BAPI BA/DCD10-50K-V-BB : Dual Channel "24/7" CO2 Rough Service Sensor, Field Selectable Voltage Output - 0 to 10V Default, 0 to 50,000 ppm Range, 5-Year Warranty
Designed to withstand harsh conditions and measure exceptionally high CO2 concentrations, the BAPI BA/DCD10-50K-V-BB excels in demanding applications.
Key Features:
- Expanded CO2 Detection Range: Measures up to 50,000 ppm, providing reliable monitoring in high-CO2 environments.
- Dual-Channel Accuracy: Ensures precise readings with two independent CO2 sensing channels for enhanced confidence.
- Rugged Construction: Withstands dust, moisture, and extreme temperatures with a NEMA 4, IP66-rated enclosure, ideal for challenging installations.
- Field-Selectable Voltage Output: Offers flexibility with options for 0 to 5 VDC or 0 to 10 VDC output to match control system requirements.
- Comprehensive Warranty: Backed by a 5-year warranty for peace of mind.
Ideal Applications:
- Outdoor air plenums in industrial areas with high CO2 emissions
- Agricultural facilities with CO2 enrichment in harsh environments
- Wastewater treatment plants
- Industrial fermentation processes
- Laboratories and research facilities studying high-CO2 environments
- Any application requiring accurate monitoring of CO2 levels up to 50,000 ppm in demanding conditions
Ensure optimal control and safety in applications with exceptionally high CO2 concentrations and challenging environments with the BAPI BA/DCD10-50K-V-BB CO2 Rough Service Sensor.
Specifications
Power: | 12 to 24 VDC, 240 mA • 18 to 24 VAC, 12 VA Peak |
Field Selectable Voltage Output: | 0 to 5 or 0 to 10 VDC |
Termination: | 3 Terminals, 16 to 22 AWG |
Operating Environment: | 32 to 122°F (0 to 50°C) 0 to 95%RH non-condensing |
CO2 Sensing Element: | Dual Channel Non-Dispersive Infrared (NDIR) |
Unventilated BAPI-Box Enclosure Rating: | NEMA 4, IP66 |
Enclosure Material: | Polycarbonate, UL94 V-O |
CO2 Detection Range: | 0 to 2,000, 0 to 5,000 and 0 to 50,000 ppm |
Start-Up Time: | <2 Minutes |
Response Time: | <2 Minutes for 90% step change typical (after start-up) |
CO2 Accuracy: | 400 to 1,000 ppm: ±75 ppm >1,000 ppm: ±10% of reading |
CO2 Drift Stability: | <5% of full scale over life of product. |
Agency: | RoHS, CE, Title 24 Requirements |
Warranty Period: | 5 Years |
Datasheets
- Sensor Type:
- Rough Service
- Humidity Element:
- None
- CO2 Element:
- Yes
- Temperature Element:
- None
- Display:
- No Display
- VOC:
- No