate?
What's the NEW Universal Duct Probe feature?
How do I wire the output and zero the transmitter?
- Series:
- P6 Pro Series (NEMA 4 Universal)
- Pressure Range Class:
- Medium (10 to 50 in WC)
- Pressure Range:
- 40 in WC
- Direction:
- Field-Selectable
- Output Signal:
- Field-Selectable (mA/V)
- Display:
- LCD
- Accuracy Class:
- Mid (0.5 to 2% FS)
- Mounting:
- Duct
- Probe:
- Probe
- Made in USA:
- Yes