ACI A/RH3-1K-2W-RP2-20'-EH : Remote Probe Relative Humidity, 3% Accuracy, RH Outputs: 0-5, 0-10 VDC & 4-20mA (Default), 1K Ohm Platinum RTD (Two Wires), 20' Plenum Cable, Plastic Enclosure (Euro), Made in USA
The ACI Relative Humidity Remote Probe utilizes a thermoset polymer capacitive sensing element with a hydrophobic filter to deliver a proportional relative humidity analog output. Single point field calibration can be done on the humidity transmitter, by using the increment and decrement dip switches. Each toggle of the increment and decrement switches will allow for a ±0.5% RH increase or decrease. Calibration of the RH transmitters electronics can also be done using both the Zero and Span potentiometers depending on whether it is a current or voltage output device. All models feature conformally coated circuit boards to improve the reliability of the product in both high moisture and mildly corrosive atmospheres. A vinyl cap is provided to place over the sintered filter in wash down applications to protect the sensing element from getting moisture sprayed directly on the sensor.
Specifications
RH Supply Voltage (Reverse Polarity Protected): |
4-20 mA: 250 Ohm Load: 15 - 40 VDC / 18 - 28 VAC | 500 Ohm Load: 18 - 40 VDC / 18 - 28 VAC 0-5 VDC: 12 - 40 VDC / 18 - 28 VAC | 0-10 VDC: 18 - 40 VDC / 18 - 28 VAC |
RH Output Signal: | 2-wire: 4 - 20 mA (Factory Default) | 3-wire: 0-5 or 0-10 VDC and 4 - 20 mA (Field Selectable) |
RH Measurement Range: | 0-100% |
Operating RH Range: | 0 to 95% RH, non-condensing |
RH Stability | Repeatability | Sensitivity: | Less than 2% drift / 5 years | 0.5% RH | 0.1% RH |
Datasheets
- Sensor Type:
- Remote Probe
- Temperature Element:
- Transmitter
- Lead Length:
- 20 Foot Plenum Rated Cable
- Enclosure:
- NEMA 3R