Part Number
BA/HQF-B-C-1-B80-J-F
Humidity Output
0-10 VDC
Temp Sensor
10K-2 Thermistor
Display
Fahrenheit Display
Mounting
Standard J-Box
Warranty
5 Years
The BA/HQF-B-C-1-B80-J-F is a BAPI-Stat Quantum combination room temperature and humidity sensor with a 10K-2 Thermistor temperature element and 0-10 VDC humidity output. The unit is equipped with a high-contrast LCD displaying temperature in °F, humidity in %RH, and occupancy status. An on-unit slider provides occupant setpoint adjustment with a -5 to +5 Offset display range and 0-20KΩ output to the controller. Occupancy override is configured as Separate Output. The capacitive polymer humidity element is factory-calibrated to ±2% RH at 25°C across the 20 to 80% RH range.
Best For
Occupied spaces where the BMS needs both ambient temperature and humidity feedback alongside occupant comfort control. The slider setpoint and override give occupants comfort input while maintaining BAS authority over scheduling and limits.
5-YEAR WARRANTY
Backed by BAPI's 5-Year Warranty. Factory-calibrated and tested to BAPI's quality standards before shipment.
Key Features
High-Contrast LCD
Upgraded display improves clarity at greater viewing distances, showing temperature, humidity, and occupancy status.
Capacitive Polymer Humidity Element
Long-term stable capacitive polymer sensor ±2% RH at 25°C across the 20 to 80% RH range, factory calibrated.
10K-2 Thermistor Temp Sensor
Passive 10K Type II Thermistor temperature element compatible with most BAS controller inputs.
Slider Setpoint Adjustment
Front-panel slider for occupant setpoint adjustment with -5 to +5 Offset display range and 0-20KΩ output to controller.
Occupancy Override Button
Push-button occupant override configured as Separate Output. Human Icon on display indicates override status when latched by controller XIN signal.
Optional Accessories Included
Includes: Test & Balance Switch.
Field Calibration
±5% RH field calibration adjustment in 0.1% increments via potentiometer (units without display) or programming pages (units with display).
Modern Quantum Enclosure
Clean modern ABS enclosure (UL94 V-0) mounts to standard 2"x4" junction box, European junction box, or directly to drywall (screws included).
Technical Specifications
| Part Number | BA/HQF-B-C-1-B80-J-F |
| Sensor Type | Room Temperature + Humidity |
| Humidity Sensor | Capacitive Polymer, ±2% RH @ 25°C, 20 to 80% RH |
| Humidity Output | 0 to 10 VDC Output |
| Temperature Sensor | 10K Type II Thermistor |
| Temp Accuracy | ±0.36°F Thermistor, ±0.5°F RTD (typical) |
| Display | °F |
| Setpoint Adjustment | Slider Setpoint Adjustment |
| Setpoint Display Range | -5 to +5 |
| Setpoint Output Range | 0 to 20KΩ |
| Occupant Override | Override as Separate Output |
| Power | 15 to 35 VDC or 15 to 28 VAC |
| Power Consumption | 20 mA max (4-20 mA), 4 mA max (0-5/0-10 VDC), 0.1 VA max (AC) |
| Field Calibration | ±5% RH in 0.1% increments (factory calibrated) |
| Wiring | 2 to 5 pair, 16 to 22 AWG |
| Mounting | Standard 2"x4" J-Box Mount |
| Operating Range | 32 to 122°F (0 to 50°C), 0 to 95% RH non-condensing |
| Enclosure | ABS Plastic, UL 94 V-0 |
| Agency | CE EN 61326-1:2013 EMC, RoHS |
| Warranty | 5 Years |
| Included Options | Test & Balance Switch |
Documentation
Frequently Asked Questions
What is the humidity sensor accuracy?
±2% RH at 25°C (77°F) across the 20 to 80% RH range, using a capacitive polymer sensing element. Field calibration adjustment of ±5% RH in 0.1% increments is available.
What temperature sensor is included in the BA/HQF-B-C-1-B80-J-F?
This unit is configured with a 10K Type II Thermistor. The temperature sensor is passive (resistance output) and connects to terminals SEN1 and SEN2.
What does the display show?
The high-contrast LCD displays temperature in °F, relative humidity in %RH, and the Human Icon for occupancy status. Display options can be configured via programming pages including rotating, fixed major/minor, and single-value modes.
How does the occupancy override work?
Pressing the override button closes a dry contact across the override output (resistance <15 ohms) and lights the Human Icon on the display. To latch the icon, the controller must connect terminal XIN to ground via a dry contact. Without the XIN confirmation signal, the icon clears after 5 seconds.
Can this sensor be field-calibrated?
Yes. Both temperature offset (P1) and humidity offset (P2) are set via the unit's programming pages in ±0.1° / ±0.1% RH increments. Enter Program Mode by setting DIP Switch S1 #1 (PAGES) to ON. A high-accuracy reference is recommended.
What mounting options are supported?
Standard 2"x4" junction box, drywall mount with included anchors, or European junction box (60mm mounting centers using the BA/HQ60 variants). Mounting screws are included.