null Skip to main content

ACI A/MSCTA-40 : Split-Core Mini Analog Current Sensor, 0 to 40 A Range, 4 to 20 mA (2-wire, loop powered), Average Measurement, 5-Year Warranty

ACI

Your Price:  $80.98
(No reviews yet) Write a Review
SKU:
A/MSCTA-40
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
Core StyleSplit-Core
Amperage Range0 to 40 A
Output Signal4 to 20 mA (2-wire, loop powered)
MeasurementAverage · Pure Sinusoidal
Accuracy+/- 0.75% FS (+/- 0.3 A) above 2 A
Warranty5-Year Limited

ACI A/MSCTA-40 Mini Analog Current Sensor

The ACI A/MSCTA-40 is a split-core AC analog current sensor that converts 0 to 40 A into a 4 to 20 mA (2-wire, loop powered) signal using average measurement. Accuracy is +/- 0.75% FS (+/- 0.3 A) above 2 A.

The A/MSCTA-40 uses averaging measurement, which assumes a pure sinusoidal waveform with little or no distortion on the monitored conductor. It is the correct and lower-cost choice for resistive and single-speed linear loads such as incandescent lighting, heating elements and across-the-line motors. Where the load is fed by a VFD or a switching supply, ACI directs users to the True RMS A/CTA2-RMS or A/SCTA2-RMS series instead.

The output is a 2-wire, loop-powered 4 to 20 mA signal, which needs an external +8.5 to 30 VDC supply. ACI specifies a maximum run of 30 m (98.4 ft) of 2-conductor shielded cable between the sensor and the building management system. Where the controller input expects a voltage signal, ACI publishes 249 Ohm and 499 Ohm precision resistors that convert the loop to 1 to 5 VDC or 2 to 10 VDC at the panel.

The split-core housing opens around an existing conductor, so the A/MSCTA-40 can be fitted to wiring that is already terminated. All power sources must be disconnected and locked out before installation. That makes it the practical choice for retrofit and service work.

Specifications on this page are taken from the ACI MSCTA-40 & MSCTE-40 Series data sheet and User's Guide I0000984.

Best For

  • Load trending and basic power monitoring on single-speed linear loads
  • LEED documentation and energy project ROI justification
  • Continuous amperage feedback to a BMS, PLC or DDC analog input
  • Preventative maintenance programs that need measured current, not just on/off status

Warranty

Five (5) Year Limited Warranty. Covered by ACI's Five (5) Year Limited Warranty. The warranty is published in the front of ACI's Sensors & Transmitters catalog and on the ACI website.

Key Features

Average Measurement

Averaging measurement for pure sinusoidal waveforms. Correct and cost-effective on resistive and single-speed linear loads.

Fixed 0 to 40 A Range

A single 0 to 40 A sensor amperage range with no jumper to set, and accuracy specified across the full range rather than a selected sub-range.

4 to 20 mA (2-wire, loop powered) Output

Loop-powered 2-wire signal on 2-conductor shielded cable, up to the 30 m (98.4 ft) run ACI specifies. Optional 249 Ohm and 499 Ohm resistors convert to 1 to 5 VDC or 2 to 10 VDC at the panel.

Split-Core Aperture

Opens around an existing conductor for retrofit installation without disconnecting any wiring.

Published Accuracy

+/- 0.75% FS (+/- 0.3 A) above 2 A. All current output sensors are calibrated at an ambient room temperature of 71 °F (21.5 °C).

Cable Tie Anchor and Mounting Foot

Secures to the monitored cable with a cable tie, or mounts with the attachable foot using one Tek screw or directly on 35 mm DIN rail.

