Siemens 590-510 : Air Differential Pressure Sensor, +/- 0.25-in WC, 0-10VDC, 1% Accuracy, Cover Included
The 590 Series Differential Pressure Sensors obtain differential or gauge (static) pressures and convert this pressure difference to a proportional electrical output. Static accuracy is ±1% full scale in normal ambient temperature environments.
Features
- 10 PSI proof pressure on all ranges
- 24 Vac excitation
- 0 to 10 Vdc analog input is compatible with all energy management systems
- Fully protected against reverse wiring
- 1% accuracy improves variable air volume system performance
- Optional accuracies as high as 0.25% FS
Specifications
Connecting thread | Screw terminal strip |
Material | Fire retardant glass filled polyester case |
Medium temperature | -18…65 °C; 0…150 ºF |
Type of fixing | 1/4-in OD pressure fitting |
Analog outputs | 0-10 V |
Measuring range | +/- 0.25-in WC |
Measurement accuracy | +/-1 % |
Connection cable | For use with 1/4 in. push on tubing |
Connecting thread | Screw terminal strip |
Datasheets
Siemens 590 Series Very Low Differential Pressure Transducer Data Sheet | |
Siemens 590 Series Very Low Differential Pressure Transducer Installation | |
EU Declaration of Conformity |
- Output Signal:
- 0-10VDC
- Pressure Type:
- Differential
- Pressure Ranges:
- 0 to 0.25 Inch
- Media:
- Dry
- Accuracy:
- 1.0%
- LCD Display:
- No Display
- Zero Function:
- Yes
- Range Setting:
- Fixed
- Communication:
- None
- Series:
- 590 Series