Functional Devices RIBD02BDC : Dry Contact Time Delay Relay, 20 Amp SPDT, Class 2 Dry Contact Input, 208-277 Vac Power Input, NEMA 1 Housing

Product Features

  • Prepackaged for quick and easy installation
  • Provides low-voltage (Class2) power needed to activate the relay (self-powered) by closing the dry contact input
  • Activated by a wide range of dry contacts such as thermostats, switches, other relays, solid-state switches, etc.
  • Power to energize the relay can be brought to the relay on a separate pair of wires along with the control output of the controller, or can be a local power source near the relay
  • Relay contacts are isolated from the input power and the dry contact input, so they can be wired to switch any other power-load or low-voltage load (see specifications for contact ratings)

SPECIFICATIONS

# Relays & Contact Type: One (1) SPDT Continuous Duty Coil
Expected Relay Life: 10 million cycles minimum mechanical
Operating Temperature: -30 to 140° F
Humidity Range: 5 to 95% (noncondensing)
Operate Time: 18ms after time delay
Relay Status: Red LED On = Activated
Time Delay Status: Pink LED FLASHING = Timing
Timing Mode: Selectable: Delay On Make, Delay On Break, or Delay On Make and Break
Timing Range: 1-30 Seconds or 1-30 Minutes
Timing Adjustment: 3 pin header w/jumper for sec/min and single turn potentiometer for timing adjustment within range
Dimensions: 4.00" x 4.00" x 1.80"with .50" NPT nipple
Wires: 16", 600V Rated
Approvals: UL Listed, UL916, C-UL, CE, RoHS
Housing Rating: UL Accepted for Use in Plenum, NEMA 1
Gold Flash: No
Override Switch: No

Contact Ratings:
20 Amp Resistive @ 277 Vac
20 Amp Ballast @ 277 Vac
16 Amp Electronic Ballast @ 277 Vac (N/O)
10 Amp Tungsten @ 120 Vac (N/O)
770 VA Pilot Duty @ 120 Vac
1,110 VA Pilot Duty @ 277 Vac
2 HP @ 277 Vac
1 HP @ 120 Vac

Power Input:
62 mA @ 208-277 Vac (RIBD02BDC)


Notes:

  • Dry Contact Input Operation:
    Mode A&C: Close White/Red wire to White/Blue wire to start timing. Relay will activate after timing sequence has ended.
  • Mode B&C: Open White/Red and White/Blue wires to start timing. Relay will deenergize after timing sequence has ended.
  • If more than one dry contact RIB® shares a single dry contact input, White/Blue must be common
  • Changing min/sec or mode while unit is running will reset the unit (de-energize the relay and turn off the timer). Once the dry-contact input is opened the unit will function as normal again
  • If the unit is powered up with the dry-contact input closed, the unit will begin timing (MODE A and MODE C) or energize the relay (MODE B).