null Skip to main content

BA/20K-PP-5'-WP : Remote Sensor, 20K Thermistor, Plenum-Rated Cable, 5 ft (1.5 m) Lead Length, Weatherproof Enclosure

BAPI

MSRP: $32.00
Your Price:  $14.40
(You save $17.60 )
(No reviews yet) Write a Review
SKU:
BA/20K-PP-5'-WP
Adding to cart… The item has been added
Sensing Element
20K Thermistor
Sensor Body
Heat conductive plastic, 0.875"
Lead Length
5 ft (1.5 m) Plenum-Rated
Enclosure
Weatherproof (WP), NEMA 3R, IP14
Accuracy
±0.36°F (±0.2°C)
Probe Range
-40° to 221°F (-40° to 105°C)

The BAPI BA/20K-PP-5'-WP is a single-point remote sensor built around a heat conductive plastic cup 0.875 in long on a 0.175 in diameter shell and a passive 20K Thermistor. It ships with 5 ft (1.5 m) of plenum-rated cable, factory-terminated into a Weatherproof (WP) enclosure.

Remote sensors are built for tight spots — inside electronic circuit enclosures, retrofitted into existing pneumatic thermostats, or dropped into a junction box behind a wall plate. The element is passive and has no polarity, so both leads land directly on any controller analog input configured for the 20K Thermistor curve. The Weatherproof (WP) gives you a rated termination point right at the mounting surface instead of a splice above the ceiling.

Specifications

Sensing Element20K Thermistor, NTC, 2-wire passive
OutputResistance (non-linear)
Accuracy±0.36°F (±0.2°C) standard
Stability< 0.036°F/year (< 0.02°C/year)
Heat Dissipation2.7 mW/°C
Temp. Drift< 0.02°C per year
Probe Range-40° to 221°F (-40° to 105°C)
Probe / BodyHeat conductive plastic cup, 0.875 in (22.2 mm) long, 0.175 in (4.45 mm) dia.
Lead Length5 ft (1.5 m)
Wire InsulationPlenum-rated cable
Lead Wire22 AWG stranded
EnclosureWeatherproof (WP)
Enclosure RatingNEMA 3R, IP14
Enclosure MaterialCast aluminum, UV rated
Enclosure Dimensions2.75 × 2.16 × 4.50 in (69.9 × 54.9 × 114.3 mm)
Conduit EntriesTwo 1/2 in FNPT entries (bell box)
Wall Gasket0.25 in (6.35 mm) closed cell foam, mold impervious
Enclosure Ambient-40° to 212°F (-40° to 100°C)
Operating RangeUnits with plenum-rated wire: -4° to 167°F (-20° to 75°C), 0-100% RH non-condensing
AgencyRoHS, CE (passive thermistors 20KΩ and smaller), PT = DIN43760 | IEC Pub 751-1983 | JIS C1604-1989

Installation Notes

  • Wire with twisted pair, 22 AWG minimum, using sealant-filled connectors. Heavier gauge may be needed on long runs.
  • Do not share conduit with high or low voltage AC power wiring — BAPI testing shows signal error when AC runs alongside sensor leads.
  • Two-wire passive element, no polarity. Land both leads on the controller analog input.
  • Fits inside a standard junction box behind a wall plate cover, or retrofits into the body of an existing pneumatic thermostat.
  • Mount the enclosure with #8 screws through at least two opposing tabs; a 1/8 in pilot hole makes this easier.
  • Use caulk or Teflon tape on conduit entries, and bring conduit in from the bottom for outdoor or wet locations.

Documentation

Product Datasheet (PDF)  ·  Installation & Operation (PDF)  ·  Enclosure Dimensions (PDF)

Warranty & Sourcing
ZOT Supply is an authorized distributor for Building Automation Products, Inc. (BAPI). This product carries the full BAPI factory warranty.
Product Family:
Remote Sensor
Signal Type:
Passive Resistive
Sensing Element:
20K Thermistor
Cable Type:
Plenum-Rated
Lead Length:
5 ft
Enclosure:
Weatherproof (WP)
Enclosure Rating:
NEMA 3R, IP14
Probe Material:
Heat Conductive Plastic
Termination Option:
Standard (Flying Leads)
Mounting Style:
Enclosure / Thermostat Retrofit