null Skip to main content

BAPI BA/HQF-B-C-1-P81-N : BAPI-Stat Quantum Room Temp/Humidity Sensor, F LCD Display, 0-10 VDC Humidity, 10K-2 Thermistor, Slider Setpoint (Custom Range / 4.75K-24.75KΩ), Override Parallel w/ Sensor

BAPI

MSRP: $368.00
$166.00
(You save $202.00 )
(No reviews yet) Write a Review
SKU:
BA/HQF-B-C-1-P81-N
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
Part Number
BA/HQF-B-C-1-P81-N
Humidity Output
0-10 VDC
Temp Sensor
10K-2 Thermistor
Display
Fahrenheit Display
Mounting
Standard J-Box
Warranty
5 Years

The BA/HQF-B-C-1-P81-N is a BAPI-Stat Quantum combination room temperature and humidity sensor with a 10K-2 Thermistor temperature element and 0-10 VDC humidity output. The unit is equipped with a high-contrast LCD displaying temperature in °F, humidity in %RH, and occupancy status. An on-unit slider provides occupant setpoint adjustment with a Special (P) display range and 4.75K-24.75KΩ output to the controller. Occupancy override is configured as Parallel w/ Sensor. The capacitive polymer humidity element is factory-calibrated to ±2% RH at 25°C across the 20 to 80% RH range.

Best For
Occupied spaces where the BMS needs both ambient temperature and humidity feedback alongside occupant comfort control. The slider setpoint and override give occupants comfort input while maintaining BAS authority over scheduling and limits.
5-YEAR WARRANTY
Backed by BAPI's 5-Year Warranty. Factory-calibrated and tested to BAPI's quality standards before shipment.

Key Features

High-Contrast LCD
Upgraded display improves clarity at greater viewing distances, showing temperature, humidity, and occupancy status.
Capacitive Polymer Humidity Element
Long-term stable capacitive polymer sensor ±2% RH at 25°C across the 20 to 80% RH range, factory calibrated.
10K-2 Thermistor Temp Sensor
Passive 10K Type II Thermistor temperature element compatible with most BAS controller inputs.
Slider Setpoint Adjustment
Front-panel slider for occupant setpoint adjustment with Special (P) display range and 4.75K-24.75KΩ output to controller.
Occupancy Override Button
Push-button occupant override configured as Parallel w/ Sensor. Human Icon on display indicates override status when latched by controller XIN signal.
Field Calibration
±5% RH field calibration adjustment in 0.1% increments via potentiometer (units without display) or programming pages (units with display).

Technical Specifications

Part NumberBA/HQF-B-C-1-P81-N
Sensor TypeRoom Temperature + Humidity
Humidity SensorCapacitive Polymer, ±2% RH @ 25°C, 20 to 80% RH
Humidity Output0 to 10 VDC Output
Temperature Sensor10K Type II Thermistor
Temp Accuracy±0.36°F Thermistor, ±0.5°F RTD (typical)
Display°F
Setpoint AdjustmentSlider Setpoint Adjustment
Setpoint Display RangeSpecial Setpoint Display Range (Code P)
Setpoint Output Range4.75K to 24.75KΩ
Occupant OverrideOverride in Parallel with Sensor
Power15 to 35 VDC or 15 to 28 VAC
Power Consumption20 mA max (4-20 mA), 4 mA max (0-5/0-10 VDC), 0.1 VA max (AC)
Field Calibration±5% RH in 0.1% increments (factory calibrated)
Wiring2 to 5 pair, 16 to 22 AWG
MountingStandard 2"x4" J-Box Mount
Operating Range32 to 122°F (0 to 50°C), 0 to 95% RH non-condensing
EnclosureABS Plastic, UL 94 V-0
AgencyCE EN 61326-1:2013 EMC, RoHS
Warranty5 Years

Documentation

Frequently Asked Questions

What is the humidity sensor accuracy?
±2% RH at 25°C (77°F) across the 20 to 80% RH range, using a capacitive polymer sensing element. Field calibration adjustment of ±5% RH in 0.1% increments is available.
What temperature sensor is included in the BA/HQF-B-C-1-P81-N?
This unit is configured with a 10K Type II Thermistor. The temperature sensor is passive (resistance output) and connects to terminals SEN1 and SEN2.
What does the display show?
The high-contrast LCD displays temperature in °F, relative humidity in %RH, and the Human Icon for occupancy status. Display options can be configured via programming pages including rotating, fixed major/minor, and single-value modes.
How does the occupancy override work?
Pressing the override button closes a dry contact across the override output (resistance <15 ohms) and lights the Human Icon on the display. To latch the icon, the controller must connect terminal XIN to ground via a dry contact. Without the XIN confirmation signal, the icon clears after 5 seconds.
Can this sensor be field-calibrated?
Yes. Both temperature offset (P1) and humidity offset (P2) are set via the unit's programming pages in ±0.1° / ±0.1% RH increments. Enter Program Mode by setting DIP Switch S1 #1 (PAGES) to ON. A high-accuracy reference is recommended.
What mounting options are supported?
Standard 2"x4" junction box, drywall mount with included anchors, or European junction box (60mm mounting centers using the BA/HQ60 variants). Mounting screws are included.