null Skip to main content

BAPI BA/10K-3-H215-O-BB2 : Outside Air Humidity Transmitter with 10K-3 Thermistor, ±2% RH, 1 to 5 VDC Output, BAPI-Box 2 IP66 / NEMA 4 Enclosure

BAPI

MSRP: $270.00
Your Price:  $125.00
(You save $145.00 )
(No reviews yet) Write a Review
SKU:
BA/10K-3-H215-O-BB2
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
RH Accuracy±2% RH
RH Output1 to 5 VDC
Temperature10K-3 Thermistor
Power10 to 35 VDC / 12 to 27 VAC
EnclosureBAPI-Box 2, IP66 / NEMA 4

BAPI BA/10K-3-H215-O-BB2 Overview

The BAPI BA/10K-3-H215-O-BB2 is an outside air humidity transmitter with a ±2% RH capacitive polymer sensor, a 1 to 5 VDC humidity output and a passive 10K-3 thermistor for outdoor air temperature, housed in a UV-resistant polycarbonate BAPI-Box 2 enclosure rated IP66 / NEMA 4.

BAPI calibrates its humidity transmitters at 10 points from 10 to 90% RH, eliminating field calibration. The humidity sensor sits in a 1 in. diameter probe below the enclosure, protected by a replaceable 80 micron sintered stainless steel filter.

The 1 to 5 VDC humidity output spans 0 to 100% RH, powered from 10 to 35 VDC or 12 to 27 VAC. A separate passive 10K-3 thermistor (Yellow/Red leads) gives the controller a resistance input for outdoor air temperature.

The BAPI-Box 2 enclosure is UV-resistant polycarbonate rated IP66 and NEMA 4, and closed cell foam on the back seals it to the mounting surface.

Specifications verified against BAPI Outside Air Units datasheet Rev. 10/06/25, BAPI installation instructions 49483 rev. 10/06/25, enclosure dimension drawings Rev. 05/26/17 and BAPI enclosure styles application note Rev. 05/02/23. Last reviewed by ZOT Supply on November 3, 2026.

Best For

  • Controllers with 1 to 5 VDC analog inputs for outdoor humidity
  • Controllers with 10K-3 thermistor temperature inputs
  • Panels supplying 10 to 35 VDC or 12 to 27 VAC
  • Exterior walls exposed to rain, sleet, snow, windblown dust and hose-directed water (NEMA 4)

Warranty

BAPI warrants its products to be free from defects in materials and workmanship for five years from the date of sale.

Key Features

10-Point Calibration

Calibrated at 10 points from 10 to 90% RH, eliminating field calibration.

1 to 5 VDC Humidity Output

1 to 5 VDC humidity output for 0 to 100% RH, powered from 10 to 35 VDC or 12 to 27 VAC.

Passive 10K-3 Thermistor

Separate 10K-3 thermistor for outdoor air temperature, accurate to ±0.36°F (0.2°C) from 32 to 158°F (0 to 70°C). Leads are Yellow/Red and are not polarity sensitive.

IP66 / NEMA 4 BAPI-Box 2

UV-resistant polycarbonate enclosure, UL 94 V-0, dust tight and protected against powerful water jets.

Replaceable Sintered Filter

80 micron sintered stainless steel filter unscrews for cleaning; replacement part BA/HDOFS3.

Reverse Polarity Protected

The humidity transmitter is polarity sensitive and reverse polarity protected.

Authorized Distributor

ZOT Supply is an authorized distributor of BAPI products.

