null Skip to main content
Image coming soon

BAPI ZPS-10-SR80-EZ-NT : EZ Pressure Sensor, 0-10 VDC Fixed Output, -5.00 to 5.00 in WC Bidirectional Fixed Range, Standard Range, ±0.25% FS Accuracy, No Tube, LCD Display, DIN Rail/Snaptrack/Surface Mount

BAPI

MSRP: $409.00
$162.00
(You save $247.00 )
(No reviews yet) Write a Review
SKU:
ZPS-10-SR80-EZ-NT
Condition:
New
Availability:
Ships in 3-5 Days
Adding to cart… The item has been added
Output (Fixed)0 to 10 VDC
Range (Fixed)-5.00 to 5.00” WC Bidirectional
Accuracy±0.25% FS
ProbeNo Tube Included
DisplayLCD Display
MountingDIN Rail / Snaptrack / Surface

The BAPI ZPS-10-SR80-EZ-NT is a factory-configured EZ Pressure Sensor with a fixed 0 to 10 VDC output and a fixed -5.00 to 5.00” WC Bidirectional pressure range (range code SR80). Unlike the field-selectable EZ variants, the output and pressure range are factory-set, reducing commissioning to an auto-zero only — no switch adjustments needed in the field. Direction (uni/bidirectional) and units (inches WC or Pascals) remain field-adjustable. No pressure tube is included — connect your own tubing to the 3/16” barbed ports. The LCD display reads live pressure over the full operational range. Mounts on DIN rail, 2.75” Snaptrack, or surface. A NIST-traceable calibration certificate is available at no extra charge.

Best for: Panel-mounted duct static pressure, fan discharge, VAV box pressure, and building pressurization where the pressure range and output are confirmed at design time. The factory-set configuration eliminates field misconfiguration risk and speeds commissioning in large installations where many sensors share the same spec.

Fixed 0-10 VDC Output

Output is factory-set to 0 to 10 VDC — no rotary-switch output adjustment needed in the field. Power: 12 to 40 VDC or 9 to 28 VAC. Wiring: 3-wire via removable/pluggable terminal block (14–24 AWG).

Fixed SR80: -5.00 to 5.00” WC

Pressure range factory-set to -5.00 to 5.00” WC (bidirectional). Accuracy: ±0.25% FS • +/-0.025 in WC (+/-6.22 Pa). Total Error Band: +/-0.5% FS or +/-0.05 in WC (+/-12.44 Pa). Auto-zero via NEXT button after mounting. No range switch adjustment required.

DIN Rail / Snaptrack / Surface

Blue mounting tabs extend for DIN rail or surface, push in for 2.75” Snaptrack — no tools to switch modes. 3/16” barbed ports accept 1/8”–3/16” ID tubing. Pair with ZPS-ACC07 for a duct or plenum pressure tap. About 1/3 the panel footprint of field-mount sensors.

Full Specifications

ZPS-10-SR80-EZ-NT EZ Pressure Sensor
ManufacturerBuilding Automation Products, Inc. (BAPI)
Part NumberZPS-10-SR80-EZ-NT
Range CodeSR80 — -5.00 to 5.00” WC Bidirectional
Output (Fixed)0 to 10 VDC
Pressure Range (Fixed)-5.00 to 5.00” WC Bidirectional
Accuracy±0.25% FS at 77°F (25°C) • +/-0.025 in WC (+/-6.22 Pa)
Total Error Band+/-0.5% FS or +/-0.05 in WC (+/-12.44 Pa)
Temp Hysteresis & Stability+/-0.25% at 77 deg F (25 deg C) for 1,000 hours
Field-SelectableDirection (uni/bidirectional), units (in WC / Pascals)
Power12 to 40 VDC or 9 to 28 VAC
WiringRemovable terminal block, 14–24 AWG; 3-wire
OverpressureProof 300 in WC (74 kPa)
Pressure Port3/16” barb (4.75 mm)
Probe / TubeNo Tube Included
DisplayLCD — live pressure over full operational range
MountingDIN Rail, 2.75” Snaptrack, or Surface
EnclosureABS Plastic, UL94 V-0 • 1.94 x 1.89 x 3.35” (49.2 x 48 x 85 mm)
Operating Temp14 to 131°F (−10 to 55°C)
Storage Temp−4 to 140°F (−20 to 60°C)
Humidity0 to 95% RH, non-condensing
AgencyRoHS, CE EN 61326-1:2013 EMC
NIST CertificateAvailable at no extra charge
Warranty5 Years

Frequently Asked Questions

What pressure range does range code SR80 correspond to?

SR80 specifies a factory-set standard range of -5.00 to 5.00 in WC (bidirectional). This range and the 0 to 10 VDC output are both fixed at the factory and cannot be changed in the field. Direction (uni/bidirectional) and units (inches WC or Pascals) remain field-adjustable via the rotary switch.

How do I auto-zero the ZPS-10-SR80-EZ-NT?

Connect the high and low pressure ports together using a short length of tubing without kinks. Set the rotary switch to the 0 position — the LCD display shows Aut0. Press the NEXT button; the display shows a series of progress bars, then donE for about 4 seconds. Return the switch to the desired pressure range. For critical applications, re-zero 2–3 times per year. Allow 24 hours unpowered acclimation and 60 minutes powered deadheaded before the first auto-zero.

What is the power requirement for the 0-10 VDC output on this unit?

The 0 to 10 VDC output requires 12 to 40 VDC or 9 to 28 VAC. For 4 to 20 mA output, the minimum voltage increases with controller input impedance: minimum voltage = (0.02 x load impedance in ohms) + 8. Example: with a 250 ohm input the minimum is 13 VDC. Connect power to the PWR terminal, controller input to the GND/4-20mA terminal (for current loop) or Voltage Out terminal (for VDC outputs).

WARRANTYBAPI backs every EZ Pressure Sensor with a 5-year manufacturer warranty against defects in materials and workmanship. ZOT Supply is an authorized BAPI distributor — contact us for warranty terms and technical support.