Dwyer 626-12-CB-P1-E5-S1 : Industrial Pressure Transmitter, Range 0-200 psig, 0.25% Full Scale Accuracy, Conduit Box Housing, 1/4" Male NPT Process, 1/2" Female NPT Conduit, 4-20 mA Signal Output, NEMA 4X (IP66)
The Series 626 Industrial Pressure Transmitters are engineered for accuracy and dependability in the most demanding industrial environments. These transmitters feature a high-precision 0.25% full-scale piezo-resistive sensor housed in a durable NEMA 4X (IP66) stainless steel enclosure, with an optional cast aluminum conduit housing available for added versatility. Designed for flexibility, the Series 626 supports absolute and gauge pressure measurements, with a range of outputs, process connections, and electrical terminations to fit your specific application. Its corrosion-resistant 316L stainless steel wetted parts ensure compatibility with a wide variety of media, from hydraulic oils to aggressive chemicals, making it an essential tool for precision pressure measurement.
Applications:
- Booster stations
- Pumping systems
- Irrigation equipment
- PTO systems
- Submersible pump control
Specifications
Service: | Compatible gases and liquids. |
Wetted Parts: | Type 316L SS. (Consult factory for additional options) |
Accuracy: | 0.25% FS, 0.20% RSS |
Temperature Limits: | 0 to 200°F (-18 to 93°C). |
Compensated Temperature Range: | 0 to 175°F (-18 to 79°C). |
Thermal Effect: |
±0.02% FS/°F (includes zero and span). |
Pressure Limit: | See table on catalog page. |
Power Requirements: | 10-30 VDC (for 4-20 mA, 0-5, 1-5, 1-6 VDC outputs); 13-30 VDC (for 0-10, 2-10 VDC outputs); 5 VDC ±0.5 VDC (for 0.5-4.5 VDC ratiometric output). |
Output Signal: | Selectable 0-5, 1-5, 0-10, 2-10 VDC |
Response Time: |
300 ms. |
Loop Resistance: |
0-1000 Ω max. R max = 50 (Vps-10) Ω (4-20 mA output), 5 KΩ min (0-5, 1-5, 0.5-4.5 VDC output), 15 KΩ min (1-6, 0-10, 2-10 VDC output). |
Current Consumption: | 38 mA maximum (for 4-20 mA output); 10 mA maximum (for 0-5, 1-5, 1-6, 0-10, 2-10, 0.5-4.5 VDC output); 140 mA maxumum |
Enclosure Rating | NEMA 4X (IP66). |
Mounting Orientation: | Mount in any position. |
Weight: | 10 oz (283 g). |
Compliance | Standard: CE; Optional: NSF/ANSI 61/372, ANSI/UL 218, ANSI/UL 508, NEPA 20. |
Datasheets