Senva PW31-3V-010C-D : Wet-Wet Differential Pressure Transducer, 3-Valve Bypass Assembly, 0-10PSI, 4-20mA Output, LCD Display, 7-Year Warranty
Senva’s PW31 Series is designed to streamline installation and provide maximum accuracy. Options for standalone transducer or 3-valve and 5-valve bypass assemblies allow flexibility and save time on installation and commissioning. The single-diaphragm element is temperature compensated to provides superior ±0.25% accuracy. The PW31’s compact, light, and rugged structure combined with IP65 stainless steel construction make it ideal for most installations and capable of withstanding the most rugged environments. Now available with a highly visible, loop-powered LED display. Just plug it in for ease of commissioning and troubleshooting (4-20mA version only).
Applications
- Meet rigid accuracy and/or bypass specifications
 - Demand measurement in HVAC systems for pump speed control and local indication
 - Process control systems
 - Measurement of gases, vapors, and liquids
 - Measure pressure changes on pumps for efficiency regulation and energy savings
 - Level measurement in tanks and vessels
 - Filter status monitoring
 - System leak detection
 
Specifications
| Power Supply | 15-35vdc, 20mA max. | 
| Outputs | 2-wire 4-20mA, 3-wire 0-10V, 3-wire 0-5V | 
| Operating Temperature (3) |  |
| Operating Temperature  |  -4 to 175°F (-20-80°C) | 
| Compensated range |  30 to 158°F (0-70°C) | 
| Media Compatibility Transmitter | 316L SS compatible liquids and gases, Viton O-rings | 
| Accuracy (2) |  ±0.25% | 
| Burst Pressure |  500% DP range high side; 300% DP range low side | 
| Sensor Enclosure |  Laser welded housing, IP65 | 
| Pressure Connection Transmitter |  1/4” NPT Female | 
| Pressure Connections Manifold |  1/4” NPT female | 
| Electrical Connection |  DIN43650A | 
| Environmental |  IP65 (Installed with water-tight fittings) 1/2” conduit adapter included  |  
(1) This is maximum gauge pressure to maintain the 0.25% accuracy.
(2) FS is defined as the full scale of the selected range. Accuracy includes non-linearity, hysteresis, repeatability, zero and span tolerance.
(3) Stated operating range is for electronics only; Media temperature may be considerably higher.  Use of device outside of compensated range may result in drift.
Datasheets
| Senva PW31 Single Diaphragm Wet Differential Transducer Datasheet | |
| Senva PW31 Installation Instructions | |
| Wet DP Sensor Selection for Chiller Optimization | 
- Series:
 - PW31
 - Pressure Type:
 - Differential
 - Media:
 - Wet
 - Bypass:
 - 3-Valve
 - Pressure Range:
 - 0-10 PSID
 - Output Signal:
 - 4-20mA
 - Display:
 - LCD Display