Dent Instruments PS24HD-C-D-N-C : PowerScout 24 HD Multi-Circuit Power Submeter, Includes Enclosure and Display, Revenue Grade, BACnet or Modbus Protocol, CTEP Approval (Revenue CA)
Maximum Flexibility for Monitoring
The flexible design of the PowerScout 24 HD allows it to be configured for monitoring any combination of up to 8 three-phase or 24 single-phase electrical circuits across two separate voltages with revenue grade accuracy (ANSI C12.20-2010 Class 0.2). Equip the PowerScout 24 HD meter with any combination of DENT's split-core, solid-core, or RoCoil (Rogowski) CTs.
Easy Installation
Every PowerScout is line powered and designed to operate on a broad range of voltages, from 90-600VAC, and features two separate voltage inputs. Modbus or BACnet protocols are field-selectable and any combination of split-core or flexible R_Coil CTs can be used.
Configure the meter using the ViewPoint HD software utility and a direct USB connection prior to installation. Eliminate expensive trips back into the field: patented* PhaseChek™ Technology ensures proper CT-to-phase installation the first time.
If ordered with an enclosure, 1-inch EMT conduit connects easily to the enclosure housing - no drilling required.
Minimum Part Numbers, Maximum Features
Keep it simple: Don't fight with a long list of SKUs only to realize an important feature is missing. All PowerScout HD Series Meters are equipped with smart, standard features like the flexibility to switch between Modbus® or BACnet®, Ethernet or Serial (RS-485), or the ability to use any millivolt CT, including Rogowski coils, on any channel. When installed, the platform agnostic PowerScout HD Series meter easily integrates within connected products of any building management system (BMS) software, models equipped with BACnet® and Modbus® protocols and can be easily utilized with any system.
The PowerScout HD Series meters are not meant to be standalone energy recorders. They are designed to connect as a slave device to a data logger, Remote Terminal Unit (RTU), or building management host network.
Applications
- Data Center Monitoring
- Tenant Submetering (shopping malls, apartments, office space, etc)
- Net Metering (renewable energy applications, such as solar or wind)
- Commercial
- Retail
- Industrial
Technical
Service Type | Single Phase, Split Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) |
Power | From L1 Phase to L2 Phase. 90-600VAC RMS CAT III 50/60Hz, 500mA AC Max. Use of 12 volt auxiliary output requires 100 VAC minimum input voltage. |
AC Protections | 0.5A Fuse 200kA interrupt capacity |
Power Out | Unregulated 12VDC output, 200 mA, self-resetting fuse. |
Voltage Channels | 90-346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III. Two voltage reference inputs. |
Current Channels | 24 channels, 0.525 VAC max, 333 mV CTs, 0-4,000 Amps depending on CT |
Maximum Current Input | 150% of current transducer rating (mV CTs) to maintain accuracy. Measure up to 4000A with RōCoil CTs |
Measurement Type | True RMS using high-speed digital signal processing (DSP) with continuous sampling |
Line Frequency | 50/60 Hz (45-70 Hz measurable range). Measurement taken L1-N. |
Waveform Sampling | 1.8 kHz |
Parameter Update Rate | 1 second |
Measurements | Volts, Amps, kW, kVAR, kVA, aPF, dPF, kW demand, kVA demand, Import (Received) kWh, Export (Delivered) kWh, Net kWh, Import (Received) kVAh, Export (Delivered) kVAh, Net kVAh, Import (Received) kVARh, Export (Delivered) kVARh, Net kVARh, THD, Theta, Frequency. All parameters for each phase and element total |
Accuracy | 0.2% ANSI C12.20-2010 Class 0.2 |
Resolution | Values in IEEE-754 single precision floating point format (32 bit). |
Display | Optional 4-line display, tri-color backlight (PhaseChekTM) |
Alarm Output | User-configurable Phase Loss Alarm |
Pulse Inputs** | Two inputs. 3.3V sourcing voltage (current limited) to customer dry contact pulse output. Max pulse rate 10 Hz (50 mSec minimum transition time). |
Communications
Hardware | RS-485, Ethernet, and USB (for configuration only) |
Supported Protocols | Modbus RTU, BACnet MS/TP, Modbus TCP or BACnet IP |
Max Communication Length | 1200 meters with Data Range of 100K bits/second or less |
