PS24FX-C-D-N-D — PowerScout FLEX 24 Multi-Circuit Power Submeter
The Dent Instruments PS24FX-C-D-N-D is part of the PowerScout FLEX 24 family, DENT's next-generation 24-channel multi-circuit submeter that replaces the PowerScout™ HD. The PS24FX-C-D-N-D measures voltage, current, power, energy, and many other electrical parameters on any combination of single- and three-phase loads — up to 8 three-phase or 24 single-phase circuits across two voltage references — making it well suited to high-density tenant submetering, bi-directional metering, and real-time monitoring across commercial and industrial facilities.
The PS24FX-C-D-N-D delivers revenue-grade performance with continuous 7.2 kHz sampling (no blind cycles), a 1-second parameter update rate, and ANSI C12.1-2024 Class 0.2 accuracy when paired with an appropriate CT. It supports both BACnet and Modbus, includes four digital pulse inputs and a 12 VDC auxiliary output, and provides RS-485 serial and Ethernet as standard. Setup is handled through FLEXPoint™ PC software or the browser-based FLEXPoint™ GO web server, and DENT's patented PhaseChek™ circuitry (U.S. Patent 7,612,552) confirms correct CT orientation during commissioning.
This model ships as a DENTCloud™-enabled unit: the PS24FX-C-D-N-D is factory-provisioned for direct connectivity to the subscription-free DENTCloud™ platform, giving authorized users remote access to real-time and historical metering data through any web browser without adding a separate gateway.
Built as a UL-Listed ABS enclosure, the PS24FX-C-D-N-D is delivered in the Enclosure configuration with the TouchSSā™ high-voltage cover for an added layer of protection. Like all PowerScout meters, the PS24FX-C-D-N-D operates as an endpoint that reports to a building management system, RTU, data acquisition device, or DENTCloud™ host rather than as a standalone recorder.
Best for
- High-density tenant and accountability submetering — up to 24 circuits from one device
- Bi-directional metering for solar, wind, and other renewable or storage interconnections
- Monitoring building mains, HVAC, pumps, motors, and equipment loads
- Multi-circuit measurement using Virtual Meters to group the PS24FX-C-D-N-D's 24 channels by load
- Hospitals, data centers, and government projects requiring Made in USA / BAA / TAA equipment
Key Features
DENTCloud™ Enabled
The PS24FX-C-D-N-D is factory-enabled for direct connectivity to the subscription-free DENTCloud™ platform, giving authorized users remote access to real-time and historical metering data from any web browser without a separate gateway.
FLEXPoint™ + FLEXPoint™ GO
Configure the PS24FX-C-D-N-D from a rebuilt PC application or directly from any web browser with FLEXPoint GO — no software install required for on-site changes, validation, and field troubleshooting.
Flexible Virtual Meters
Assign any of the 24 CT channels to any load in any combination — single-phase, split-phase, or three-phase groupings — and meter multiple loads from a single PS24FX-C-D-N-D with consistent load labels across software, the LCD, register exports, and cloud systems.
Dual-Protocol + 4 Pulse Inputs
The PS24FX-C-D-N-D speaks both BACnet and Modbus over RS-485 and Ethernet, adds four digital pulse inputs for gas, water, or other meters, and uses an IEEE-754 floating-point register map that flattens all Virtual Meters to a single address.
PhaseChek™ + Revenue-Grade Accuracy
Built-in PhaseChek verification confirms correct CT orientation and phase matching to reduce installation errors, while the PS24FX-C-D-N-D meets ANSI C12.1-2024 Class 0.2 revenue-grade accuracy (dependent on CT selection).
Universal CT Compatibility
Mix and match a full range of 333.3 mV CTs — Solid Core, Split Core, or RōCoil™ (Rogowski) — including revenue-grade options, measuring up to 4000 A depending on the CT used with the PS24FX-C-D-N-D.
Technical Specifications
| Specification | PS24FX-C-D-N-D |
|---|---|
| Model / Part Number | PS24FX-C-D-N-D |
| Series | PowerScout FLEX 24 (24-channel, multi-circuit) |
| Channel Capacity | Up to 8 three-phase or 24 single-phase circuits; 2 voltage references |
| Service Type | Single Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) |
| Power | From L1 Phase to L2 Phase. 90-600 VAC RMS, CAT III, 50/60 Hz, 500 mA AC Max |
| Auxiliary Power Out | Unregulated 12 VDC, 200 mA, self-resetting fuse (requires 100 VAC minimum input) |
| AC Protection | 0.5 A fuse, 200 kA interrupt capacity |
| Voltage Channels | 90-346 VAC Line-to-Neutral, 600 V Line-to-Line, CAT III; two voltage reference inputs |
| Current Channels | 24 channels, 0.525 VAC max, 333.3 mV CTs, 0-4000 A depending on CT |
| Maximum Current Input | 150% of CT rating (mV CTs) to maintain accuracy; up to 4000 A with RōCoil CTs |
| Pulse Inputs | 4 inputs to a customer dry-contact pulse output; max pulse rate 10 Hz (50 ms min transition) |
| Measurement Type | True RMS using high-speed DSP with continuous sampling |
| Accuracy | 0.2% — ANSI C12.1-2024 Class 0.2; NIST traceable calibration |
| Resolution | 32-bit IEEE-754 single-precision floating point |
| Line Frequency | 50/60 Hz (45-65 Hz measurable range); measured L1-N |
| Waveform Sampling | 7.2 kHz continuous (no blind cycles) |
| Parameter Update Rate | 1.0 second |
| Measurements | Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import/Export/Net kWh, kVAh and kVARh, THD, Theta, Frequency — per phase and per Virtual Meter |
| Display | 4-line LCD with tri-color backlight |
