AccuEnergy ACUVIM-IIW-M-MV-P1V3 : Acuvim IIW Power Quality Meter, DIN Rail Transducer without Display, 333mV/Rogowski Current Input, Universal AC/DC Power
The AccuEnergy Acuvim IIW is an advanced, revenue-grade power and energy meter with IEC 61000-4-30 Class S power quality event logging and waveform capture. It supports a 4th CT input for neutral current measurement, high-resolution frequency readings, and flexible CT input options for new construction or retrofit metering. Configuration: DIN Rail Mount Transducer (No Display). Current input option: 333mV and Rogowski Coil (Input Field Selectable). Control power: 100~415Vac, 50/60Hz; 100~300Vdc.
Specifications:
| Series | Acuvim II |
| Meter Model | Acuvim IIW |
| Revenue Grade | ANSI C12.20 Class 0.1; IEC 62053-22 Class 0.1s |
| Power Quality | IEC 61000-4-30 Class S PQ event logging + waveform capture |
| Mounting | DIN Rail Mount Transducer (No Display) |
| Current Inputs | 333mV and Rogowski Coil (Input Field Selectable) |
| Neutral Current | 4th CT input supported |
| Voltage Inputs | Up to 828Vac line-to-line / 480Vac line-to-neutral |
| Communications | Modbus RTU & BACnet MS/TP (optional modules add Ethernet/Wi-Fi and more protocols) |
| Control Power | 100~415Vac, 50/60Hz; 100~300Vdc |
| Operating Temperature | -25¡C to 70¡C (-13¡F to 158¡F) |
| Anti-Tamper | Electronic seal function available (configured via Modbus) |
Datasheets
| Acuvim II Advanced Power & Energy Meter Datasheet | |
| Acuvim II Series Power Meter User Manual |
- Mountain Option:
- DIN Rail Mount Transducer (No Display)
- Current Input:
- 333mV and Rogowski Coil
- Power Supply:
- 100~415Vac, 50/60Hz; 100~300Vdc
- Meter Model:
- Acuvim IIW