BAPI BA/CO-D-BB : Duct Mount Carbon Monoxide Sensor , Field Selectable Ranges and Outputs, Large Display and Two Independent Alarm Contacts, 5-Year Warranty

BAPI

MSRP: $832.00
$361.00
(You save $471.00 )
(No reviews yet) Write a Review
SKU:
BA/CO-D-BB
Condition:
New
Availability:
Ships 2 Weeks
Adding to cart… The item has been added

BAPI BA/CO-D-BB : Duct Mount Carbon Monoxide Sensor , Field Selectable Ranges and Outputs, Large Display and Two Independent Alarm Contacts, 5-Year Warranty

BAPI’s Carbon Monoxide Sensor offers enhanced electrochemical sensing with outstanding accuracy at low concentrations. The Duct unit samples duct air using an aspiration tube.

The sensor has field selectable CO ranges of 0 to 100, 0 to 200, 0 to 300 and 0 to 500 ppm. It also has field selectable outputs of 0 to 5, 1 to 5, 0 to 10 and 2 to 10 VDC as well as a 3-wire 4 to 20 mA output.  The LCD shows the CO reading in ppm and is backlit for 10 seconds after any button push. Two independent SPDT alarm contacts switch at field selectable CO concentrations of 25, 35, 50, 100 and 200 ppm.  A status LED is green when the measured CO is below the lowest relay setpoint.  The LED turns red whenever an alarm relay is on.

An alarm timer holds the output relays on for a field selectable time 0 to 10 minutes after the CO level has fallen below 80% of setpoint.

  • Field Replaceable Long Life Electrochemical Sensor
  • Two Independent Alarm Contacts
  • Field Selectable CO Ranges and Outputs
  • Certificate of Calibration Included with Sensors and Replacement Modules

Specifications

Power: 18 to 28 VAC, 7.2 VA Max
18 to 40 VDC, 180 mA Max
Field Selectable Ranges: 0 to 100, 0 to 200, 0 to 300 & 0 to 500 ppm
Alarm Relays:
  • 2 Independent, Dry SPDT (Form C)
  • 2 Amps at 24 VAC/DC, Resistive
  • 140 VA Inrush, 48 VA Holding at 24 VAC
Field Wiring Terminals: Pluggable Screw Terminals, 14 to 24 AWG
Response Time: <80 seconds from 10% to 90% of range
Alarm Relay Setpoints: 25, 35, 50, 100 or 200 ppm
Alarm Timer: 0, 1, 5 & 10 minutes
Sensor Element Life: 7 Years Typical
Field Selectable Outputs: 3-wire 4 to 20 mA
0 to 5, 1 to 5, 0 to 10, 2 to 10 VDC
Agency: RoHS, CE
Accuracy: <200 ppm = ±3% FS, 32 to 122°F (0 to 50°C)
201 to 500 ppm = ±5% FS, 50 to 122°F (10 to 50°C)
Environmental Operation Range: 14 to 122°F (-10 to 50°C) / 5 to 95%RH Noncondensing

 

Datasheets

pdf logo BAPI Carbon Monoxide (CO) Duct and Rough Service Sensor, Datasheet for Submittal
pdf logo Carbon Monoxide Sensor in a Ventilated BAPI-Box Enclosure Instructions
pdf logo Frequently Asked Questions for the Carbon Monoxide Sensor in a BAPI-Box
Enclosure Style:
Duct
Gas Element:
Carbon Monoxide
Analog Output:
1
Relay Output:
2 SPDT
Communication:
None
Display:
LCD Display