BAPI ZPS-10-FR78-BB-NT : Fixed Range Pressure (FRP) Differential Pressure Sensor, 0-10V Output, -2.5" to 2.5" Bidirectional Pressure Range, No Tube included, NEMA 4 Enclosure, 5-Color LED to Indicate Pressure Status, 5-Year Warranty
The BAPI Fixed Range Pressure Sensor (FRP) is a budget-friendly option for precise pressure measurement. It features a single, factory-set pressure and output range for each sensor, simplifying installation and reducing costs by a third compared to adjustable models. A single button auto-zeros the unit, while its rugged construction and visible LED indicator keep you informed of pressure status.
Features & Options
- Single Pressure Range and Single Output Range
- Optional Attached Static Pressure Probe So the Unit Doesn’t Require Two Trades to Install
- Simple Auto-Zero Process
- Rugged IP66, NEMA 4 Enclosure with Hinged Cover
- Visible 5-Color LED to Indicate Current Pressure Status Without Having to Access the BASReverse Wiring Protection
- Free NIST Certificate Included with Each Unit at No Extra Charge
Multicolor LED Status Indicator
The LED is on whenever power is applied. The LED color varies according to the following list:
- Red = Over pressure
- Green = Top half of span
- Amber = Center of span
- Blue = Bottom half of span
- Purple = Under pressure.
Specifications
Power: | 18 to 28 VAC @ 1 VA max (DC Power varies - See Data Sheet) |
System Accuracy at 72°F: | For units ≥ 0.25” WC (62.5 Pa) ±1.0% FS of input range For units < 0.25” WC (62.5 Pa) ±0.5% FS of input range |
Environmental Operation Range: | 14 to 140°F (-10 to 60°C) |
Storage Temp: | -40 to 203°F (-40 to 95°C) |
Stability: | 0.15% FS per year |
Overpressure: | Proof: 27.68” WC (1 PSI) Burst: 41.52” WC (1.5 PSI) |
Wiring: | 3-wires, AC or DC powered, Voltage out |
Humidity: | 0 to 95% RH, non-condensing |
Port Connection: | 1/4” tubing (1/8 to 3/16” ID) |
Enclosure Material & Rating: | UV-resistant Polycarb., UL94 V-0, IP66, NEMA 4 |
Mounting: | 4 external tabs with holes for #10 screws |
Datasheets
BAPI Fixed Range Pressure (FRP), Data-sheet for Submittal | |
Fixed Range Pressure (FRP) Transmitter Installation & Operation Sheet | |
Frequently Asked Questions - BAPI's Pressure Line of Products |
- Output Signal:
- 0-10VDC
- Pressure Type:
- Differential
- Pressure Ranges:
- 0 to 2.5 Inch
- Media:
- Dry
- Accuracy:
- 1.0%
- LCD Display:
- 5-Color LED
- Zero Function:
- Yes
- Range Setting:
- Fixed
- Communication:
- None
- Series:
- FRP Series