Technical Specifications

ACI Item Number151890
Core StyleSplit-Core
Sensor Amperage Range0 to 40 A
Measurement MethodAverage
AC WaveformPure Sinusoidal
Output Signal4 to 20 mA (2-wire, loop powered)
Accuracy+/- 0.75% FS (+/- 0.3 A) above 2 A
Supply Voltage+8.5 to 30 VDC (reverse polarity protected); 250 Ohm load (1 to 5 VDC): +13.5 to 30 VDC; 500 Ohm load (2 to 10 VDC): +18.5 to 30 VDC
Supply Current25 mA minimum
Maximum Load Resistance775 Ohms @ 24 VDC
Response Time< 600 mS (rise and fall times)
Operating Temperature Range-22 to 140 °F (-30 to 60 °C)
Monitored Current TypeAC Current
Maximum AC Voltage600 VAC
Isolation Voltage2200 VAC
Operating Frequency Range50/60 Hz
Aperture Size0.20 in (5.0 mm) x 0.49 in (12.5 mm)
Monitored Wire SizeFits 10 AWG to 14 AWG THHN insulated wire
DIN Rail Size35 mm
Operating Humidity Range10 to 95% RH, non-condensing
Storage Temperature | RH Range-40 to 158 °F (-40 to 70 °C) | 10 to 95% RH, non-condensing
Enclosure Material | Flammability RatingPC/ABS (polycarbonate / ABS blend) | UL94-V0
Wiring Connections2-position screw terminal block (polarity sensitive)
Wire Size16 to 22 AWG (1.31 mm2 to 0.33 mm2), copper wires only
Terminal Block Torque Rating4.43 to 5.31 in-lbs (0.5 to 0.6 Nm)
Minimum Mounting Distance1 in (2.6 cm) from relays, contactors and transformers
Product Dimensions (L x W x H)1.93 in (48.99 mm) x 1.31 in (33.17 mm) x 2.18 in (55.37 mm)
Product Weight0.165 lbs (0.075 kg)
Agency ApprovalsUL/CUL US Listed (UL 508) Industrial Control Equipment, File # E309723, CE, RoHS, UKCA, FCC, CAN ICES-3 / NMB-3
WarrantyFive (5) Year Limited Warranty

Not intended for use in life / safety applications or in hazardous / classified locations.

Disconnect and lock out all power sources before installation. Required by the ACI Installation & Operation Instructions. Installation must be performed by qualified personnel in compliance with all national and local electrical codes.

Accuracy Specifications

AccuracyCurrentOperating TemperatureFrequency
+/- 0.75% FS (+/- 0.3 A)Greater than 2 A5 to 140 °F (-15 to 60 °C)60 Hz
+/- 0.75% FS (+/- 0.3 A)Greater than 2 A32 to 140 °F (0 to 60 °C)50 Hz

Output Conversion Resistors (ordered separately)

ACI Item #Description
100307249 Ohm, 1/4 W, +/- 1% tolerance, 50 ppm resistor (converts output to 1 to 5 VDC)
100306249 Ohm, 1/4 W, +/- 0.1% tolerance, 50 ppm resistor, recommended for best accuracy (converts output to 1 to 5 VDC)
100469499 Ohm, 1 W, +/- 1% tolerance, 50 ppm resistor (converts output to 2 to 10 VDC)

Documentation

Related Products

Frequently Asked Questions

What output signal does the ACI A/MSCTA-40 produce?

The A/MSCTA-40 produces a 4 to 20 mA (2-wire, loop powered) signal. It is loop powered and needs an external +8.5 to 30 VDC supply.

What amperage ranges does the ACI A/MSCTA-40 cover?

The A/MSCTA-40 has a fixed sensor amperage range of 0 to 40 A.

Can the ACI A/MSCTA-40 be used downstream of a variable frequency drive?

No. This sensor uses averaging measurement, which assumes a pure sinusoidal waveform. For VFDs, switching power supplies and other distorted waveforms, ACI directs users to the True RMS A/CTA2-RMS or A/SCTA2-RMS series.

What is the published accuracy of the ACI A/MSCTA-40?

+/- 0.75% FS (+/- 0.3 A) above 2 A. All ACI current output sensors are calibrated at an ambient room temperature of 71 °F (21.5 °C).

How is the ACI A/MSCTA-40 converted to a voltage signal?

ACI publishes precision resistors for this: item # 100307 or # 100306 (249 Ohm) convert the loop to 1 to 5 VDC, and item # 100469 (499 Ohm, 1 W) converts it to 2 to 10 VDC. The resistor is ordered separately and installed at the controller input.

ACI Five (5) Year Limited Warranty. This product is covered by Automation Components, Inc.’s Five (5) Year Limited Warranty, published in the front of the ACI Sensors & Transmitters catalog and on the ACI website. Warranty terms are set by the manufacturer and are subject to change without notice.

Mounting Type:
Split-Core
Amp Range:
0-40A
Output Signal:
4-20 mA
Measurement:
Average
AC Waveform:
Pure Sinusoidal
Sensor Power:
Loop Powered
Warranty:
5-Year Limited