null Skip to main content
Image coming soon

BAPI BA/VOM-BLE-05-H-F-EZ : Wireless Voltage Output Module, 0 to 5 VDC, Temperature -20 to 120 F

BAPI

MSRP: $150.00
$67.73
(You save $82.27 )
(No reviews yet) Write a Review
SKU:
BA/VOM-BLE-05-H-F-EZ
Condition:
New
Availability:
Ships 3-5 days
Adding to cart… The item has been added
Part Number
BA/VOM-BLE-05-H-F-EZ
 
Output
0 to 5 VDC
 
Range
-20 to 120°F (-29 to 49°C)
 
Measure
Temperature
 
List Price
$150
 
Warranty
5 Years

The BAPI Wireless Voltage Output Module (BA/VOM-BLE-EZ) converts temperature data received from the BAPI Wireless Receiver into a linear 0 to 5 VDC signal for the BAS controller. This variant is scaled for -20 to 120°F (-29 to 49°C). Wide range for outdoor air and freezer-adjacent applications. With 150 microvolt output resolution and 4K ohm minimum load, it is compatible with virtually all DDC analog voltage inputs.

Best for: BAS controllers with 0 to 5 VDC temperature analog inputs that need wireless sensor data without any controller reprogramming.

5-Year Warranty

Carries BAPI's 5-year warranty. On lost comm (35 minutes without transmission), the output reverts to 0V (indicates low temperature) so the controller detects a fault condition. Recovers automatically on next transmission.

0 to 5 VDC Output — Factory Calibrated

Linearly scaled temperature output from -20 to 120°F (-29 to 49°C). Factory calibrated, 150 µV resolution, 4K ohm minimum load. No field adjustment required.

Direct Drop-In for Hardwired Sensors

Connects to the controller's 0 to 5 VDC temperature input exactly like a hardwired transmitter. No controller programming changes needed.

Powered Through Receiver

Powers in-line through the BAPI BLE Receiver for up to 10 modules. Remote mounting beyond 100 ft requires a separate 15 to 24 VDC supply.

Lost Comm Protection

After 35 minutes without a transmission, the output reverts to 0V (indicates low temperature). Recovers automatically when the next transmission is received.

SpecificationValue
Part NumberBA/VOM-BLE-05-H-F-EZ
Output Voltage0 to 5 VDC
Range-20 to 120°F (-29 to 49°C)
Output Resolution150 µV
Output Current2.5 mA @ 4K ohm load
Minimum Load Resistance4K ohm
Supply Power15 to 24 VDC or powered through receiver
Power Consumption25 mA @ 24 VDC
Lost Comm Timeout35 minutes — reverts to 0V (indicates low temperature)
Operating Temp32 to 140°F (0 to 60°C)
MountingSurface, 2.75 in snaptrack, or 35mm DIN rail
AgencyRoHS
Warranty5 Years
Does the VOM require any controller reprogramming?
No. The VOM outputs a standard linear 0 to 5 VDC signal. The controller sees it as a normal hardwired transmitter — no software changes needed.
What happens if wireless communication is lost?
After 35 minutes, the output reverts to 0V (indicates low temperature). It recovers automatically on the next transmission.
What VOM ranges are available?
BAPI VOM modules are available in 0-5V and 0-10V output with 8 temperature ranges and 2 humidity ranges. Contact us or search by part number for the range you need.
Module Type:
Analog Output Module
Output Type:
Voltage
Output Voltage:
0 to 5 VDC
Measures:
Temperature
Temp Range:
-20 to 120 F