Senva PW31-5V-100B : Wet-Wet Differential Pressure Transducer, 5-Valve Bypass Assembly, 0-100PSI, 0-10V Output, 7-Year Warranty
Senva’s PW31 Series is designed to streamline installation and provide maximum accuracy. Options for standalone transducer or 3-valve and 5-valve bypass assemblies allow flexibility and save time on installation and commissioning. The single-diaphragm element is temperature compensated to provides superior ±0.25% accuracy. The PW31’s compact, light, and rugged structure combined with IP65 stainless steel construction make it ideal for most installations and capable of withstanding the most rugged environments. Now available with a highly visible, loop-powered LED display. Just plug it in for ease of commissioning and troubleshooting (4-20mA version only).
Applications
- Meet rigid accuracy and/or bypass specifications
- Demand measurement in HVAC systems for pump speed control and local indication
- Process control systems
- Measurement of gases, vapors, and liquids
- Measure pressure changes on pumps for efficiency regulation and energy savings
- Level measurement in tanks and vessels
- Filter status monitoring
- System leak detection
Specifications
Power Supply | 15-35vdc, 20mA max. |
Outputs | 2-wire 4-20mA, 3-wire 0-10V, 3-wire 0-5V |
Operating Temperature (3) | |
Operating Temperature | -4 to 175°F (-20-80°C) |
Compensated range | 30 to 158°F (0-70°C) |
Media Compatibility Transmitter | 316L SS compatible liquids and gases, Viton O-rings |
Accuracy (2) | ±0.25% |
Burst Pressure | 500% DP range high side; 300% DP range low side |
Sensor Enclosure | Laser welded housing, IP65 |
Pressure Connection Transmitter | 1/4” NPT Female |
Pressure Connections Manifold | 1/4” NPT female |
Electrical Connection | DIN43650A |
Environmental | IP65 (Installed with water-tight fittings) 1/2” conduit adapter included |
(1) This is maximum gauge pressure to maintain the 0.25% accuracy.
(2) FS is defined as the full scale of the selected range. Accuracy includes non-linearity, hysteresis, repeatability, zero and span tolerance.
(3) Stated operating range is for electronics only; Media temperature may be considerably higher. Use of device outside of compensated range may result in drift.
Datasheets
Senva PW31 Single Diaphragm Wet Differential Transducer Datasheet | |
Senva PW31 Installation Instructions | |
Wet DP Sensor Selection for Chiller Optimization |
- Series:
- PW31
- Pressure Type:
- Differential
- Media:
- Wet
- Bypass:
- 5-Valve
- Pressure Range:
- 0-100 PSID
- Output Signal:
- 0-10V
- Display:
- No