ACI CO-D-RB-D : Carbon Monoxide Sensor, 0-125 PPM Default, (250 PPM Max), Duct Mount, 4-20mA or 2-10VDC Output, LCD, Relay & Buzzer
The CO Duct Series monitors carbon monoxide (CO) levels and is designed for the continuous monitoring of vehicle exhaust in non-hazardous areas. This series uses a wide spectrum, long life electrochemical sensor to measure the amount of carbon monoxide in the environment. It is offered with an operating range of 0 to 125 ppm. Duct CO transmitters are offered in a standard NEMA 1 rated ABS Polycarbonate plastic enclosure. Other options include an LCD display with (2) SPDT Form 1C relays and a buzzer. Refer to all applicable Federal, State, Provincial and Local Health and Safety laws and regulations before using these products. CO-D is not compatible with the Q4C-II or Q-Controllers.
Specifications
Supply Voltage: | 24 VAC +/- 10% Floating; 24 VAC +/- 10%, One side Grounded; 24 VDC |
Sensor Type: | Electrochemical |
Sensor Life: | ~ 5 years under Normal Conditions |
Factory Set: | 0 – 125 ppm / 0 – 250 ppm Field Adjustable |
Indicators: | Alphanumeric – 2 line X 8 digit LCD / (2) Red LED’s for Relay Status |
Analog Outputs: | 4-20 mA or 2-10V Jumper Selectable |
Datasheets
CO Duct Carbon Monoxide Duct Sensor |
- Enclosure Style:
- Duct
- Gas Element:
- Carbon Monoxide
- Analog Output:
- 1
- Relay Output:
- None
- Communication:
- None
- Display:
- LCD Display