Communicaiton Rate (BAUD) | 9600 (Default), 19200, 38400, 57600, 76800, 115200 |
Data Bits | 8 |
Parity | None, Even, Odd |
Stop Bit | 2, 1 |
Termination | None provided |
Mechanical
Wire Connections | 12-28 AWG 600 VAC, Voltage connection must be #14 AWG or larger & 600 VAC rated |
Mounting | Panel Mount/Enclosure |
TouchSafe High Voltage Cover | IP30. Available with PS24 Enclosure & Plate Models |
Operating Temperature | -20° to 60°C (-4° to 140°F)** |
Humidity | 5% to 95% non-condensing |
Enclosure | ABS Plastic, 94-V0 flammability rating. Connections: 1” EMT conduit |
Enclosure Dimensions | (L) 33.7cm x (W) 25.1cm x (H) 8.0 cm (13.3” x 9.8” x 3.1”) |
Mounting Plate Dimensions | (L) 26.2cm x (W) 24.1cm x (H) 8.0 cm (10.3” x 9.5” x 3.1”) |
PCBA Dimensions | (L) 21.6cm x (W) 21.6cm x (H) 6.4 cm (8.5” x 8.5” x 2.5”) |
Datasheets
Warranty Statement
DENT Instruments, Inc. promises buyer that any product sold by DENT Instruments, Inc. shall be free from material defects in design, materials, or manufacturing for the period shown on the current data sheet for that product beginning from the manufacture date; provided, however, that the warranty shall not extend to ordinary wear and tear, or to normally replaceable components (e.g., batteries and humidity sensor elements). During the warranty period, DENT Instruments, Inc. may repair or replace (at its sole discretion) any product suffering from a warranty defect and returned freight prepaid by buyer, with no charge to buyer for any warranty repair or replacement. The warranty shall remain in full force and effect for said period, provided that the product: (1) was installed, operated, and maintained properly; (2) has not been abused or misused; (3) has not been repaired, altered, or modified outside of DENT Instruments’ authorized facilities; (4) has not been sold subject to other warranty terms specified at the time of sale. This warranty provides specific legal rights that may be varied by local laws.
POWERSCOUT SERIES INSTRUMENTS & ACCESSORIES
Seller warrants to Buyer that PowerScout Series instruments products and accessories or services are free from substantial defect in material and workmanship under normal use given prior installation and maintenance for the period of 5 years (60 months) after delivery.
LIMITATION OF WARRANTY
CORRECTION OF DEFECTS BY REPAIR, REPLACEMENT, SERVICE OR CREDIT WILL BE AT SELLER’S OPTION AND CONSTITUTE FULFILLMENT OF ALL OBLIGATIONS TO BUYER FOR BREACH OF WARRANTY.
Seller assumes no warranty liability with respect to defects in the product caused by: (a) modification, repair, installation, operation or maintenance of the product by anyone other than Seller or its agent, except as described in Seller’s documentation; or (b) the negligent or other improper use of the product.
Other manufacturers’ equipment purchased by Seller and resold to Buyer will be limited to that manufacturers’ warranty. Seller assumes no warranty liability for other manufacturers’ equipment furnished by Buyer.
No agent, distributor, or representative is authorized to make any warranties on behalf of Seller or to assume for Seller any other liability in connection with any Seller product or service.
DISCLAIMER OF WARRANTY
Buyer understands and agrees as follows:
THE ABOVE WARRANTY REPLACES ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, & ALL OTHER OBLIGATIONS OR LIABILITIES OF SELLER, INCLUDING ANY WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. ALL OTHER WARRANTIES ARE DISCLAIMED AND EXCLUDED BY SELLER.THE FOREGOING WILL BE THE SOLE AND EXCLUSIVE REMEDY WHETHER IN CONTRACT, TORT, OR OTHERWISE, & SELLER WILL NOT BE LIABLE FOR INJURIES OR DAMAGES CAUSED BY THE GROSS NEGLIGENCE OF SELLER. THIS LIMITATION APPLIES TO ALL SERVICES AND PRODUCTS DURING AND AFTER THE WARRANTY PERIOD.
LIMITATION OF REMEDIES
IN NO EVENT WILL SELLER BE LIABLE FOR ANY SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES OR COMMERCIAL LOSSES EVEN IF SELLER HAS BEEN ADVISED OF THE POSSIBILITY THEREOF.
- Supported Protocols:
- Modbus RTU, BACnet MS/TP, Modbus TCP or BACnet IP
- Meter Type:
- Multi-Circuit
- Mounting:
- Panel Mount/Enclosure
- Current Channels:
- 24