ACI A/LLS-T(0-500) : Light Level Sensor w/ Transmitter, 0-500 foot-candles (fc), 4-20 mA (3 Wire) Output, NEMA 3R Enclosure
TheA/LLS-T light level transmitter is used for applications such as turning on or off indoor or outdoor lighting based upon the amount of available light. The sensor can be mounted in a NEMA 3R rated enclosure. The A/LLS-T incorporates a transmitter with the sensor to produce a non-linear 4-20 mA output signal. The A/LLS-T is calibrated for 4 mA in darkness and 20 mA in bright Light. Typically the 0-500 is used for outdoor parking lot lighting/signage applications and the 0-100 is used for indoor lighting.
Applications
- Indoor/Outdoor Lighting Control Systems
- Building Automation Systems
Specifications
Supply Voltage | 24 to 35 VDC |
Input Impedance | 150K Ohms |
Output Current Signal Range | 4-20 mA (3 Wire) |
Maximum Load Resistance | 500 Ohms |
Light Level Measurement Range | Model Dependent: 100 foot-candles (0-100) / 500 foot-candles (0-500) |
Operating Temperature Range | 35 to 131°F (1.5 to 55°C) |
Storage Temperature Range | -0 to 160°F (-40 to 71°C) |
Operating Relative Humidity Range | 5 to 95% non-condensing |
Enclosure Specifications (Material, Flammability, NEMA/IP Ratings) | Aluminum, IP32 (NEMA 3R) |
Snaptrack Material | Polyvinyl Chloride (PVC) |
Snaptrack Flammability Rating | UL94 V-0 |
Connections | Wire Size | Screw Terminal Blocks | 16 (1.31 mm2) to 26 AWG (0.129 mm2) |
Terminal Block Torque Rating | 0.5 Nm (Minimum); 0.6 Nm (Maximum) |
Product Dimensions | (L) 4.58” (116.3 mm) x (W) 2.82” (71.63 mm) x (H) 2.25” (57.15 mm) |
Product Weight | “LLS”: 0.054 lbs (0.025 kg) | “LLS-T”: 0.85 lbs (0.386 kg) |
Agency Approvals | RoHS2, WEEE |
Datasheets