The BAPI Wireless Setpoint Output Module (BA/SOM-BLE-EZ) converts setpoint data from a BAPI wireless room sensor into a 0 to 10V voltage output for the BAS controller, allowing occupants to adjust their space temperature setpoint wirelessly. The override output briefly drops to 0 when the occupant presses the override button on the room sensor, signaling a timed occupancy override to the controller. Also available without override as BA/SOM-BLE-10-EZ.
Best for: BAS applications where occupant setpoint adjustment is required. Works with BAPI-Stat Quantum wireless room sensors that have the optional setpoint slider.
Carries BAPI's 5-year warranty. On lost comm (35 minutes), the output holds the last commanded setpoint value and the blue LED blinks. Recovers automatically on next transmission.
0 to 10V voltage Setpoint Output
Linearly scaled voltage output representing the occupant's wireless setpoint adjustment. Factory calibrated — no field adjustment required.
Wireless Occupant Setpoint Control
Works with BAPI-Stat Quantum wireless room sensors equipped with the optional setpoint slider. Allows space-level setpoint adjustment without running additional control wiring.
Override Output Available
Override output drops to 0 when the override button on the sensor is pressed, immediately signaling the controller.
Lost Comm Hold
After 35 minutes without a transmission, the SOM holds the last commanded setpoint value rather than reverting to an extreme value, protecting occupant comfort during brief outages.
| Specification | Value |
|---|---|
| Part Number | BA/SOM-BLE-10-EZ-O |
| Output Range | 0 to 10V voltage |
| Output Resolution | 150 µV (voltage) or 100 ohm (resistance) |
| Override Output | Yes — drops to 0 on override button press |
| Supply Power | 15 to 24 VDC or powered through receiver |
| Power Consumption | 25 mA @ 24 VDC (voltage) or 20 mA @ 24 VDC (resistance) |
| Lost Comm Timeout | 35 minutes — holds last setpoint value |
| Operating Temp | 32 to 140°F (0 to 60°C) |
| Mounting | Surface, 2.75 in snaptrack, or 35mm DIN rail |
| Agency | RoHS |
| Warranty | 5 Years |
Voltage Outputs
BA/SOM-BLE-00-EZ (0-5V), BA/SOM-BLE-10-EZ (0-10V). Resistance Outputs: BA/SOM-BLE-60-EZ (0-10K ohm), BA/SOM-BLE-81-EZ (4.75K-24.75K ohm). Add -O suffix to any part number for override output version.
- Module Type:
- Analog Output Module
- Output Type:
- Setpoint
- Output Signal:
- 0 to 10V
- Override Output:
- Yes