Functional Devices RIB013P : Enclosed Power Relay, 20 Amp Contact Rating, Relay Contact Type: 3PST-N/O, 120 Vac Coil Voltage, NEMA 1 Housing
SPECIFICATIONS
# Relays & Contact Type: One (1) 3PST Continuous Duty Coil
Expected Relay Life: 10 million cycles minimum mechanical
Operating Temperature: -30 to 140° F
Humidity Range: 5 to 95% (noncondensing)
Operate Time: 20ms
Relay Status: LED On = Activated
Dimensions: 4.00" x 4.00" x 1.80" with .50" NPT Nipple
Wires: 16", 600V Rated
Approvals: UL Listed, UL916, UL864, C-UL California State Fire Marshal, CE, RoHS UL
Housing Rating: Accepted for Use in Plenum, NEMA 1
Gold Flash: No
Override Switch: No
Contact Ratings:
20 Amp Resistive @ 300 Vac, 28 Vdc 20 Amp Ballast @ 277-480 Vac
Not rated for Electronic Ballast
15 Amp Resistive @ 600 Vac
770 VA Pilot Duty @ 120 Vac, 1 Phase 1158 VA Pilot Duty @ 240 Vac, 1 Phase 1110 VA Pilot Duty @ 277 Vac, 1 Phase 1640 VA Pilot Duty @ 480 Vac, 1 Phase 1466 VA Pilot Duty @ 240 Vac, 3 Phase 2112 VA Pilot Duty @ 480 Vac, 3 Phase Heavy Pilot Duty @ 600 Vac
7.5 HP @ 480 Vac, 3 Phase
5 HP @ 240 Vac, 3 Phase
3 HP @ 480-600 Vac, 1 Phase
2 HP @ 240-277 Vac, 1 Phase
1 HP @ 120 Vac, 1 Phase
Coil Current: 154 mA @ 120 Vac
Coil Voltage Input: 120 Vac ; 50-60 Hz Drop Out = 35 Vac Pull In = 85 Vac
Notes: Order Normally Closed by adding “-NC” to end of model number
- Mounting:
- Enclosed
- Number of Relays:
- 1
- Relay Contact Type:
- 3PST-N/O
- Relay Coil Voltage:
- 120 Vac
- Contact Ratings:
- 20 Amp