Skip to main content

Veris EP2121S2 : Electropneumatic Transducer, Selectable 4 to 20 mA/0 to 5 V/0 to 10 VDC Control Input, Selectable 0 to 20 psig or 3 to 15 psig Control Output, Manual Mode Alarm, Vent on Power Fail, EP Cover Plate

Veris

MSRP: $431.33
$207.00
(You save $224.33 )
(No reviews yet) Write a Review
SKU:
EP2121S2
Condition:
New
Availability:
Ships in 1 Week
Adding to cart… The item has been added

Veris EP2121S2 : Electropneumatic Transducer, Selectable 4 to 20 mA/0 to 5 V/0 to 10 VDC Control Input, Selectable 0 to 20 psig or 3 to 15 psig Control Output, Manual Mode Alarm, Vent on Power Fail, EP Cover Plate

The EP2 series electro pneumatic pressure transducer uses microcontrolled poppet valve technology for highly accurate pressure sensing in multiple applications. The poppet valves consume no air, eliminating unnecessary air losses in the system and allowing for stable and reliable operation. The EP2 comes installed on standard SnapTrack. An LCD display and LED indicators make it easy to read system status at a glance.

  • Field-selectable 4 to 20 mA/0 to 5 V/0 to 10 VDC input for application flexibility
  • Poppet valve technology for quiet operation
  • Manual override with set and hold feature, great for commissioning leaky systems
  • Media connection - clean, dry air, or inert gas, do not use with oxygen service
  • Pressure indication - electronic, 3-1/2 digit LCD

Specifications

Input Power Class 2; 24 Vac/dc nominal, 30 Vac max.; 150 mA max.
Control Input Class 2; 4 to 20mA/0-5 V/0-10 Vdc; jumper-selectable
Input Impedance 4 to 20 mA, 250 Ω; 0-5 V/0-10 Vdc, 10 kΩ
Air Capacity 523 in3/min @ 45 psi (8570 cm3/min @ 310.3 kPa); 333 in3/min @ 20 psi (5456 cm3/min @ 137.9 kPa)
Supply Pressure 45 psig max.
Control Range 0 to 20 psig or 3 to 15 psig, jumper-selectable
Pressure Differential 0.1 psig (supply to branch)
Pressure Indication Electronic, 3-1/2 digit LCD
Minimum Tubing Length 15 feet
Port Connection 1/8” I.D. poly tubing
Media Connection Clean, dry air, or inert gas. Do not use with oxygen service

 

Datasheets

pdf logo Veris EP2 Electropneumatic Transducers Data Sheet
pdf logo Veris EP2 Electropneumatic Transducers Installation
pdf logo Veris EP2 Electropneumatic Transducers Certificate of Conformity
Feedback:
Manual Mode Alarm
Failsafe:
Vent on Power Fail
Cover:
EP Cover Plate