| Communications Hardware | RS-485, Ethernet, and USB (USB for configuration only) |
| Supported Protocols | Modbus RTU, BACnet MS/TP, Modbus TCP or BACnet IP |
| Communication Rate | Modbus: 9600-115200 baud; BACnet: 9600-76800 baud |
| Max Communication Length | 1200 m at 100K bits/second or less |
| Alarm Output | Phase-loss / undervoltage (open collector, 30 VDC max) |
| Web Page Security | 2 levels of PIN protection (Read/Write or Read-Only) |
| Mounting | Panel mount / self-contained UL-Listed ABS enclosure with 1 in EMT conduit connections |
| High-Voltage Cover | TouchSSā™ high-voltage cover, IP30 |
| Enclosure | ABS plastic, 94-V0 flammability rating; 1 in EMT conduit connections |
| Dimensions | 33.7 x 25.1 x 8.0 cm (13.3 x 9.8 x 3.1 in) |
| Wire Connections | 12-28 AWG, 600 VAC; voltage connection must be #14 AWG or larger and 600 VAC rated |
| Operating Temperature | -20 to 60 °C (-4 to 140 °F) |
| Humidity | 5% to 95% non-condensing |
| Certifications | UL Listed (E186827, UL 61010-1 3rd Ed.; CSA C22.2 No. 61010-1); CE (LVD EN61010-1, EMC EN61326-1); RoHS 3 (IEC 63000:2018); ANSI C12.1-2024 Class 0.2; Made in USA; BAA and TAA compliant |
| Configuration Software | FLEXPoint™ (Windows 10 / 11) and FLEXPoint™ GO web server |
Documentation
- PDF PowerScout FLEX 24 Data Sheet
- PDF Installation, Wiring & Operator's Guide
- PDF FLEXPoint Software & Integration Guide
- PDF Commissioning Checklist
- PDF Quick Start Guide
Frequently Asked Questions
How many circuits can the PS24FX-C-D-N-D meter?
The PS24FX-C-D-N-D has 24 current channels and can meter up to 8 three-phase or 24 single-phase circuits across two voltage references, grouped however your site is organized using Virtual Meters.
What protocols does the PS24FX-C-D-N-D support?
The PS24FX-C-D-N-D supports Modbus RTU, BACnet MS/TP, Modbus TCP or BACnet IP, plus four digital pulse inputs, so it integrates with most BACnet or Modbus building management and energy systems.
Which current transformers work with the PS24FX-C-D-N-D?
The PS24FX-C-D-N-D accepts 333.3 mV DENT CTs — Solid Core, Split Core, and RōCoil™ (Rogowski) — including revenue-grade options, and measures up to 4000 A depending on the CT selected.
What is the form factor of the PS24FX-C-D-N-D?
The PS24FX-C-D-N-D is supplied as a UL-Listed ABS enclosure in the Enclosure configuration, measuring 33.7 x 25.1 x 8.0 cm (13.3 x 9.8 x 3.1 in).
Is the PS24FX-C-D-N-D revenue grade?
The PS24FX-C-D-N-D meets ANSI C12.1-2024 Class 0.2 revenue-grade accuracy, dependent on the CT selected, and ships with a NIST-traceable calibration.
Does the PS24FX-C-D-N-D connect to DENTCloud™?
Yes. The PS24FX-C-D-N-D is the DENTCloud™-enabled variant, factory-provisioned for direct connectivity to the subscription-free DENTCloud platform so authorized users can view real-time and historical data from any web browser.
Is the PS24FX-C-D-N-D Made in USA?
Yes. Per the DENT data sheet the PowerScout FLEX 24, including the PS24FX-C-D-N-D, is Made in USA and is marked BAA and TAA compliant.
Warranty
DENT Instruments, Inc. warrants that PowerScout Series instruments and accessories are free from substantial defects in material and workmanship under normal use, given proper installation and maintenance, for 5 years (60 months) from the invoice date.
More broadly, DENT Instruments promises that any product it sells is free from material defects in design, materials, or manufacturing for the period shown on that product's current data sheet, beginning from the date of manufacture. This warranty does not extend to ordinary wear and tear, or to normally replaceable components such as batteries and humidity sensor elements.
Coverage & Remedy
During the warranty period, DENT Instruments may, at its sole option, repair, replace, service, or credit any product found to be defective and returned freight prepaid by the buyer, at no charge to the buyer for the warranty repair or replacement. Refurbished material may be used. DENT covers ground shipping for advance warranty replacements; if the customer requests expedited shipping, the customer pays the difference.
The warranty remains in effect provided the product: (1) was installed, operated, and maintained properly; (2) has not been abused or misused; (3) has not been repaired, altered, or modified outside of DENT Instruments' authorized facilities; and (4) was not sold subject to other warranty terms specified at the time of sale.
Limitation & Disclaimer
This warranty replaces all other warranties, expressed or implied, including any warranties of merchantability and fitness for a particular purpose, and is the sole and exclusive remedy. In no event will DENT Instruments be liable for any special, incidental, or consequential damages or commercial losses, even if advised of the possibility. Correction of defects by repair, replacement, service, or credit at the seller's option constitutes fulfillment of all warranty obligations. All transactions are governed by the laws of the State of Oregon, U.S.A.
Warranty Service
To request warranty service, contact DENT Instruments Technical Support at 541.388.4774 or 800.388.0770, or email support@dentinstruments.com. A Returned Material Authorization (RMA) number is required before returning any product.
- Product Line:
- PowerScout FLEX
- Channels:
- 24
- Mounting:
- Enclosure
- Display:
- Yes
- Protocol:
- BACnet
- Protocol:
- Modbus
- Revenue Grade:
- Yes
- Country of Origin:
- USA
- DENTCloud: