null Skip to main content

BA/10K-2-PP-10'-BB2 : Remote Sensor, 10K-2 Thermistor, Plenum-Rated Cable, 10 ft (3.0 m) Lead Length, BAPI-Box 2 Enclosure

BAPI

MSRP: $35.00
Your Price:  $15.75
(You save $19.25 )
(No reviews yet) Write a Review
SKU:
BA/10K-2-PP-10'-BB2
Adding to cart… The item has been added
Sensing Element
10K-2 Thermistor
Sensor Body
Heat conductive plastic, 0.875"
Lead Length
10 ft (3.0 m) Plenum-Rated
Enclosure
BAPI-Box 2 (BB2), IP66, NEMA 4
Accuracy
±0.36°F (±0.2°C)
Probe Range
-40° to 221°F (-40° to 105°C)

The BAPI BA/10K-2-PP-10'-BB2 is a single-point remote sensor built around a heat conductive plastic cup 0.875 in long on a 0.175 in diameter shell and a passive 10K-2 Thermistor. It ships with 10 ft (3.0 m) of plenum-rated cable, factory-terminated into a BAPI-Box 2 (BB2) enclosure.

Remote sensors are built for tight spots — inside electronic circuit enclosures, retrofitted into existing pneumatic thermostats, or dropped into a junction box behind a wall plate. The element is passive and has no polarity, so both leads land directly on any controller analog input configured for the 10K-2 Thermistor curve. The BAPI-Box 2 (BB2) gives you a rated termination point right at the mounting surface instead of a splice above the ceiling.

Specifications

Sensing Element10K-2 Thermistor, NTC, 2-wire passive
OutputResistance (non-linear)
Accuracy±0.36°F (±0.2°C) standard
Stability< 0.036°F/year (< 0.02°C/year)
Heat Dissipation2.7 mW/°C
Temp. Drift< 0.02°C per year
Probe Range-40° to 221°F (-40° to 105°C)
Probe / BodyHeat conductive plastic cup, 0.875 in (22.2 mm) long, 0.175 in (4.45 mm) dia.
Lead Length10 ft (3.0 m)
Wire InsulationPlenum-rated cable
Lead Wire22 AWG stranded
EnclosureBAPI-Box 2 (BB2)
Enclosure RatingIP66, NEMA 4
Enclosure MaterialUV-resistant polycarbonate, UL94 V-0
Enclosure Dimensions4.9 × 2.8 × 2.4 in (125 × 72 × 60 mm)
Conduit EntriesThree 1/2 in NPSM entries and three 1/2 in drill-outs
Wall Gasket0.25 in (6.35 mm) closed cell foam, mold impervious
Enclosure Ambient-40° to 185°F (-40° to 85°C)
Operating RangeUnits with plenum-rated wire: -4° to 167°F (-20° to 75°C), 0-100% RH non-condensing
AgencyRoHS, CE (passive thermistors 20KΩ and smaller), PT = DIN43760 | IEC Pub 751-1983 | JIS C1604-1989

Installation Notes

  • Wire with twisted pair, 22 AWG minimum, using sealant-filled connectors. Heavier gauge may be needed on long runs.
  • Do not share conduit with high or low voltage AC power wiring — BAPI testing shows signal error when AC runs alongside sensor leads.
  • Two-wire passive element, no polarity. Land both leads on the controller analog input.
  • Fits inside a standard junction box behind a wall plate cover, or retrofits into the body of an existing pneumatic thermostat.
  • Mount the enclosure with #8 screws through at least two opposing tabs; a 1/8 in pilot hole makes this easier.
  • Use caulk or Teflon tape on conduit entries, and bring conduit in from the bottom for outdoor or wet locations.

Documentation

Product Datasheet (PDF)  ·  Installation & Operation (PDF)  ·  Enclosure Dimensions (PDF)

Warranty & Sourcing
ZOT Supply is an authorized distributor for Building Automation Products, Inc. (BAPI). This product carries the full BAPI factory warranty.
Product Family:
Remote Sensor
Signal Type:
Passive Resistive
Sensing Element:
10K-2 Thermistor
Cable Type:
Plenum-Rated
Lead Length:
10 ft
Enclosure:
BAPI-Box 2 (BB2)
Enclosure Rating:
IP66, NEMA 4
Probe Material:
Heat Conductive Plastic
Termination Option:
Standard (Flying Leads)
Mounting Style:
Enclosure / Thermostat Retrofit