Belimo 22DTM-56 : Duct CO2 / Humidity / Temperature Sensor, 2% Accuracy, Outputs: 0-5 VDC or 0-10 VDC, Temperature Transmitter, BACnet communication, UL Enclosure Type 4X/IP65
For measuring CO2, with integrated temperature and humidity sensor. Dual channel CO2 technology. With BACnet MS/TP communication and integrated 0...10 V outputs. NEMA 4X / IP65 rated enclosure.
Specifications
Voltage AC/DC | AC/DC 24 V |
Electrical Connection | Terminals |
Measured Values | CO2/Temperature/Humidity |
Output Signal | BACnet / 0...5 V / 0...10 V |
Measuring Range CO₂ |
Default setting: 0...2000 ppm / With A-22G-A05: 0...5000 ppm |
Measuring Range Humidity | Adjustable via BACnet / Default setting: 0...100% RH |
Measuring Range Temperature |
Adjustable via BACnet / 32...122°F [0...50°C] |
Communication | BACnet MS/TP |
Output Voltage [Range] | 2 x 0...5 V, 0...10 V, min. resistance 10 kΩ |
Output signal active note | Output 0...5/10 V with jumper adjustable |
Probe Length | 7" [180 mm] |
Datasheets
Technical data sheet – 22DTM-56 | |
Installation instructions - 22DTM-..5, 22DTM-..6 | |
Belimo Sensor Brochure | |
Sensors Master Format - Consultant Specifications |
- Sensor Type:
- Duct
- Output Signal:
- 0-5 VDC or 0-10 VDC
- Temperature Element:
- Transmitter
- Supported Protocols:
- BACnet
- Humidity Element:
- 2%
- CO2 Element:
- Yes
- Display:
- No Display
- Probe Length:
- 8