Dwyer 605-11: Magnehelic Differential Pressure Indicating Transmitter, +/-0.25 in WC, Bidirectional, 4-20 mA 2-Wire Output, 4-Inch Analog Dial, +/-2% FS Electrical Accuracy

Dwyer

MSRP: $615.45
Your Price:  $490.05
(You save $125.40 )
(No reviews yet) Write a Review
SKU:
605-11
Condition:
New
Availability:
0 In Stock | Lead Time: 4 weeks
Adding to cart… The item has been added
SKU605-11
Pressure Range±0.25 in WC
Electrical Accuracy±2% FS
Output4–20 mA, 2-Wire
Local Display4″ Magnehelic® Dial
Max Pressure10 psi (68.95 kPa)

The Dwyer 605-11 Magnehelic® Differential Pressure Indicating Transmitter is a ±0.25 in WC (approximately ±62 Pa equivalent) bidirectional configuration of the Series 605 platform that combines the time-proven Magnehelic® mechanical dial gage with a 2-wire, 4–20 mA electronic transmitter in a single 4-inch instrument. The 605-11 measures pressure swings in both directions across the ±0.25 in WC span and delivers both a local analog reading and a linear loop signal simultaneously, so a technician walking the equipment room reads the value directly off the dial while the building automation system receives the same measurement — no parallel gage + transmitter pair and no isolation amplifier between the local indicator and the loop.

The 605-11 delivers ±2% FS electrical accuracy and ±3% FS mechanical accuracy. Power for the 605-11 comes from any 10–35 VDC supply through the rear-mounted screw terminal block, and the 605-11 drops into 4-inch panel cutouts originally drilled for a standard Magnehelic® gage — ordering with the optional -SS stainless bezel makes a one-for-one field upgrade without rework, so legacy gage installations get a BAS-compatible signal without a panel re-cut.

Best for

Building pressurization monitoring where pressure swings around zero (positive and negative), cleanroom envelope monitoring, isolation room pressure verification, and any HVAC application where directional pressure information matters as much as magnitude.

WarrantyCovered under Dwyer’s published Terms and Conditions of Sale. ZOT Supply is an authorized DwyerOmega distributor. Series 605 units are not field-repairable; if service is required, return shipping freight-prepaid to the factory is necessary.

Key Features

Dial Gage and 4–20 mA Transmitter in One

The 605-11 puts a Magnehelic® analog dial and a calibrated 2-wire 4–20 mA transmitter into the same 4-inch instrument, so the 605-11 gives a maintenance technician a direct visual reading while the controller upstairs sees the same measurement as a loop signal.

Time-Proven Magnehelic® Mechanism

Inside the 605-11 is the same magnetically-linked diaphragm-and-helix sensing mechanism that has driven the Magnehelic® gage line for decades — quick response and ±1% FS/year stability without recalibration drift.

±2% FS Electrical Accuracy

The 605-11 delivers ±2% FS electrical accuracy on its ±0.25 in WC range — well within the tolerance band for typical HVAC differential-pressure indication and BAS trending.

Simple 2-Wire 4–20 mA Loop

The 605-11 is a true 2-wire transmitter powered by any 10–35 VDC supply through the rear screw-terminal block, with a maximum 1250 Ω loop resistance — making the 605-11 a drop-in fit for nearly any BAS or PLC current-loop input without isolation amplifiers.

Magnehelic® Legacy Compatibility

Ordered with the optional -SS brushed-stainless bezel, the 605-11 matches the installation diameter of a standard Magnehelic® gage — existing 4-inch panel cutouts accept the 605-11 directly, so gage-only panels can be upgraded to a 4–20 mA signal point without re-cutting sheet metal.

Tamper-Resistant Field Calibration

Zero and span on the 605-11 are set with protected potentiometers driven by a supplied spanner-style key — not exposed knobs — so a verified 605-11 calibration stays put even in shared mechanical rooms with foot traffic.

