Skip to main content

ACI A/RH2-AN-D-BB : Duct Relative Humidity Sensor, 2% Accuracy, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), 10K Ohm Thermistor (Type III), NEMA 3R Duct Enclosure, Made in USA

ACI

MSRP: $398.00
$151.30
(You save $246.70 )
(No reviews yet) Write a Review
SKU:
A/RH2-AN-D-BB
Condition:
New
Availability:
Ships in 2-4 Days
Adding to cart… The item has been added

ACI A/RH2-AN-D-BB : Duct Relative Humidity Sensor, 2% Accuracy, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), 10K Ohm Thermistor (Type III), NEMA 3R Duct Enclosure, Made in USA

The ACI Relative Humidity with Thermistor Duct Series utilizes a thermoset polymer capacitive sensing element with a factory fitted hydrophobic filter to improve its moisture resistance. The sensing elements multilayer construction also provides excellent resistance in applications where dust, dirt, oils and common environmental chemicals are found. The RH duct sensors include on board DIP switches which allow the user to select the desired output signal and can be powered by AC or DC power sources. Each unit also contains 0%, 50%, and 100% test options to verify that the transmitter is both working and wired properly. Field calibration can be performed by using the increment and decrement calibration DIP switches without the need to replace the sensing element. These enhancements provide increased flexibility and outstanding long-term reliability without the need to replace the sensors in the field.

Applications:

  • Humidification
  • Dehumidification
  • Supply / Discharge / Return Air
  • Economizers
  • Clean Rooms
  • Data Centers
  • Process Control
  • Schools
  • Hospitals
  • Office Buildings

Specifications

RH Supply Voltage (Reverse Polarity Protected): 4-20 mA / 0-5 VDC /  0-10 VDC
RH Output Signal: 2-wire: 4 - 20 mA (Factory Default) /3-wire: 0-5 or 0-10 VDC and 4 - 20 mA (Field Selectable)
RH Measurement Range: 0-100%
Operating RH Range: 0 to 95% RH, non-condensing
RH Stability | Repeatability | Sensitivity: Less than 2% drift / 5 years | 0.5% RH | 0.1% RH
Nominal Thermistor Resistive Output @ 77°F (25°C) (Lead Wire Colors) Non-Linear NTC

RHx-AN Series (Type III): 10KΩ (White/White)

 

Datasheets

pdf logo ACI RH Duct Relative Humidity/Temp Data Sheet
pdf logo ACI RH Duct Relative Humidity/Temp Installation
Sensor Type:
Duct
Humidity Element:
2%
Output Signal:
4-20mA, 0-5 VDC, or 0-10 VDC
Temperature Element:
10K Type III
CO2 Element:
None
Display:
No Display
VOC Element:
None
Probe Length:
8
Enclosure:
Aluminum NEMA 3R Enclosure
Supported Protocols:
None