Dwyer DH-006 : Digihelic Differential Pressure Controller, 0 to 5 in w.c., 4-20 mA + dual SPDT relays + Modbus, LCD gage

Dwyer

MSRP: $890.00
Your Price:  $708.66
(You save $181.34 )
(No reviews yet) Write a Review
SKU:
DH-006
Condition:
New
Availability:
72 In Stock
Adding to cart… The item has been added

Model

DH-006

Range

0 to 5 in w.c.

Accuracy

±0.5% FS

Output

4-20 mA

Relays

2 SPDT, 8 A

Comms

Modbus RS485

Dwyer DH-006 Digihelic Differential Pressure Controller

The Dwyer DH-006 is a 3-in-1 Series DH Digihelic® controller that combines a digital display gage, two control relays, and a scalable 4-20 mA transmitter in a single 1/8 DIN panel instrument. The DH-006 is factory ranged for 0 to 5 in w.c. (1245 Pa full scale) and holds ±0.5% full-scale accuracy at 77°F (25°C), including hysteresis and repeatability. In addition to pressure, the DH-006 can be field-configured for pressure, air velocity, and volumetric flow, with a square-root output that tracks the actual airflow curve. Pressure is displayed in field-selectable engineering units: 5.000 in w.c., 1245 Pa, .4167 ft w.c., 127.0 mm w.c., 12.70 cm w.c., .1806 psi, .3678 in Hg, 9.342 mm Hg, 12.45 mbar, 1.245 kPa, 12.45 hPa, 2.890 oz/in².

Best For

  • Duct air velocity and SCFM volumetric flow
  • Industrial oven and process air flow
  • Filter and air-handler status monitoring
  • Clean room, building, and isolation room pressurization
  • Fume hood and exhaust pressure monitoring
  • Damper and fan control with dual set points

Warranty

The Dwyer DH-006 is backed by the Dwyer 2-year limited warranty against defects in materials and workmanship. Factory calibration (-FC) and NIST-traceable calibration (-NIST) certificates are available as ordering options.

Key Features

3-in-1 Instrument

Replaces a separate gage, switch, and transmitter with one device, reducing inventory, panel space, and installation time.

Dual SPDT Control Relays

Two 8 A relays with independent, keypad-adjustable on/off set points let you run two-stage control or set point plus alarm logic.

Scalable 4-20 mA Transmitter

The current output is field-scaled with POL/POH so 4 mA and 20 mA map to any reading inside the unit’s range.

Modbus RTU over RS485

9600 baud Modbus RTU lets the controller read and write to a BAS or PLC; up to 128 units can share one daisy-chained bus.

Square-Root Flow Extraction

Velocity and flow modes apply true square-root extraction so SCFM and FPM readings track the real airflow curve when used with a pitot or flow station.

Universal Power Input

Accepts 100-240 VAC or 24 VDC, so the same unit drops into line-powered or 24 VDC control-panel applications.

Technical Specifications

ModelDH-006
Operating Range0 to 5 in w.c. (1245 Pa full scale)
Operating ModesPressure, velocity (SFPM, m/s), and volumetric flow (SCFM, m³/h)
Velocity Range0 to 8954 SFPM / 0 to 45.48 m/s
ServiceAir and non-combustible, compatible gases
Accuracy±0.5% FS at 77°F (25°C), incl. hysteresis and repeatability
Stability< ±1% per year
Pressure (Overpressure) Limit5 psi for this model
Temperature Limits32 to 140°F (0 to 60°C)
Thermal Effect0.020%/°F (0.036%/°C) from 77°F (25°C)
Output Signal4-20 mA DC into 900 Ω max, scalable
Display4-digit LCD, 0.4 in height; LED set point & alarm indicators
Control Relays2 SPDT, 8 A at 240 VAC resistive
Serial CommunicationsModbus® RTU, RS485, 9600 baud, 8-N-1, address 1-247
Power100-240 VAC (50-400 Hz) or 132-240 VDC; or 24 VDC ±20%
Power Consumption7 VA max (high voltage); 130 mA max at 24 VDC
Response Time250 ms (dampening = 1)
Process ConnectionsCompression fitting for 1/8 in ID x 1/4 in OD tubing; optional barbed fitting for 3/16 in ID (-B)
HousingABS plastic, UL 94 V-0
Enclosure RatingFace designed to meet NEMA 4X (IP66)
Mounting1/8 DIN panel, horizontal orientation; cutout 1.772 x 3.620 in (45 x 92 mm)
Weight14.4 oz (408 g)
Agency ApprovalsUL Listed, cUL Listed (File E83725), CE

Documentation

Frequently Asked Questions

What pressure range does the Dwyer DH-006 cover?

The DH-006 is factory ranged for 0 to 5 in w.c. (1245 Pa full scale). The 4-digit display and 4-20 mA output are both scaled to this range.

Can the DH-006 control equipment on its own?

Yes. The DH-006 has two built-in SPDT relays rated 8 A at 240 VAC, each with an independent keypad-set turn-on and turn-off point, so it can switch fans, dampers, or alarms without an external controller.

Does the DH-006 support BAS integration?

Yes. The DH-006 provides Modbus® RTU over RS485 at 9600 baud and a scalable 4-20 mA analog output, so it integrates with most building automation and PLC systems.

Can the DH-006 measure air velocity and flow?

Yes. The DH-006 can be configured for velocity (up to 8954 SFPM) and volumetric flow (SCFM / m³/h). It applies square-root extraction and accepts a K-factor for pitot tubes, plus round or rectangular duct dimensions.

What power input does the DH-006 require?

The DH-006 accepts either 100-240 VAC (50-400 Hz) / 132-240 VDC high-voltage power or 24 VDC low-voltage power, making it suitable for both line-powered and 24 VDC control-panel installations.

Brand:
Dwyer
Series:
Digihelic
Product Type:
Differential Pressure Controller
Pressure Range:
0 to 5 in w.c.
Bidirectional:
No
Output Signal:
4-20 mA
Control Relays:
Dual SPDT
Communication:
Modbus RTU RS485
Display:
Digital LCD
Mounting:
1/8 DIN Panel