ACI A/WPR2-30-M10-LCD : Remote Wet Differential Pressure Transmitter,Uni/Bi-Directional: 0-30, 0-15, 0-7.5 and 0-3 psid, 10' Metal Clad Cable Harness, Selectable Outputs: 0-5 VDC, 0-10 VDC, 4-20mA, LCD Display, 5-Year Warranty, Made in USA
The ACI WPR2 Series Remote Wet to Wet Differential Pressure Transmitter is a versatile and efficient device designed to streamline installation and offer flexible mounting options.It often eliminates the need for additional plumbing and manifolds, saving time and effort during installation. The transmitter can be ordered with either a standard CMP rated PVC cable or a metal clad cable, which provides comprehensive protection to the cables through its flexible metal conduit.
This series of pressure transmitters is highly accurate and capable of measuring wet media pressures in various applications. While commonly used for monitoring pumps, they are equally suitable for measuring pressure across filters, heat exchangers, and compressors. The WPR2 transmitter offers excellent flexibility, allowing for reconfiguration between three additional ranges and offering output options of 4 to 20 mA, 0 to 5 VDC, or 0 to 10 VDC (default). The device also features a convenient push-button auto zero function for remote calibration.
Specifications
Supply Current | 4-20 mA Output: 24 mA minimum | 0-5 VDC / 0-10 VDC Outputs |
Output Signals | 0-5 VDC, 0-10 VDC, 4-20 mA (Field Selectable) |
Response Time (0-100% FSO) | 8 seconds |
Output Update Rate | 1 second |
Output Load Resistance | 4 to 20 mA: 500 ohms maximum | 0-5 VDC / 0-10 VDC: 5K ohms minimum |
Field Selectable Ranges | Uni-Directional: 0-30, 0-15, 0-7.5 and 0-3 psid Bi-Directional: +/-30, +/-15, +/-7.5 and +/-3 psid |
Warm Up Time | 15 minutes (wait 15 minutes before zeroing) |
Accuracy (Three Highest Ranges) | ±1.0% FSO |
Accuracy (Lowest Range) | ±1.5% FSO |
Thermal Effects | ±2.0% FSO from 32-140°F (0-60°C) |
Operating Temperature Range | Transducer: -40 to 257°F (-40 to 125°C) | Electronics/Housing/Cables: 32-167°F (0-75°C) |
Compensated Temperature Range | 32 to 140°F (0 to 60°C) |
Storage Temperature Range | -13 to 176°F (-25 to 80°C) |
Operating Humidity Range | 10 to 90% RH, non-condensing |
Proof Pressure | 60 PSI |
Burst Pressure | 300 PSI |
Media Types | Any gas or liquid compatible w/ 304L or 316L Stainless Steel |
Process Fitting Material | 304 SS |
Process Fitting Size | 1/4" - 18 NPT Male; Pressure Snubber included for light oils/water |
Recommend Torque Specification | 150 lbs-in (16.95 Nm) |
Transducer Cable Rating | Connector Type | Type CMP - Plenum Rated (UL Standard 444), NEC Article 800 | IP65 at the sensors Packard Connector |
Metal Clad Rating: | Continuously interlocked Type 304 Stainless Steel core |
Enclosure Material | Flammability Rating | Flame Retardant PC | PBT Alloy | UL94V-0 |
Enclosure Rating | NEMA 4X/IP66 |
Agency Approvals | CE, RoHS2, WEEE, Reach |
Datasheets
- Series:
- WPR2
- Pressure Type:
- Differential
- Media:
- Wet
- Bypass:
- None
- Output Signal:
- 4-20mA, 0-5 VDC, 0-10 VDC
- Display:
- LCD Display
- Enclosure:
- NEMA 4X
- Cable:
- 10' Armored Cable
- Remote Sensors:
- 0-300 PSID