The BAPI BA/TXS10[20 TO 120F]-RPP-15-BBX-TS is a field-selectable voltage-output temperature transmitter that pairs a 1KΩ platinum RTD (385 curve) probe with an onboard transmitter circuit, factory-calibrated to a 20 to 120°F span and housed in a BAPI-Box Crossover (BBX) enclosure. It delivers field-selectable voltage (0-5, 0-10, 1-5, 2-10 vdc or 4-20 ma via dip switch) to your controller, so the signal arrives already linearized — no resistance curve to configure at the front end.
The sensing element is a rigid 304 stainless steel probe, 1.75 in long and 0.25 in OD, terminated with 15 ft (4.6 m) of flame-retardant PVC plenum-rated cable. The transmitter linearizes the signal at the device, so the controller input is configured for a standard analog signal rather than a thermistor or RTD resistance curve. BAPI specifies a 12 to 40 VDC supply, with PWR, GRD and Vout connections for voltage output, and calls for the transmitter to be mounted at least 5 ft from any radio wave-emitting device.
Specifications
| Output | Field-selectable voltage (0-5, 0-10, 1-5, 2-10 VDC or 4-20 mA via DIP switch) |
| Calibrated Range | 20 to 120°F |
| Power Required | 12 to 40 VDC |
| Output Wiring | PWR, GRD and Vout for voltage output; field-switchable to 4-20 mA (2-wire loop) |
| System Accuracy | ±0.065% of span |
| Linearity | ±(0.125 × T-20°C)/100 |
| Output Limits (4-20 mA mode) | <1 mA (short), <22.35 mA (open) |
| Load (4-20 mA mode) | 850Ω @ 24 VDC |
| Sensing Element | 1KΩ Platinum RTD @ 0°C, 385 curve, 2-wire |
| RTD Accuracy | 0.12% @ Ref, or ±0.55°F (±0.3°C) |
| RTD Sensitivity | 3.85Ω/°C approx. @ 32°F (0°C) |
| Probe Range | -40° to 221°F (-40° to 105°C) |
| Transmitter Ambient | -4° to 158°F (-20° to 70°C), 0-95% RH non-condensing |
| Probe / Body | Rigid 304 stainless steel, 1.75 in (44.5 mm) long, 0.25 in (6.35 mm) OD |
| Lead Length | 15 ft (4.6 m) |
| Wire Insulation | Flame-retardant PVC plenum-rated cable |
| Lead Wire | 22 AWG stranded |
| Enclosure | BAPI-Box Crossover (BBX) |
| Enclosure Rating | IP10, NEMA 1 |
| Enclosure Material | Cover: polycarbonate UL94 V-0 · Base: nylon UL94 HB |
| Enclosure Dimensions | 3.1 × 2.2 × 1.9 in (79 × 56 × 49 mm) |
| Conduit Entries | Hinged thumb-latch cover, one 1/2 in open port (IP44 with BA/PKP-100 knockout plug) |
| Wall Gasket | Closed cell foam |
| Enclosure Ambient | -40° to 221°F (-40° to 105°C) |
| Termination Option | Terminal Strip (-TS) — factory-wired screw terminals |
| Operating Range | Units with plenum-rated wire: -4° to 167°F (-20° to 75°C), 0-100% RH non-condensing |
| Agency | CE EN 61326-1:2013 EMC (Industrial), RoHS, PT = DIN43760 | IEC Pub 751-1983 | JIS C1604-1989 |
Installation Notes
- Wire with twisted pair, 22 AWG minimum, using sealant-filled connectors. Heavier gauge may be needed on long runs.
- Do not share conduit with NEC Class 1, 2 or 3 AC power wiring, or with feeds to motors, contactors or other highly inductive loads.
- Keep the transmitter at least 5 ft from any radio wave-emitting device — two-way radios within that distance can cause interference.
- Wire with power disconnected. Incorrect supply voltage, polarity or connections can damage the unit and will void the warranty.
- Voltage output is set by a 3-position DIP switch on the circuit board. It is set at the factory to your ordered output and can be changed in the field, including to 4-20 mA.
- For strap-on pipe mounting, insulate a minimum of four pipe diameters on each side of the probe (a 1/2 in pipe needs 2 in of insulation each way, wrapped fully around).
- The break-off tab on a BAPI Flexible Probe Bracket (BA/FPB) accepts the 1/4 in probe body and limits heat conduction from the mounting surface.
- Mount the enclosure with #8 screws through at least two opposing tabs; a 1/8 in pilot hole makes this easier.
- Use caulk or Teflon tape on conduit entries, and bring conduit in from the bottom for outdoor or wet locations.
- The -TS terminal strip arrives factory-wired to the sensor. Land the controller pair on "Sensor A Out"; "Sensor A In" is already made up.
Documentation
Product Datasheet (PDF) · Installation & Operation – Transmitters (PDF) · Enclosure Dimensions (PDF)
ZOT Supply is an authorized distributor for Building Automation Products, Inc. (BAPI). This product carries the full BAPI factory warranty.
- Product Family:
- Remote Probe
- Signal Type:
- Voltage Output Transmitter
- Sensing Element:
- 1K Platinum RTD (385 Curve)
- Cable Type:
- Plenum-Rated
- Lead Length:
- 15 ft
- Enclosure:
- BAPI-Box Crossover (BBX)
- Enclosure Rating:
- IP10, NEMA 1
- Probe Material:
- 304 Stainless Steel
- Termination Option:
- Terminal Strip (-TS)
- Mounting Style:
- Strap-On / Bracket / Thermowell
- Calibrated Range:
- 20 to 120F