null Skip to main content

BAPI BA/HQX-X-C-X-XX-N : BAPI-Stat Quantum Room Humidity Sensor, No Display, 0-10 VDC Humidity, Override Parallel w/ Sensor

BAPI

MSRP: $301.00
$135.00
(You save $166.00 )
(No reviews yet) Write a Review
SKU:
BA/HQX-X-C-X-XX-N
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
Part Number
BA/HQX-X-C-X-XX-N
Humidity Output
0-10 VDC
Mounting
Standard J-Box
Warranty
5 Years

The BA/HQX-X-C-X-XX-N is a BAPI-Stat Quantum room humidity sensor providing a 0-10 VDC output signal for connection to your building automation system. Occupancy override is configured as Parallel w/ Sensor. The capacitive polymer humidity element is factory-calibrated to ±2% RH at 25°C across the 20 to 80% RH range.

Best For
Spaces where humidity monitoring alone is required — server rooms, storage areas, archives, and process environments where temperature is monitored by a separate dedicated sensor.
5-YEAR WARRANTY
Backed by BAPI's 5-Year Warranty. Factory-calibrated and tested to BAPI's quality standards before shipment.

Key Features

Sensor-Only Configuration
Configured without an LCD display for sense-only applications where the controller handles all logic and feedback.
Capacitive Polymer Humidity Element
Long-term stable capacitive polymer sensor ±2% RH at 25°C across the 20 to 80% RH range, factory calibrated.
Occupancy Override Button
Push-button occupant override configured as Parallel w/ Sensor. Human Icon on display indicates override status when latched by controller XIN signal.
Field Calibration
±5% RH field calibration adjustment in 0.1% increments via potentiometer (units without display) or programming pages (units with display).

Technical Specifications

Part NumberBA/HQX-X-C-X-XX-N
Sensor TypeRoom Humidity Only
Humidity SensorCapacitive Polymer, ±2% RH @ 25°C, 20 to 80% RH
Humidity Output0 to 10 VDC Output
DisplayNo Display
Setpoint AdjustmentNo Setpoint Adjustment
Occupant OverrideOverride in Parallel with Sensor
Power15 to 35 VDC or 15 to 28 VAC
Power Consumption20 mA max (4-20 mA), 4 mA max (0-5/0-10 VDC), 0.1 VA max (AC)
Field Calibration±5% RH in 0.1% increments (factory calibrated)
Wiring2 to 5 pair, 16 to 22 AWG
MountingStandard 2"x4" J-Box Mount
Operating Range32 to 122°F (0 to 50°C), 0 to 95% RH non-condensing
EnclosureABS Plastic, UL 94 V-0
AgencyCE EN 61326-1:2013 EMC, RoHS
Warranty5 Years

Documentation

Frequently Asked Questions

What is the humidity sensor accuracy?
±2% RH at 25°C (77°F) across the 20 to 80% RH range, using a capacitive polymer sensing element. Field calibration adjustment of ±5% RH in 0.1% increments is available.
How does the occupancy override work?
Pressing the override button closes a dry contact across the override output (resistance <15 ohms) and lights the Human Icon on the display. To latch the icon, the controller must connect terminal XIN to ground via a dry contact. Without the XIN confirmation signal, the icon clears after 5 seconds.
Can this sensor be field-calibrated?
Yes. Humidity offset is set via potentiometer R12 on the circuit board, providing ±5% RH adjustment in 0.1% increments. A high-accuracy humidity reference is recommended.
What mounting options are supported?
Standard 2"x4" junction box, drywall mount with included anchors, or European junction box (60mm mounting centers using the BA/HQ60 variants). Mounting screws are included.