The Dwyer 1911-20 is the bare-switch version of the popular Series 1900, supplied without the standard conduit enclosure cover. The unit is intended for OEM panel integration or for factory installation in the optional weatherproof (-WP) or explosion-proof (-EXPL) housings. It covers a setpoint range of 4.0-20.0 in WC, switches 15 A at 120-480 VAC through an SPDT relay, and is built around Dwyer's force-motion amplifier mechanism for repeatable trip performance (+/-3%) at very low actuating pressures. Service is air and other non-combustible, compatible gases only.
WARRANTY
Key Features
Force-Motion Amplifier Mechanism
Dwyer-engineered internal linkage amplifies diaphragm motion, giving the snap switch more travel per unit of pressure change. Result: +/-3% repeatability even at actuating pressures as low as 0.07 in WC.
15 A Switch Rating
SPDT snap switch is rated 15 A at 120-480 VAC, 60 Hz - significantly heavier duty than typical HVAC pilot relays. Drive small motors, contactors, or alarm circuits directly without an interposing relay. Derate to 10 A for high cycle rates.
Bare-Switch Format
Ships without the standard conduit enclosure cover for OEM integration into customer-supplied control panels or for factory installation in the optional -WP weatherproof or -EXPL explosion-proof housings. Lower BOM cost when the enclosure is provided by the assembly.
One-Side Installation
Pressure ports, electrical conduit, and setpoint adjustment are all located on the same side of the housing. The switch can be installed in corners or tight spaces where a conventional pressure switch with rear connections will not fit.
Wide Service Envelope
Operating temperature -30 to 180 F (32 F minimum for non-dry air), 80% RH non-condensing, up to 6,560 ft altitude. Continuous overpressure rated 45 in WC, 10 psig surge - tolerant of typical HVAC transients.
UL/CSA/FM/CE Listed
Series 1910 and 1920 carry multi-agency approvals: UL listed, CSA certified, FM approved, and CE marked. Installation category III (transient overvoltage); pollution degree 2. Ready for use in code-listed control panels.
Technical Specifications
| Specification | Value |
|---|---|
| Model | 1911-20 |
| Operating Range | 4.0-20.0 in WC |
| Approx. Deadband at Min. Setpoint | 0.40 in WC |
| Approx. Deadband at Max. Setpoint | 0.50 in WC |
| Service | Air and non-combustible, compatible gases (not for natural gas or other combustibles) |
| Wetted Materials | Consult factory |
| Switch Type | 1 Form C relay, SPDT |
| Electrical Rating | 15 A @ 120-480 VAC, 60 Hz; resistive 1/8 HP @ 125 VAC, 1/4 HP @ 250 VAC, 60 Hz. Derate to 10 A for high cycle rates. |
| Repeatability | +/- 3% |
| Electrical Connections | 3 screw-type terminals: common (COM), normally open (NO), normally closed (NC) |
| Installation Category | III (transient overvoltage) |
| Pollution Degree | 2 |
| Process Connections | 1/8 in female NPT, front-mounted (high and low) |
| Enclosure | Less conduit enclosure (bare switch); 7/8 in conduit connection on body. Use with -WP or -EXPL housing, or integrate into customer panel. |
| Temperature Limits, Operating | -30 to 180 F (-34 to 82.2 C); 32 F minimum for non-dry air |
| Humidity Limit | 80% RH, non-condensing |
| Altitude Limit | 6,560 ft (2,000 m) max |
| Pressure Limit, Continuous | 45 in WC (11.2 kPa) |
| Pressure Limit, Surge | 10 psig (68.95 kPa) |
| Mounting Orientation | Diaphragm in vertical plane |
| Setpoint Adjustment | Slotted screw inside conduit enclosure (tamper-resistant) |
| Weight | 1 lb 4.5 oz (581 g) |
| Compliance | CE, UL, CSA, FM |
| Manufacturer Part Number | 1911-20 |
Documentation
Frequently Asked Questions
What pressure range does the 1911-20 cover?
Can the 1911-20 be used outdoors or in cold environments?
Is the 1911-20 rated for natural gas or other combustible gases?
What's the difference between the 1911-20 and the 1910-20?
What is the Dwyer force-motion amplifier and why does it matter?
How do I wire the bare switch?
- Brand:
- Dwyer
- Series:
- 1900
- Sub-Family:
- 1911
- Product Type:
- Compact Differential Pressure Switch (Bare, less Conduit Enclosure)
- Operating Range:
- 4.0-20.0 in WC
- Range Code:
- -20
- Deadband at Min Setpoint:
- 0.40 in WC
- Deadband at Max Setpoint:
- 0.50 in WC
- Service:
- Air, Noncombustible Gases (not natural gas)
- Switch Type:
- SPDT, 1 Form C Relay
- Reset Type:
- Automatic
- Electrical Rating:
- 15 A at 120-480 VAC, 60 Hz
- Repeatability:
- +/- 3%
- Process Connection:
- 1/8 in FNPT, Front
- Conduit Connection:
- 7/8 in (1/2 in NPT compatible)
- Conduit Enclosure:
- Less enclosure (bare switch)
- Pressure Limit (Continuous):
- 45 in WC, 11.2 kPa
- Pressure Limit (Surge):
- 10 psig, 68.95 kPa
- Temperature Range:
- -30 to 180 F, -34 to 82.2 C (32 F min for non-dry air)
- Humidity Limit:
- 80% RH non-condensing
- Altitude Limit:
- 6,560 ft, 2,000 m
- Installation Category:
- III
- Pollution Degree:
- 2
- Mounting Orientation:
- Diaphragm Vertical
- Setpoint Adjustment:
- Slotted screw inside enclosure (tamper-resistant)
- Certifications:
- CE, UL, CSA, FM
- Weight:
- 1 lb 4.5 oz, 581 g