BAPI BA/DCD10-5K-D-BB : Dual Channel "24/7" CO2 Duct Sensor, Field Selectable Voltage Output - 0 to 10V Default, 0 to 5,000 ppm Range, 5-Year Warranty
Reliable CO2 Monitoring for Demanding Duct Environments: The BAPI BA/DCD10-5K-D-BB Sensor
Designed for continuous CO2 monitoring in challenging duct environments, the BAPI BA/DCD10-5K-D-BB offers a comprehensive solution for maintaining optimal indoor air quality.
Key Features:
- Expanded CO2 Detection Range: Measures up to 5,000 ppm, providing versatility for various applications.
- Dual-Channel Accuracy: Ensures precise readings with two independent CO2 sensing channels.
- Field-Selectable Voltage Output: Offers flexibility with options for 0 to 5 VDC or 0 to 10 VDC output.
- Rugged Construction: Withstands harsh duct environments with a NEMA 4, IP66-rated enclosure.
- Intuitive LED Indicators: Clearly display CO2 levels (Good, Fair, Poor) for at-a-glance assessment.
- Comprehensive Warranty: Backed by a 5-year warranty for peace of mind.
Ideal Applications:
- Commercial and industrial buildings with demanding duct environments
- Schools, hospitals, and healthcare facilities
- Office buildings and meeting rooms
- Indoor agricultural facilities
- Industrial and manufacturing facilities with potential for higher CO2 levels
- Laboratories and research facilities requiring precise CO2 monitoring
Ensure optimal indoor air quality and efficient ventilation control in a variety of demanding duct applications with the dependable BAPI BA/DCD10-5K-D-BB CO2 Sensor.
Specifications
Power: | 12 to 24 VDC, 240 mA • 18 to 24 VAC, 12 VA Peak |
Field Selectable Voltage Output: | 0 to 5 or 0 to 10 VDC |
Termination: | 3 Terminals, 16 to 22 AWG |
Operating Environment: | 32 to 122°F (0 to 50°C) 0 to 95%RH non-condensing |
CO2 Sensing Element: | Dual Channel Non-Dispersive Infrared (NDIR) |
Unventilated BAPI-Box Enclosure Rating: | NEMA 4, IP66 |
Enclosure Material: | Polycarbonate, UL94 V-O |
CO2 Detection Range: | 0 to 2,000, 0 to 5,000 and 0 to 50,000 ppm |
Start-Up Time: | <2 Minutes |
Response Time: | <2 Minutes for 90% step change typical (after start-up) |
CO2 Accuracy: | 400 to 1,000 ppm: ±75 ppm >1,000 ppm: ±10% of reading |
CO2 Drift Stability: | <5% of full scale over life of product. |
Agency: | RoHS, CE, Title 24 Requirements |
Warranty Period: | 5 Years |
Datasheets
- Sensor Type:
- Duct
- Humidity Element:
- None
- CO2 Element:
- Yes
- Temperature Element:
- None
- Display:
- No Display
- VOC:
- No