Technical Specifications

SpecificationValue
Manufacturer Part Number605-11
SeriesDwyer Series 605 Magnehelic® Indicating Transmitter
Pressure Range±0.25 in WC (approximately ±62 Pa)
DirectionBidirectional
ServiceAir and non-combustible, compatible gases
Electrical Accuracy±2% FS (includes linearity, hysteresis, repeatability)
Mechanical Accuracy±3% FS
Long-Term Stability±1% FS/year
Maximum Pressure10 psi (68.95 kPa)
Operating Temperature20 to 120 °F (-6.67 to 48.9 °C)
Compensated Temperature Range32 to 120 °F (0 to 48.9 °C)
Thermal Effect±0.025% FS/°F (±0.045% FS/°C)
Power Requirements10–35 VDC (2-wire)
Output Signal4–20 mA
Loop Resistance0–1250 Ω max
Current Consumption38 mA max
Zero & Span AdjustmentProtected potentiometers (spanner key supplied)
Electrical ConnectionsScrew terminal block (rear)
Process Connections1/8 in female NPT (high and low)
MountingPanel mount or surface mount
Mounting OrientationDiaphragm vertical (required for stated accuracy)
Dial Face Size4 in (101.6 mm)
Outside Diameter5 in (127 mm); 4-3/4 in (120.7 mm) with -SS bezel
Depth2-11/16 in (68.3 mm); 2-21/32 in (67.5 mm) with -SS bezel
Weight1 lb 12.6 oz (811 g)
ComplianceCE
Options Available-SS (304 brushed stainless steel bezel), -NIST (traceable calibration certificate)

What’s In the Box

Each 605-11 ships with
  • Dwyer Series 605 Magnehelic® indicating transmitter (605-11)
  • Mounting ring and split snap ring for panel mounting
  • (4) 6-32 x 1-1/4 in screws for panel mounting
  • (3) 6-32 x 5/16 in screws for surface mounting
  • (2) Tubing-to-1/8 in NPT adapters
  • (2) 1/8 in NPT pipe plugs (for unused pressure ports)
  • Spanner-style adjustment key (for protected zero/span potentiometers)

Documentation

Frequently Asked Questions

What is the pressure range of the 605-11?

The 605-11 is a bidirectional indicating transmitter with a ±0.25 in WC range. Both the analog dial and the 4–20 mA loop scale linearly across the full bidirectional span, with the loop signal centered at the midpoint of the range.

Does the 605-11 have to be mounted vertically?

For the rated accuracy, yes — the 605-11 is factory-calibrated with the diaphragm in the vertical position and should be installed face-vertical. Non-vertical orientation will shift the zero and degrade the published accuracy of the 605-11; consult Dwyer if a non-standard orientation is required.

What output signal does the 605-11 provide?

The 605-11 outputs a 2-wire 4–20 mA current signal linearly proportional to the ±0.25 in WC range, with 4 mA at zero (or the negative end on bidirectional models) and 20 mA at full scale. Maximum loop resistance is 1250 Ω at 35 VDC.

Can the 605-11 directly replace a Magnehelic® gage in an existing panel?

Yes — ordering the 605-11 with the optional -SS (304 brushed stainless steel) bezel makes the installation diameter compatible with the standard Magnehelic® gage cutout, so an existing 4-inch panel hole accepts the 605-11 directly. This is the intended field-upgrade path for gage-only panels that need to feed a 4–20 mA loop to the BAS.

What kind of power supply does the 605-11 need?

Any 10–35 VDC supply with at least 40 mA capacity per 605-11. The 605-11 is a 2-wire transmitter and is not designed for AC voltage operation — applying AC will cause permanent damage not covered by warranty.

Can multiple 605-11 units share one power supply?

Yes — a single DC supply can power several 605-11 transmitters in parallel as long as the supply has enough current. Minimum required current is the number of 605-11 units multiplied by 20 mA.

Can the 605-11 drive a 1–5 V receiver input instead of 4–20 mA?

Yes — insert a 250 Ω resistor (commonly 249 Ω 1/2 W ±1% metal film) in series with the 605-11 current loop, in parallel with the receiver input at the panel end. The voltage drop across that resistor converts the 4–20 mA loop into a 1–5 V input.

How is the 605-11 field-calibrated?

The 605-11 ships factory-calibrated for 4 mA at zero and 20 mA at full scale. To re-verify: insert a milliammeter in series with the loop, vent both ports and set the dial zero with the slotted screw at center-bottom, apply 0.25 in WC (positive) to the HI port, and use the supplied spanner key on the protected SPAN potentiometer for 20 mA then on ZERO for 4 mA. The two controls are slightly interactive on the 605-11 — iterate two or three times.

Brand:
Dwyer
Series:
605 Magnehelic
Product Type:
Indicating Transmitter
Pressure Range Class:
Bidirectional Symmetric
Pressure Range:
+/-0.25 in WC
Direction:
Bidirectional
Output Signal:
4-20 mA
Display:
Analog Dial
Accuracy Class:
Mid (0.5 to 2% FS)
Mounting:
Panel/Surface
Probe:
No Probe