Technical Specifications

Humidity
SensorCapacitive polymer
Accuracy±2% RH (10 to 80% RH @ 25°C), ±3% RH (80 to 90% RH @ 25°C), non-condensing
Calibration10 points from 10 to 90% RH
Drift0.5% per year
Response Time< 5 seconds in moving air
RH LinearityNegligible, factory corrected linear from 10 to 80% RH
RH HysteresisFactory corrected to <1%
Output1 to 5 VDC at 0 to 100% RH
Low RH BehaviorOutput goes to its maximum value if humidity drops to 5% RH or below
Output Impedance10 kΩ
WiringRed: power; White: humidity output to controller analog input; Black: common (ground for power and humidity output)
Power
Supply10 to 35 VDC, 22 mA max; 12 to 27 VAC, 0.53 VA max
Temperature Sensor
ElementPassive 10K-3 thermistor
Accuracy±0.36°F (0.2°C) from 32 to 158°F (0 to 70°C)
Lead Wire ColorsYellow/Red (not polarity sensitive)
OutputResistance
Physical
Probe2.4 in. below enclosure, 1 in. diameter
Filter80 micron sintered stainless steel, replaceable (BA/HDOFS3)
EnclosureBAPI-Box 2 (BB2)
Enclosure MaterialUV-resistant polycarbonate, UL 94 V-0
Enclosure RatingIP66, NEMA 4
Enclosure Dimensions4.91 x 2.82 x 2.35 in. (124.8 x 71.6 x 59.7 mm), H x W x D
PortsTwo 1/2 in. NPSM ports and three 1/2 in. drillable ports
Mounting SealClosed cell foam
TerminationOpen wire; 18 to 26 AWG with sealant filled crimp connector (BA/SFC1000-x00) or 26 to 16 AWG with sealant filled wire nut (BA/SFC2000-x00)
Wiring PracticeTwisted pair, 22 AWG minimum; do not run in the same conduit as AC power wiring
Environment and Compliance
Operating Range-40 to 158°F (-40 to 70°C), 0 to 100% RH
CompensationFully temperature compensated
AgencyCE EN 61326-1:2013 EMC, RoHS
Warranty5 years from date of sale

Documentation

Frequently Asked Questions

What is the BAPI BA/10K-3-H215-O-BB2?

The BAPI BA/10K-3-H215-O-BB2 is an outside air humidity transmitter with a ±2% RH capacitive polymer sensor, a 1 to 5 VDC humidity output and a passive 10K-3 thermistor for outdoor air temperature, housed in a UV-resistant polycarbonate BAPI-Box 2 enclosure rated IP66 / NEMA 4.

What power supply does the BAPI BA/10K-3-H215-O-BB2 need?

The BAPI BA/10K-3-H215-O-BB2 runs on 10 to 35 VDC (22 mA max) or 12 to 27 VAC (0.53 VA max). Power requirements depend on the humidity output type.

How accurate is the BAPI BA/10K-3-H215-O-BB2?

Humidity accuracy is ±2% RH (10 to 80% RH @ 25°C), ±3% RH (80 to 90% RH @ 25°C), non-condensing. The 10K-3 thermistor is accurate to ±0.36°F (0.2°C) from 32 to 158°F (0 to 70°C).

How do I convert the 1 to 5 VDC output to percent RH?

Use %RH = (V - 1) / 0.04. The output spans 0 to 100% RH.

Can the BAPI-Box 2 enclosure take hose-directed water?

Yes. The BAPI-Box 2 is rated IP66 (dust tight and protected against powerful water jets from any direction) and NEMA 4 (protected against rain, sleet, snow, windblown dust, splashing water and hose-directed water, and undamaged by external ice formation).

Does an outdoor sensor need a weather shade?

Radiant heat from building surfaces and parking lots affects outdoor temperature and humidity sensors. The BAPI Weather Shade blocks that radiant heat, improving sensor accuracy.

Where should an outside air humidity sensor be mounted?

Mount it in a permanently shaded area away from windows and doors, out of direct sunlight, with the sensor probe pointed down. Seal the wiring hole with caulk after wiring, and terminate with sealant filled connectors.

5-year BAPI warranty from date of sale
Sensor Type:
Outside Air
Humidity Element:
2%
Output Signal:
1-5 VDC
Temperature Element:
10K Type III
CO2 Element:
None
Display:
No Display
VOC Element:
None
Probe Length:
2.4
Enclosure:
NEMA 4 Enclosure
Supported Protocols:
None