ACI PXP7.3G : Analog Input (0-5VDC), Pressure Output (0-15PSI), Single Valve, 0.007" Bleed Orifice, Gauge, (0-10V, 0-15V, 0-20mA Selectable)
The PXP*.3 is an electric-to-pneumatic transducer that converts an analog electrical input signal into a proportional pneumatic output. It automatically adjusts its control valve(s) to maintain the branch line pressure at a selected set point determined by the input signal. The PXP*.3 offers four selectable input ranges, resulting in a 0 to 15 psig modulating output (note that the EPC product provides 0 to 20 psig outputs). It also provides a 0-5 VDC feedback signal that corresponds linearly to the branch pressure (0 volts = 0 psig, 5 volts = 15 psig).
PXP1.3, 5.3, and 7.3 are constant bleed controllers, and their branch exhaust response time depends on the bleed orifice size and pressure differentials. In case of a power failure, they continue to release air through the bleed orifice until branch pressure reaches zero psig. A three-way solenoid valve assembly can be used to revert control to the local controller in case of power failure.
Specifications
Supply Voltage: | 24 VAC (+/-10%), 50 or 60Hz, 24 VDC (+10%/- 5%) |
Supply Current: | 160 mA maximum, 200 mA on fail safe models |
Input Signal Source (@ Impedance): | 0-5 VDC @ 10,000 Ω | 0-10 VDC @ 10,000Ω | 0-15 VDC @ 10,000Ω | 0-20 mA @ 250Ω |
Feedback Signal Output Range: | 0-5 VDC = Output Span |
Output Pressure Range: | Field Calibration Possible: 0 to 15 psig (0-103.421 kPa) maximum |
Air Supply Pressure: | Maximum: 25 psig (172.369 kPa) | Minimum: 18 psig (124.106 kPa) |
Air Consumption: | See Ordering Grid |
Output Pressure Accuracy: | 1% full scale @ room temperature | 2% full scale across operating temperature range |
Manual / Auto Override: | MAN function = output can be varied | AUTO function = output is controlled from input signal |
Air Flow: | Supply valves @ 20 psig (138 kPa) main/15 psig (103 kPa) out, 750 scim (1400 on LG model) Branch Line requires 2 in3 or 33.78 cm3 (min.). Branch line min. of 25 feet of 1/4” O.D. poly tubing |
Filtering: | Furnished with integral-in-barb 80-100 micron filter (Part # PN004) except for PXP2LG which is furnished with external 5 micron in-line filter (PN021) |
Connections: | 90° Pluggable Screw Terminal Blocks |
Wire Size: | 16 (1.31 mm2) to 26 AWG (0.129 mm2) |
Terminal Block Torque Rating: | 0.5 Nm (Minimum); 0.6 Nm (Maximum) |
Connections | Pneumatic Tubing Size-Type: | 1/4" O.D. nominal (1/8” I.D.) polyethylene |
Pneumatic Fitting: | Removeable brass barbed fittings for Main and Branch in machined aluminum manifold Plugged 1/8-27-FNPT gauge port | Gauge installed at additional cost |
Gauge Pressure Range (Gauge Models): | 0-30 psig (0-200 kPa) |
Gauge Pressure Accuracy (Gauge Models): | ± 2.5% Midscale (± 3.5% Full Scale) |
Operating Temperature Range: | 35 to 120°F (1.7 to 48.9°C) |
Operating Humidity Rage: | 10 to 95% non-condensing |
Storage Temperature: | -20 to 150°F (-28.9 to 65.5°C) |
Snaptrack Material: | Polyvinyl Chloride (PVC) |
Snaptrack Flammability Rating: | UL94 V-0 |
Product Dimensions: | No Gauge: (L) 3.25” (W) 2.18” (H) 1.87” (82.55 x 55.37 x 47.49 mm) With Gauge: (L) 3.25” (W) 2.18” (H) 2.95” (82.55 x 55.37 x 74.9 mm) |
Product Weight: | PXP1.3: 0.40 lbs. (0.1814 Kg) | PXP2.3: 0.47 lbs. (0.2126 Kg) | PXP1.3G: 0.49 lbs. (0.2211 Kg) PXP2.3G & PXP2.3GFS: 0.59 lbs. (0.2693 Kg) |
Agency Approvals: | RoHS2, WEEE |
Data Sheets
- Input Signal:
- Analog
- Output Signal:
- Pressure
- Guage:
- With Gauge
- Failsafe:
- No Failsafe
- Valves:
- 1 Valve