Functional Devices RIB21CDC-RD : Dry Contact Relay, 10 Amp SPDT, Class 2 Dry Contact Input, 120-277 Vac Power Input, Red Housing
Product Features
- Prepackaged for quick and easy installation
- Provides low-voltage (Class2) power needed to activate the relay (self-powered) by closing the dry contact input
- Activated by a wide range of dry contacts such as thermostats, switches, other relays, solid-state switches, etc.
- Power to energize the relay can be brought to the relay on a separate pair of wires along with the control output of the controller, or can be a local power source near the relay
- Relay contacts are isolated from the input power and the dry contact input, so they can be wired to switch any other power-load or low-voltage load (see specifications for contact ratings)
SPECIFICATIONS
# Relays & Contact Type: One (1) SPDT Continuous Duty Coil
Expected Relay Life: 10 million cycles minimum mechanical
Operating Temperature: -30 to 140° F
Humidity Range: 5 to 95% (noncondensing)
Operate Time: 1.8 Seconds
Relay Status: LED On = Activated
Dimensions: 1.70" x 2.80" x 1.50"with .50" NPT Nipple
Wires: 16", 600V Rated
Approvals: UL Listed, UL916, C-UL, CE, RoHS
Housing Rating: UL Accepted for Use in Plenum, NEMA 1
Gold Flash: No
Override Switch: No
Contact Ratings:
10 Amp General Use @ 277 Vac
10 Amp Resistive @ 30 Vdc (N/O)
7 Amp Resistive @ 30 Vdc (N/C)
1/2 HP @ 125 Vac
1 HP @ 250 Vac
1/4 HP @ 277 Vac
470 VA Pilot Duty @ 125 Vac
770 VA Pilot Duty @ 250 Vac
Power Input:
50 mA @ 240 Vac Max.
Notes: